Troubleshooting
Why a Text List Shows Overlapping Text After a Value Change
Short answer
Stacked entries on a text list mean the panel painted the new value without erasing the old one. Prove it by reading the same tag in a numeric field on the same screen, check every layer and the template for a second field bound to that tag, then stop feeding the panel one giant list: split an 8-bit status word into eight two-state bit indicators and give the tag an acquisition cycle shorter than the screen's update cycle.
On this page
A text list on a TP177A running WinCC flexible 2008 SP3 Runtime occasionally paints the entry for the new value without erasing the entry for the old one, and the operator reads two statuses at once. Two things produce that: a second field bound to the same tag hiding on another layer or in the template, and a tag that changes inside the same update window in which the field is still painting. Verify the tag with a numeric field on the same screen, audit every layer and the template, then remove the fragile part for good: split the status word into one indicator per bit, which takes away the shared tag and leaves each field nothing but a short string to repaint.
What the stacked text looks like #
Four units at the site show the same behavior, so this is not one defective panel. The pattern in the reports:
- Two or three list entries occupy the same rectangle, with the previous status still readable behind or under the current one.
- The stacking is tied to change: a status that sits still renders clean, and the field misbehaves when the value steps.
- The characters themselves draw cleanly; whole strings land on the same spot, which is what separates this from corrupted glyphs.
- It has only been seen on the larger lists in the project; small lists run clean.
Stacked strings are a different fault from badly drawn characters. If glyphs come out mangled instead of two clean strings landing on one spot, the problem lives in font rendering rather than the list, and the walk-through of garbled font rendering in an Ignition Vision client covers that class of fault.
Read the tag as a number on the same screen #
Before touching the layout, find out which side is lying. Place a numeric output field bound to the same tag next to the list field on the same screen, then force the status to change and watch both fields together.
- The number steps cleanly to the value the machine is actually in, and the text still stacks: the tag is healthy and the fault is the panel's redraw of a long entry. Go to the update race below, then the bit split.
- The number itself flickers through values that do not match the machine: the panel is catching the status byte half-written. The PLC sets the status bits one after another, and a read between those writes returns a combination that exists for only an instant. Assemble the status in a work byte the panel never sees, copy it to the tag with a single transfer, and overwrite the copy only when the next complete status is ready. Fix that before anything else.
- Neither field tracks the machine: correct the tag and its addressing first, because no redraw fix helps a tag that lies.
Run the first download on a bench panel or in a planned stop: this field is the operator's view of motor status, and a test build that blanks it hides real faults from the people who act on them.
Audit every layer and the template for a second field #
Open the screen, then the template it inherits from, and walk every layer, including any set invisible. A second text or output field bound to the same tag - left on the template, parked on a background layer, or orphaned when the screen was rebuilt - draws its own string into the same rectangle and reads exactly like stacking. Delete it or move it to its own spot; if a duplicate was the whole story, the symptom disappears at the next download.
Two elements placed on top of each other as a plain layout mistake are a related fault with a different cure, and that is the entire story behind overlapping text on gas dispenser screens.
Size raises no error of its own: the tool compiles and downloads a list of this size without complaint, which is why the fault arrives unannounced. The per-device limits for text lists sit in the tool's system limits documentation, worth checking before any list grows further.
Close the update race between the tag and the screen #
Compare two settings in the project. The tag's acquisition cycle is how often the panel reads the value; the screen's cycle is how often the screen redraws its contents. Give the tag a shorter acquisition cycle than the screen's update cycle, so every repaint starts from a value that has already settled instead of catching a change in flight.
Then measure the PLC side: the shortest time between two changes of the status byte. Keep the program from stepping the tag faster than the panel reads it, and transfer each complete status exactly once, as in the work-byte pattern above. A change that lands inside a repaint window is the trigger condition for the stack.
Two cheap tests isolate a corrupted field definition. Place the same field with the same text list and tag on an empty screen; if it runs clean there, delete the original field, build a new one in its place with the same list and tag, and download. The rebuild costs a few minutes and clears the last of the project-side suspects.
Splitting a 249-entry motor status list into 8 bit indicators #
Inputs.
- Status word: 8 bits, one per independent condition - running, overload and the rest; several bits can be high at once, which is why the combinations multiply.
- Combinations an 8-bit word can express: 2^8 = 256.
- Combinations that cannot occur on this machine: 7, from the project's own status scheme.
- Entries the flat list carries: 249, one per value that can occur.
Rule. A word of N bits expresses 2 to the N combinations, and a flat text list needs one entry per combination that can occur. On every change the panel looks up the matched string and repaints it whole in the field's rectangle. One indicator per bit needs two strings per bit, because a bit has two states, and each indicator repaints only inside its own rectangle.
Arithmetic.
- 2^8 = 2 × 2 × 2 × 2 × 2 × 2 × 2 × 2 = 256 combinations.
- 256 - 7 = 249 entries in the flat list.
- 8 bits × 2 states = 16 short strings spread over 8 separate fields.
Result. The flat list asks one field to look up and repaint one of 249 long strings on each change. The bit layout asks each of 8 small fields to repaint one of its own 2 short strings; because no two indicators share a rectangle or a tag, no entry can land on top of another.
Decision. Split whenever the entries count combinations of independent bits rather than states the process really distinguishes - here 8 on/off facts spread across list lines. Keep a flat list only where the value enumerates genuinely exclusive states and the count stays small; the field behavior behind this fault showed up on large lists while small ones ran clean.
Fixes in the order that pays off #
Work down the list and stop when the symptom is gone:
- Numeric field beside the list field, same tag, forced change: a clean number means panel redraw; a flickering number means the PLC assembly, fixed with the work byte and the single transfer.
- Every layer of the screen and its template, visible or not: delete any second field bound to the status tag.
- Field rebuilt on an empty screen, then rebuilt in place with the same list and tag.
- Acquisition cycle shorter than the screen's update cycle, PLC write rate capped to the panel's read rate, one transfer per complete status.
- Word split into one indicator per bit. Addressing one bit of a word as its own tag is a standard technique; the walk-through of accessing one bit of a word in Operator Terminal Expert shows it in another panel family's tool, and the idea carries straight over.
For the site in question: run the numeric check at the next planned stop, clear the layers and template, re-cut the field, and make the bit split the standard for all twenty stations - the sixteen still to be commissioned should never receive a list this size.
Questions asked
Why can nobody reproduce the stacking on demand?
Because the trigger is timing, not data. The stack needs a value change to land in the same window as a repaint, and a motor status that sits still for hours rarely provides one. Run the project in the runtime simulation and force the status tag to step rapidly: if the fault appears there it lives in the project, and if it appears only on the panel the update timing is implicated.
How do I test without disturbing a running plant?
Put the numeric field into the project and send it with the next planned download, or do the forcing on a bench panel with a test configuration. The display is the operator's view of motor status, so never leave a test build running where it can hide a real overload or fault from the control room.
What should the PLC do so the panel never reads a half-written status?
Assemble the status in a memory byte the panel does not read, copy that byte to the HMI tag with a single transfer, and leave the copy untouched until the next complete status is ready. A panel that reads the tag while individual bits are still being set catches a value that maps to the wrong entry or to no entry at all.
Can the status be shown as alarms instead of a text list?
Yes. Wire one discrete alarm to each status bit instead of one list entry per combination. Each active bit then takes its own line in the alarm view with its own time stamp, the display grows line by line as bits set and clear, and bits that change together stop fighting over a single field.