Why a TP 177micro Cannot Connect to a LOGO! 0BA7 RCE
Short answer
A TP 177micro cannot connect to a LOGO! 0BA7 12/24RCE; the panel's only port is an RS485 fieldbus interface for PROFIBUS, while the RCE variant accepts HMI connections on its Ethernet port. No cable or media converter bridges a missing physical layer and a missing protocol at once; use an Ethernet panel with a documented LOGO! driver, or use the LOGO! local display.
On this page
No, a TP 177micro cannot be connected to a LOGO! 0BA7 12/24RCE. The panel's single communication port is an RS485 fieldbus interface for PROFIBUS on a 9-pin D-sub, and the RCE variant of the LOGO! exposes its HMI access on an Ethernet RJ45 socket. The two devices share neither a physical layer nor a protocol, so no passive cable closes the gap, and the documented fix is an Ethernet-capable panel with a LOGO! driver or the LOGO!'s own local display.
What each device actually exposes #
Read the ports before you read anything else, because the ports decide the answer:
- TP 177micro: one 9-pin D-sub marked as a PROFIBUS interface. It carries RS485 differential signalling with fieldbus framing. There is no RJ45 and no usable general-purpose serial port, even though the connector shape resembles one.
- LOGO! 0BA7 12/24RCE: an RJ45 Ethernet interface. The RCE suffix identifies the Ethernet variant, and this socket is how an HMI panel reaches the controller. There is no PROFIBUS port on the housing.
A connector that looks like a serial port is not a serial port. On this panel it is an RS485 fieldbus link, and wiring it to anything else damages the transceiver rather than establishing a link.
Two separate gaps, not one #
An HMI panel reaches a controller through a communication driver inside the panel runtime. That driver is bound to one physical interface and one protocol family. Here both bindings fail at once:
- Physical layer: RS485 differential two-wire signalling on the panel against 10/100 twisted-pair Ethernet on the controller. Nothing converts one into the other passively; they are different signalling schemes on different media.
- Protocol layer: even with a physical bridge, the panel would have to issue the request format the LOGO!'s Ethernet interface accepts. A PROFIBUS-side driver does not generate it, and the LOGO! will not answer PROFIBUS framing on either port.
Fixing only one gap leaves the connection dead, which is why every "adapter" idea for this pairing fails.
Why no converter closes the gap #
A media converter changes the wire, not the application protocol the panel driver generates. After the conversion, the panel still transmits fieldbus framing that the LOGO! ignores.
A genuine gateway would have to terminate the panel's protocol on one side and emulate the LOGO! Ethernet protocol on the other, holding configuration for both. When a gateway is the right tool — for example, a documented PROFIBUS-to-EtherNet/IP gateway for HMI and PLC — it is configured and verified as part of the project, not bought as an anonymous black box. No gateway covering this exact pairing appears in the available documentation, so do not budget for one without a documented, supported part number.
If your real goal is to put a LOGO! on a network it was not designed for, check what the controller actually speaks before buying anything: the article on whether a LOGO! 0BA7 can talk Modbus TCP to remote I/O modules walks through what its Ethernet stack does and does not offer, at https://industrialmonitordirect.com/blogs/knowledgebase/can-a-siemens-logo-0ba7-talk-modbus-tcp-to-remote-io-modules.
What the LOGO! 0BA7 side expects from an HMI #
On the controller side, the Ethernet connection is set up in LOGO!Soft Comfort under the Ethernet Connections tool, where you add a server connection for the panel. The 0BA7 supports one HMI in this documented setup, and the connection count on the LOGO! is limited, so design the panel as a single station reading and writing the LOGO! memory rather than as one of several clients. The page on how the LOGO! 0BA7 supports one HMI in the documented setup shows the server connection and its limit in detail, at https://industrialmonitordirect.com/blogs/knowledgebase/logo-0ba7-supports-one-hmi-in-the-documented-setup.
The panel side then needs a driver that matches that Ethernet protocol. Which panel offers it is a compatibility-list question, answered in the next section — not a wiring question, because the wiring is now ordinary Ethernet.
Panel choice and the engineering software #
Work through these checks in order and stop at the first one that fails:
- Panel port: the candidate panel must have a built-in RJ45 Ethernet port. The TP 177micro fails this test and is excluded.
- Driver list: open the connections editor in your installed engineering software and confirm a LOGO! entry exists for the panel type you selected. WinCC Flexible 2007 predates the 0BA7 generation, so treat its driver list as unverified for this controller until you look.
- Documented support: if the entry is missing, read the minimum software version that supports both the panel and the LOGO! 0BA7 from the manufacturer's compatibility documentation, and install that version or its successor.
- Firmware match: the panel's runtime firmware must match the software version that generated the project. A transfer error at download is the usual symptom of a mismatch.
If you only need text messages and a handful of setpoints, skip the graphic panel entirely and use the LOGO!'s on-board display and buttons, or the dedicated LOGO! text display. Given that your reason for choosing the LOGO! is that you know LOGO!Soft Comfort and not S7 programming, this route keeps all the work in tools you already use, and the panel remains purely a display and entry device.
If you do need a graphic HMI and want the freedom of PC-based runtime instead of a proprietary terminal, that is the case where an industrial panel PC replaces the failed or unsuitable operator panel, with the LOGO! connection handled by the runtime's driver.
Worked example: addressing a replacement panel #
Say you replace the TP 177micro with an Ethernet panel and put both devices on a small switch. Give the LOGO! the address 192.168.0.1 and the panel 192.168.0.2, both with subnet mask 255.255.255.0. Check the network part of each address with a bitwise AND against the mask:
- 192.168.0.1 AND 255.255.255.0 = 192.168.0.0
- 192.168.0.2 AND 255.255.255.0 = 192.168.0.0
The network parts are equal, so the two devices are in the same subnet and can address each other directly — no router, no gateway entry. Then verify the layer before the project: ping the LOGO! at 192.168.0.1 from a PC on the same switch and require replies with no loss. If a device sits outside that subnet — say the panel at 192.168.1.2, whose network part 192.168.1.0 differs — the link looks dead even though the cable and driver are correct. Addresses must be unique, too: a duplicate address on the switch produces intermittent, misleading failures that resemble a protocol problem.
Verification before you commit #
- Panel and controller ports inspected: RJ45 on the panel, RCE order number confirmed on the LOGO!.
- Driver present in the connections editor of the installed engineering software for the chosen panel.
- Ping test between panel-side PC and LOGO! passes with no loss, addresses unique in one subnet.
- Runtime link: one LOGO! input shown on the panel follows the physical input, and a setpoint written from the panel reaches the LOGO! program.
The decision #
- TP 177micro plus LOGO! 0BA7 RCE: not connectable. The pairing lacks both the physical layer and the protocol, and no documented cable, converter or gateway closes it.
- TP 177micro must stay in service: pair it with the controller family its RS485 interface was designed for, not with the LOGO!. For its known software limits, the article on why WinCC Flexible cannot connect to a TP177 Micro by USB covers the transfer side of the same panel.
- Graphic HMI required on the LOGO!: buy a panel with a built-in Ethernet port that the compatibility documentation lists for the LOGO! 0BA7, confirm the driver in your engineering software before ordering, and use one server connection on the LOGO!.
- Only a few values and setpoints needed: use the LOGO!'s local display or the dedicated text display and skip the panel project altogether.
One safety note: never wire the panel's 9-pin RS485 fieldbus connector to a PC COM port, an RJ45 adapter or any homemade cable. The pinout mismatch can damage the transceivers at both ends, and it will never produce a working link.
Questions asked
What happens if I wire the TP 177micro 9-pin port to the LOGO! 0BA7 RCE with an adapter?
Nothing useful. The LOGO! 0BA7 RCE has no PROFIBUS or serial port, so there is nothing on the controller side for the panel's RS485 interface to talk to. A forced cable risks damaging the panel's RS485 transceiver, because the pinout was never meant to mate with an RJ45 socket.
Does a PROFIBUS-to-Ethernet converter solve this?
Not by itself. A media converter changes only the physical wire. The panel keeps transmitting PROFIBUS framing, and the LOGO!'s Ethernet interface does not interpret it, so the link never establishes. Ethernet protocol on the other, and no such device is documented for this pairing.
Is WinCC Flexible 2007 enough to build the panel project for a LOGO! 0BA7?
Do not assume it. WinCC Flexible 2007 predates the 0BA7 generation, so open the connections editor in your installed copy and check whether a LOGO! entry appears in the driver list for the panel you select. If the entry is missing, read the minimum engineering-software version that supports both the panel and the LOGO! from the manufacturer's documentation and install that version or its successor.