Why a WebIQ Project Link Loads on the PC but Not the HMI Screen
Short answer
No universal WebIQ link exists: a browser HMI loads only when the screen has a routed path to the WebIQ server, at http[s]://{SERVER HOSTNAME OR IP}:{LISTENER PORT}/{FOLDER NAME OF PROJECT}/. When the link works on the PC but not the screen, fix the address, subnet, listener binding or routing — in that order.
On this page
No, there is no universal link. A WebIQ HMI is a web page served by a WebIQ server, and any browser — the engineering PC or the HMI screen — loads it only from a network that can reach that server, exactly like any other website. Every WebIQ address has the same form, http[s]://{SERVER HOSTNAME OR IP}:{LISTENER PORT}/{FOLDER NAME OF PROJECT}/, with the placeholders filled from the installed server. When the link opens on the PC but not on the screen, one of four things is wrong: a loopback host in the address, no usable path between the two subnets, a listener that refuses remote connections, or a wrong project folder. Work those checks in order; the link itself is never the fault.
Read the address the PC generated #
The link the PC's "open in browser" action produced encodes four decisions; take it apart before touching the network:
| Address part | Where the value comes from | What it decides |
|---|---|---|
| Server hostname or IP | The network configuration of the device running WebIQ | Which computer or controller the screen connects to |
| Listener port | The server's listen (HTTP/HTTPS) settings | Which service accepts the connection; 10123 is the documented default |
| Scheme, http or https | The same listen settings | Unencrypted or TLS-protected transfer |
| Project folder | The published project's folder name | Which project the server serves |
The braces are placeholders, not text to paste, and http[s] means pick the scheme the server is configured for. The first suspect is the host. The documented default host is localhost, which resolves into the IPv4 loopback block 127.0.0.0/8 — the device running that browser. A link that works on the PC and contains localhost tells the screen to look for the server inside the screen. Replace the host with the address of the device actually serving the project — the controller, panel PC or workstation running WebIQ — and retry before changing anything else.
Check the subnet between screen and server #
One incoming Ethernet connection does not put two devices in the same IP subnet; the subnet mask decides delivery. Read the IP address, mask and gateway on the screen and on the server device, then do the comparison the screen's stack performs on every connection.
Worked example with illustrative addresses; your plant values decide your case:
- WebIQ server on the controller: 192.168.10.20, mask 255.255.255.0
- HMI screen: 192.168.20.5, mask 255.255.255.0, gateway 192.168.20.1
With mask 255.255.255.0 the AND keeps the first three octets and zeroes the fourth: 192.168.10.20 → 192.168.10.0, and 192.168.20.5 → 192.168.20.0. The network addresses differ in the third octet, so the two devices sit in different subnets. The screen cannot deliver frames to 192.168.10.20 directly; it hands those packets to gateway 192.168.20.1 and needs a route — and a return route — from there. A switch carrying both subnets forwards frames; it does not route between them.
Decision for this example: re-address the screen into the server's subnet when the plant numbering allows it. 192.168.10.35 with mask 255.255.255.0 gives 192.168.10.0, the server's network, so delivery becomes direct and the gateway leaves the picture. If re-addressing is not allowed, route between 192.168.20.0/24 and 192.168.10.0/24 — routing browser access to a fixed-IP HMI over two subnets covers the gateway settings that path needs.
Test by IP address first, because a hostname adds name resolution as a second failure point. Once the project loads, a maintained hostname is the better permanent address — it survives a server address change, provided the certificate carries the same name. Treat ping as what it is: proof of IP reachability only. A listener can refuse the connection after a good ping, and a filtered ping fails on a working path.
Check the listener binding and the scheme #
If the project opens in a browser on the server's own device but not from the screen, routing is proven and the service is the fault. A listener bound to the loopback interface accepts local connections only. Configure the listen (HTTP/HTTPS) ports on the server's Ethernet interface, in the server management pages where those ports are set, and permit that port through any host firewall for the intended clients. Opening unrelated ports fixes nothing.
Match the scheme to the listener. Since WebIQ 2.20, new installations use HTTPS by default, and HTTP requests on port 10123 are redirected to HTTPS — on a current install the address that finally sticks is the HTTPS one. Sending https to a plain-http listener fails even with routing and port correct.
The browser's verdict names the failing layer:
- Timeout — packets never arrive: wrong IP, routes or firewall.
- Connection refused — the host answered and nothing accepts that port: listener state or port number.
- Certificate warning — the path works and the TLS identity check failed: the name on the certificate against the address used, its validity, and the screen's clock.
- HTTP error page — the server answered: host, port, project folder, and the server's request logs.
Resolve certificate trust through certificate configuration, not by reading the warning as a network fault.
Check the project path, then leave the tags alone #
When the server answers but the expected HMI does not appear, compare the folder in the address with the published project's folder, spelling exact, and check the published state in the server's request logs. Confirm the server is actually serving it — when the runtime has to come up by itself after publishing, starting a published WebIQ HMI project without Runtime Manager is the piece to verify.
Then keep two connections apart. The browser talks to the WebIQ server for the HMI and its runtime data; the server-side driver talks to the controller for process values. A project that never loads is a host, listener, routing or path fault — never a controller tag address. An HMI that loads with faulted values is a driver fault: the configured endpoint, the controller's reachability from the server, access permissions, and tag mapping. HMI OPC UA server vs client: which direction works explains which end of that second connection must connect. When driver diagnostics show good values and one widget still misreads, the fault is that widget's binding, not the network.
Why no link can be universal #
A public website loads from anywhere because its name resolves to a public address and every network in between routes toward it. A local WebIQ server almost always holds an RFC 1918 address instead: that standard reserves 10.0.0.0/8, 172.16.0.0/12 and 192.168.0.0/16 for private networks and keeps them off public internet routing. No spelling of a URL changes routing, so a client outside the plant cannot reach 192.168.10.20 — by design, not by WebIQ limitation.
The PC loading the project proves only local reachability; local reachability is not routed access, and routed access is what the screen and every remote client needs.
Decision for remote clients: have the network administrator provide one approved routed path — a site-to-site link or VPN into the plant network — and publish a single address for everyone. The HMI writes setpoints into a running machine, so give remote access only through an authenticated path you control, never a port opened straight to the control network.
The fix for each finding #
localhostor any 127.x.x.x host — open the address with the server's real IP or maintained hostname.- Different subnets — re-address one device into the other's subnet when allowed, or route between them; the URL cannot cross that line.
- Opens locally, refused or times out remotely — bind the listener to the Ethernet interface and permit the port through the firewall.
- Scheme error or an http-to-https redirect — keep the scheme the server is configured for; current installs are HTTPS by default.
- Server answers, no HMI — correct the project folder spelling and confirm the published state.
- HMI loads, values fault — fix the server-side driver endpoint, permissions and tags, not the browser address.
- Client on another network — an approved routed path arranged with the network administrator; no universal link exists to create.
Questions asked
Can a special URL make the WebIQ project load from any network?
No. A public site works because its name resolves to a public address and the networks in between route toward it. A WebIQ server on a plant network usually holds an RFC 1918 private address such as 192.168.10.20, which the public internet does not route. Give each remote client an approved routed path — a site-to-site link or VPN — and that client then uses the identical address format, nothing special.
Why does the link with localhost fail only on the screen?
localhost resolves into the IPv4 loopback block 127.0.0.0/8, with 127.0.0.1 the usual address, and it always means the device running that browser. On the engineering PC it reaches the PC where the design-time server runs; on the screen it reaches the screen itself, where no server is listening. Replace the host part with the WebIQ server's address on the plant network and test again.
The browser redirects http on port 10123 to https — which address should the screen keep?
Use the HTTPS address. Since WebIQ 2.20, new installations use HTTPS by default and redirect HTTP requests on port 10123 to HTTPS. If the screen then shows a certificate warning, the connection works and only the TLS identity check failed: compare the name on the certificate with the address used, and check the screen's clock, because a clock far off rejects otherwise valid certificates.
The project finally opens on the screen but every value shows a fault. Same problem?
No. The browser fetches the HMI from the WebIQ server, while the server-side driver fetches process values from the controller — two different connections. A screen showing the HMI has proven the first. Check the driver endpoint, the controller's reachability from the server, access permissions and tag mapping from the server side, not the browser address.
Is a successful ping from the screen enough proof?
No. Ping tests IP reachability only. The WebIQ listener can still be bound to a loopback interface, blocked by a firewall, or listening on another port, and a failed ping can equally be filtering rather than a dead path. Where the screen offers no diagnostic tools, the browser's own verdict on the complete project address is the instrument: timeout, refusal, certificate warning or error page each name a different layer.