Troubleshooting
Why a PanelView 550 will not show up for a DH-485 download
Short answer
Delete both RSLinx drivers so COM1 belongs only to the 1747-PIC/AIC+ driver at station 0 and 19,200 baud, then browse RSWho: a DF1 driver holding the same COM port is what hides the node-2 PanelView 550 from a PanelBuilder32 download. Confirm the fix with the isolated PC-to-PIC-to-SLC test before rebuilding the network.
On this page
The PanelView 550 is not the fault; the PC is. On this job the terminal at node 2 never appeared in the PanelBuilder32 download list while the DF1 driver reached the SLC 5/03, because two RSLinx drivers — AB_PIC-1 and AB_DF1-1 — were both assigned to COM1, and a physical serial port serves only one active driver. Delete both drivers, restart RSLinx, configure only the 1747-PIC/AIC+ driver at station 0 and 19,200 baud, and the browse returns node 1 and node 2. The numbers below rule out addressing and baud first, and the isolated PC-to-converter-to-SLC test proves the converter path before the network goes back together.
The setup that failed #
| Piece | Confirmed configuration |
|---|---|
| Terminal | PanelView 2711-K5A2, Series H, FRN 4.41; DH-485 node 2 |
| Controller | SLC 5/03, 1747-L532 Series D, processor revision 4; 1747-OS302 Series B, FRN 10; DH-485 node 1 |
| PC interface | 1747-PIC Series A on COM1; station 0; maximum station 31 |
| Software | PanelBuilder32 03.81.00 build 316; RSLinx Classic Lite 2.51.00.21 |
| Cabling | PC to 1747-PIC to 1747-C10 into the terminal's DH-485 programming connector; second 1747-C10 from the terminal's DH-485 communication port to the SLC |
| Terminal power | Separate 120 V supply from Fuse 1 |
The terminal's comm indicator flicked between steady and flashing, which reads as a link coming and going rather than a wrong node or baud. The 120 V supply behind Fuse 1 is outside this troubleshooting path: treat that wiring as live and stay on the low-voltage DH-485 side unless the supply itself is being isolated.
Run the numbers first #
Three stations share the link: the PC driver at station 0, the SLC 5/03 at node 1, and the PanelView at node 2, with maximum station 31.
- Addresses in use: 0, 1 and 2. Values needed: 3. Distinct values present: 3. Duplicates: none, since 0 ≠ 1, 1 ≠ 2 and 0 ≠ 2.
- Range: the highest address in use is 2, and 2 ≤ 31, so the maximum-station setting covers every node on the link.
- Baud: 19,200 baud at the PC driver, at the SLC port and at the terminal; 19,200 − 19,200 = 0 mismatch on both links.
Decision: addressing, range and speed are clean, so the download failure is not in the DH-485 configuration. The one variable left on the PC side is which driver owns COM1 — and that is where the fault sat.
Two drivers on one COM port #
Both the AB_PIC-1 (1747-PIC/AIC+) driver and the AB_DF1-1 (RS-232 DF1) driver were configured against COM1. One physical serial port serves one active driver, and the DF1 driver held it — which is why the SLC answered over RS-232 while the PIC browse came back empty. The DF1 link working proved the port and the PC healthy, not the PIC path available.
The 1747-PIC installation instructions, document 1747-IN024A-EN-P, require the converter on a built-in COM1 or COM2 and tell you to reserve the port for exclusive use when you configure the driver. Two drivers pointed at one port break that requirement from the DF1 side, and RSLinx does not flag the conflict for you.
Clear COM1 and run only the PIC driver #
- In RSLinx, delete AB_PIC-1 and AB_DF1-1 so neither driver claims COM1.
- Restart RSLinx.
- Configure a single 1747-PIC/AIC+ driver on COM1: station 0, 19,200 baud, maximum station 31.
- Open RSWho and browse: the SLC should show at node 1 and the PanelView at node 2.
- Return to PanelBuilder32 and repeat the download; the terminal now lists.
Do not start the DF1 driver on COM1 while testing the PIC. If DF1 is needed again, delete or stop the PIC driver first, then hand COM1 back.
Prove the converter path in isolation #
If the browse still returns nothing once the port is clean, take the PanelView out of the path and test the converter alone:
- Wire PC to 1747-PIC to 1747-C10 to the SLC's DH-485 port, with nothing else on the link.
- Browse with only the PIC driver active.
- No SLC at node 1 means the fault is below RSLinx: the converter, its ribbon cable, any 9-to-25 pin adapter, converter power, or the SLC's port.
- SLC at node 1 means the converter path is good; reconnect the terminal one cable at a time until the failing segment shows itself.
The 1747-PIC draws power from the DH-485 side, not from the PC's serial port. The terminal documentation allows that power from an SLC, a live DH-485 network, or a 1747-NP1 supply, so the programming connector fed the converter here only because the second 1747-C10 kept the terminal networked to the SLC — when you isolate the terminal, leave the converter on the SLC side. On a well-used converter the ribbon cable is a known intermittent; reseat it and the adapter before condemning the box. The 1747-C10 link between terminal and SLC is the same wiring covered from the panel side in connecting an HMI to an SLC 500 over DH-485.
When both nodes disappear together #
After the driver fix, the application loaded — and then the SLC 5/03's DH-485 port indicator went dark and the PIC driver lost both nodes at once. When two devices vanish together, the fault is in the shared path, not in either node's settings: COM1 ownership, converter power, the ribbon cable, the adapters, both 1747-C10 cables, or the SLC port itself. Treat the SLC as the suspect only after the isolated test repeats cleanly with converter power stable; the dead port indicator on this unit pointed at the 5/03's channel.
Two supported routes keep the terminal usable while that is sorted. SLC 5/03 passthrough carries the DH-485 traffic over the DF1 link into the SLC's channel 0 — the serial side of that link is the one walked through in how to connect a laptop to an SLC 500 serial port. The alternative is transferring the application on a memory card, which removes the PC-to-network link from the job entirely.
Acceptance check #
- Exactly one COM1 driver exists, the 1747-PIC/AIC+ driver, and the DF1 driver stays deleted or stopped.
- RSWho finds node 1 and node 2 on repeated browses with the SLC port indicator steady.
- The PanelBuilder32 download completes and the terminal runs the application.
- Neither node drops after the full network is reconnected and browsed again.
If all four hold, the original failure was port contention and it is closed. If the last point fails, the shared-path fault is still live on the SLC side, and passthrough or the memory card is the interim way to keep the operator screen in service.
Questions asked
Will a USB-to-RS-232 adapter let the 1747-PIC driver work on a PC without a serial port?
No. The 1747-PIC and its RSLinx driver work only with the PC's built-in COM1 or COM2 serial ports, and the driver does not run through general-purpose USB-to-RS-232 adapters. The supported route on a newer PC is the 1747-UIC, the USB equivalent of the 1747-PIC. Check your RSLinx revision too, because newer releases no longer include the 1747-PIC/AIC+ driver.
Both drivers show up in RSWho — is that not fine?
RSWho lists every configured driver as its own root, so both can look present while only one owns COM1. The DF1 root browsed because it held the port; the PIC root stayed empty because it never got to transmit. That display is exactly how a port conflict hides the PanelView while the DF1 path looks healthy.
What does it mean when the SLC and the PanelView vanish from RSWho together?
One shared piece failed. Both nodes reach the PC through the same converter path, so check that path first: COM1 ownership, converter power, the ribbon cable, any 9-to-25 pin adapter, both 1747-C10 cables, and the SLC's DH-485 port. On this job the SLC 5/03 port indicator went dark at the same moment, which pointed at the controller side.
Does the maximum station setting matter?
It must cover the highest node you need to see. Here the highest address is the PanelView at node 2 and maximum station is 31, and 31 is greater than 2, so the browse covers it. If that field were set below the terminal's node, RSWho would never list the terminal regardless of wiring — a five-second check worth doing first.