IMDTouchKnowledge BaseShop main store

Troubleshooting

Why a C-more EA9 fails to reach a Do-more PLC through an ECOM100

HMI and touchscreens Published 9 min read

Short answer

A C-more EA9 reaches a Do-more PLC through an ECOM100 when the panel driver is the Do-more Ethernet protocol pointed at the ECOM100's own address, every device keeps a unique four-octet IP, and the masks put both nodes in one calculated subnet. Most failures are duplicate addresses or a wrong protocol target, not the driver family.

On this page
  1. Why does a C-more EA9 fail to reach a Do-more PLC through an ECOM100?
  2. Which protocol and target address does the EA9 driver need?
  3. Can the EA9 sit on a different subnet than the DM1E embedded port?
  4. Example: do 192.168.0.20 and 192.168.3.40 share a subnet under 255.255.255.0?
  5. How do I prove no device holds a duplicate IP address?
  6. What ECOM100 firmware does the Do-more Ethernet driver need?
  7. How do I test the ECOM100 path without disturbing the machine network?
  8. Why does the link still fail after addresses, mask and firmware check out?
  9. Questions asked

A C-more EA9 talks to a Do-more H2-DM1E through an ECOM100 as soon as three things hold: the panel driver is the Do-more Ethernet protocol, its target is the ECOM100's own address rather than the CPU's embedded port, and every device keeps a unique IP with masks that put the panel and the module in one calculated subnet. In one recorded commissioning, the link came up only after the module firmware went to 4.0.2120, the mask moved to 255.255.0.0, and both devices were re-addressed — three changes at once, with a duplicate address still unconfirmed. Work the checks in the order below and the link comes up without guessing.

Why does a C-more EA9 fail to reach a Do-more PLC through an ECOM100? #

The failure is almost never the driver family: the EA9's Do-more Ethernet protocol reaches N, R and C memory through an ECOM100, and the three checks that decide the link are the protocol selection, the target address, and unique addressing with agreeing masks.

An ECOM100 slotted beside the DM1E is a second, independent Ethernet interface. Frames that arrive on it reach the controller's memory, but they are not routed onward to the embedded port, and frames addressed to the embedded port never appear on the module. The panel must therefore speak to the interface its cable actually touches. Recorded installations put C-more panels on an H2-DM1E through a single ECOM100 and hold, so the pairing itself works; what failed at first was addressing. Rank the suspects the same way:

  • wrong protocol or target: the driver is not Do-more Ethernet, or it still points at the embedded port after the cable moved;
  • subnet mismatch: a mask that calculates the other device as off-network on a cable with no router;
  • duplicate address: two devices answering for one IP;
  • stale module firmware: a revision that predates C-more targeting on this protocol.

Which protocol and target address does the EA9 driver need? #

Set the PLC connection in the C-more programming software to the Do-more Ethernet driver and enter the ECOM100's IP address as its target — never the DM1E's embedded-port address — because the panel can only reach the interface its cable actually touches.

The panel's own IP address travels with the project too, so after any re-addressing read it back from the panel and match it against the stored value; the article on where to save C-more panel IP settings in the project explains that storage. Then audit the screens: every numeric display, push button and alarm taking part in the test must reference this connection definition, not one left over from the embedded-port trial.

Two protocol facts prevent the classic dead ends. Do-more Ethernet and Modbus TCP are different application protocols even on the same wire, so a successful ping proves reachability, never the driver. And the embedded port is busy serving Terminator I/O and Modbus TCP/IP devices; it is not the door the panel should knock on from its own cable. When the link is up, the driver reads and writes the same N, R and C memory the embedded port serves — one controller, two doors.

Can the EA9 sit on a different subnet than the DM1E embedded port? #

Yes — the split is the whole point of the module — but on a cable with no router the two addresses must fall in one calculated subnet, and for 192.168.0.x against 192.168.3.x the mask that does it is 255.255.0.0.

The split is worth keeping: the embedded port carries the machine I/O traffic — Terminator I/O racks and the Modbus TCP/IP devices — and the module carries the operator.

Interface Serves Recorded plan
DM1E embedded port Terminator I/O and Modbus TCP/IP devices 192.168.0.x
ECOM100 the EA9 on its own cable 192.168.3.x

Two plans work, and you must commit to one before touching the panel. With no router between the two cables, set one mask both ends share that gathers both ranges into a single calculated network — 255.255.0.0 in the recorded case. Reachability returns immediately, but the ranges stay one logical network, so keep them unbridged if separation is the goal. With a router in place, keep 255.255.255.0 on both ranges and set a gateway at each end. A gateway cannot substitute for the router: peers inside one calculated subnet never use a gateway at all, and a gateway entry cannot repair two ranges that the mask divides.

Example: do 192.168.0.20 and 192.168.3.40 share a subnet under 255.255.255.0? #

No — under a 255.255.255.0 mask the third octet belongs to the network, so 192.168.0.20 and 192.168.3.40 calculate to different networks and cannot exchange frames without a router, while the same two addresses fall together under 255.255.0.0.

Take an ECOM100 at 192.168.3.40 and an EA9 at 192.168.0.20 — example hosts in the two ranges from the recorded case. The test is a bitwise AND of each address with each candidate mask, octet by octet:

  • 192.168.0.20 AND 255.255.255.0 = 192.168.0.0
  • 192.168.3.40 AND 255.255.255.0 = 192.168.3.0 — two networks, direct delivery fails
  • 192.168.0.20 AND 255.255.0.0 = 192.168.0.0
  • 192.168.3.40 AND 255.255.0.0 = 192.168.0.0 — one network, direct delivery works

The third octet is the hinge: 255.255.255.0 keeps it in the network portion, so 0 and 3 separate the devices; 255.255.0.0 pushes it into the host portion, so they pair. Decision: no router between panel and module means the wide mask on both ends; a kept 255.255.255.0 means moving the panel into 192.168.0.x or installing a router.

How do I prove no device holds a duplicate IP address? #

Treat uniqueness as a commissioning test, not an assumption: compare all four octets of the panel and module addresses, then disconnect each device in turn and confirm its address stops responding — a reply from a disconnected address means another device owns it.

The commissioning case closed with a written suspicion that the addresses may have been identical, which is exactly why this is a test. Conflicting devices answer address-resolution requests at unpredictable moments, so the link comes up after a power cycle and dies again as caches age out — that on-off pattern is the signature, and chasing it as a firmware bug wastes a shift. The disconnect test costs five minutes per device: unplug the EA9, query the address it held from a laptop on the same segment, and a reply convicts an unknown second owner. Unplug the module and repeat for its address.

The same trap has an established name elsewhere, and the article on the duplicate controller IP error in a CODESYS system shows how a second owner hijacks a fixed address. The wrong-interface variant, where the address is held by the path you did not intend, is the subject of the article on a PC that fails to reach an HMI when Wi-Fi owns its address.

What ECOM100 firmware does the Do-more Ethernet driver need? #

The ECOM100 firmware history records the revision that made the module targetable by a C-more panel running the Do-more Ethernet protocol, and the commissioning case closed its fault with module firmware 4.0.2120.

The manufacturer's revision history for the ECOM100 family lists the additions in order: PEERLINK support for integration with Do-more controllers, then the change that lets a C-more panel using the Do-more Ethernet driver target the module. Below that revision the module does not answer the panel on this protocol, and no mask or panel setting changes that. Read the running revision with the module's setup utility, NetEdit, and update from the same place; the ECOM100 setup guidance recommends the update whenever the controller's firmware predates the module revision. Take firmware only from the module manufacturer's own support downloads.

One discipline from the recorded case: it closed with the firmware update, the mask and the addresses all changed in one session, so no single cause was ever isolated. Treat the updated revision as a working revision, not proof that firmware was the guilty layer, and re-walk the other three checks after any update.

How do I test the ECOM100 path without disturbing the machine network? #

Build a two-node segment first — panel and module on one cable with no switch — and use the EA9-to-embedded-port test only as a baseline you disconnect afterwards, because every device you leave attached is another possible address owner.

Schedule these steps for a window when nobody depends on the panel's displays, because the tests deliberately take them offline.

  1. Record the embedded-port address, the ECOM100 address, the EA9 address, every mask and gateway, and which cable feeds which port.
  2. Connect the EA9 to the embedded port's switch and prove the project and driver reach the controller — then disconnect it. That is a baseline, not the commissioning.
  3. Return the EA9 to its own cable at the ECOM100, power both devices, and check link indication at both ends. No link means a cable or jack fault, which no IP setting repairs.
  4. Read the ECOM100 address back from NetEdit and set the driver target to exactly that value, octet for octet.
  5. Apply one mask plan from the subnet section to both ends and leave the gateway fields empty on a router-less segment.
  6. Power-cycle the panel and watch the link re-establish itself; a connection that never survives a restart is not commissioned.

Work the four checks in order — protocol target, calculated subnet, four-octet uniqueness, module firmware — and each remaining failure points at one specific layer: a dead cable shows no link LEDs, a wrong driver times out on a live link, and a hidden duplicate reappears after a reboot.

Map the remaining symptom to its layer and act:

  • no link indication at either end: replace the cable and rerun the two-node test before touching software;
  • link up, panel times out: confirm the driver is Do-more Ethernet and its destination equals the address read back from the module;
  • link up, target right, still timing out: apply the mask decision from the worked example to both ends;
  • link survives a power cycle and dies later: run the disconnect test on both devices until every address answers for exactly one owner;
  • module below the revision its history lists for C-more targeting: update the firmware from the manufacturer, then re-walk the checks.

When the link finally holds but values crawl instead of jump, the connection work is finished and the fault has moved to polling cadence — the article on why HMI point updates run slow on an Ethernet PLC link takes it from there. Restated as the decision: Do-more Ethernet driver, the module's address as target, four unique octets, one shared calculated subnet or a real router, module firmware at the listed revision — and the EA9 reaches the N, R and C memory through its own door while the I/O network never sees it.

Questions asked

Can two C-more panels share one ECOM100?

Yes. The recorded working installation had an EA9 and an EA7 both talking to an H2-DM1E through one ECOM100 on the Do-more Ethernet protocol. Give each panel its own unique IP address and its own driver entry pointed at the module's address, and apply the same mask discipline on both panels.

Where do I read and update the ECOM100 itself?

The module's setup utility is where its IP address and firmware revision live, and the same dialog runs the firmware update; the module maker's setup guidance recommends updating when the controller's firmware predates the module revision. Get firmware only from the module manufacturer's own downloads, and record the revision you installed.

How can the EA9 raise an alarm when the DM1E's Ethernet I/O rack goes offline?

Read the $EthIOMaster.Error member in the Do-more program instead of relying on ST153. ST153 stays off when the remote rack is configured as optional, and when 'CPU remains in RUN mode on slave error' is disabled the CPU leaves RUN before the HMI could see the bit. $EthIOMaster.Slave0Error reports the last error code.

Do I need a crossover cable for the direct EA9-to-ECOM100 link?

The recorded working link used a simple crossover cable with no switch, but the point of the test is one cable between exactly two nodes. Use any known-good cable that raises link indication at both ends; if one end stays dark on a straight cable, swap to a crossover before changing software settings.

Keep reading

  • How-to

    Where to save C-more panel IP settings in the project

    The C-more project does store the panel's IP address and subnet mask: enter them under Setup > Touch Panel Network > Ethernet Port and save the project. That entry is a record, not a lock — the panel's System menu can still change the live values — and it is separate from the PLC destinations, so a controller address change still means editing each affected project and re-transferring it to every panel.

    HMI and touchscreens

  • Troubleshooting

    Why EasyBuilder Asks for a Tag CSV for a Mitsubishi Q PLC

    EasyBuilder asks for a tag CSV because the selected Mitsubishi driver is the label-based one, and GX Developer cannot export labels in that format - its converter refuses label-based projects. Switch the project to the Q-series Ethernet driver and address D, X and Y devices directly, with no CSV at all. If you want symbolic names, open the Q project in GX Works2 and export the label CSV from there.

    HMI and touchscreens

  • Troubleshooting

    Why an HMI Fails to Talk to an FX2n PLC Over 232-BD

    Moving a value into D8120 only sets the serial format — the link still fails on a wrong driver, an inactive PLC configuration or a miswired cable. Set the format once, through the PLC parameter settings in GX Works or GX Developer or one deliberate D8120 write, match the driver's framing at both ends, then prove the FX2N-232-BD cable pin by pin, in that order.

    HMI and touchscreens