Troubleshooting
Why a Weintek HMI Will Not Connect to a Mitsubishi FX PLC
Short answer
A Weintek HMI that reports no connection to a Mitsubishi FX over an SC09-style cable almost always has a physical-layer problem: the FX port is RS-422, the cable pinout at both ends must match the documented assignments, and the HMI's USB port is not a PLC serial port. Verify driver, port, settings and wiring in that order.
On this page
- Why does a Weintek HMI fail to connect to a Mitsubishi FX over an SC09 cable?
- What electrical interface does the FX programming port actually use?
- Can I use the HMI's USB port instead of a serial port?
- How do I verify the cable pinout at both ends?
- Example: how long does a serial exchange take at 9600 baud?
- How do I prove the fix before trusting the screens?
- When is replacing the HMI the right call?
- Questions asked
The connection fails at the physical layer, not because the HMI is wrong: the Mitsubishi FX programming port is an RS-422 interface, while many HMI serial ports are RS-232, so the cable between them is a converter whose pinout must be correct at both ends. Weintek publishes an FX-series driver, so the fix is to verify driver, port, serial settings and wiring in that order before considering a replacement terminal.
Why does a Weintek HMI fail to connect to a Mitsubishi FX over an SC09 cable? #
Because the FX programming port speaks RS-422 and the SC09 is a converter cable, not a straight pass-through: if the pins on the HMI side are wired for a different assignment than the HMI's own serial connector expects, no data arrives and the driver reports no PLC response. Connector shape proves nothing.
Three layers have to line up before any screen works: the PLC port and its protocol, the HMI driver and serial settings, and the cable or converter between them. A mismatch in any one kills the link, but the cable is the layer nobody documents, and it is the one that changed in the reported failure. The Mitsubishi FX communication manual covers the RS-422, RS-232 and RS-485 options for this family, and Weintek publishes its own connection guide for the FX232 and FX485-BD boards, so both ends of the pinout question are documented. Start there, not with a connector photo.
What electrical interface does the FX programming port actually use? #
The FX programming port is RS-422, a differential interface on either the 8-pin round mini-DIN connector or the DB25 connector depending on the model, and the SC09 cable family exists precisely to bridge between that and an RS-232 side. That is why a laptop programming cable is not automatically an HMI cable.
RS-422 uses paired differential lines for send and receive, so a cable has to carry four signal conductors plus signal ground, and the pairs must land on the pins each manual assigns. Substituting an RS-232 pinout onto an RS-422 port does not degrade gracefully; it simply does not communicate. If you need the interface background, the FX-series communication manual is the reference to keep on the bench, and it also defines the parameter registers that set the port's serial format when a BD communication board is used instead of the programming port.
Can I use the HMI's USB port instead of a serial port? #
No. On an HMI, the USB port is a transfer and service port, and it does not become a PLC serial interface just because a USB-to-RS-422 converter cable exists for programming from a PC. Use one of the HMI's documented serial ports.
The PC-side USB-SC09 converters work because the PC software runs a driver for that specific converter. An HMI runtime does not carry that driver, and expecting the USB port to pass the FX protocol is a dead end that costs hours. Select the FX driver in the HMI project on a physical COM port the HMI documentation lists as supported for that driver, then build the cable for that port's connector and interface.
How do I verify the cable pinout at both ends? #
Pull the pin assignments from the two manuals, wire point to point, and confirm every conductor with a continuity test before the cable ever touches the PLC. Do not infer wiring from a DB9 or DB25 shell size.
- Record the PLC end: the FX manual gives the pin functions for the port you are using, mini-DIN or DB25.
- Record the HMI end: the HMI manual gives the pin functions for the exact serial connector and interface you selected, and they differ between models and between RS-232, RS-422 and RS-485 variants.
- Note any converter in the path and which side is which interface; treat "RS-232 converter" as incomplete identification.
- Wire each documented signal to its documented pin, keeping the differential pairs together.
- Continuity-check every conductor end to end, and check that no two pins are shorted.
- Only then connect both ends and power up.
Example: how long does a serial exchange take at 9600 baud? #
At 9600 bit/s with 10 bits per character, a 12-character request-and-reply exchange moves 120 bits and takes 120 ÷ 9600 = 12.5 ms on the wire. That is the scale you should see on a healthy link, so a screen that sits for seconds is not waiting on the wire.
The arithmetic: 12 characters × 10 bits per character = 120 bits, and 120 bits ÷ 9600 bit/s = 0.0125 s = 12.5 ms per exchange. The exact figure depends on the protocol's real frame length and on the driver's polling interval and timeout, which add their own delays on top. Its value here is as a sanity check: if the HMI reports timeouts in the hundreds of milliseconds or longer on every scan, the problem is a link that never establishes or a settings mismatch, not a slow wire. Set both ends to the same baud rate, data bits, parity, stop bit and station number, read from the FX port configuration, and change one parameter at a time.
How do I prove the fix before trusting the screens? #
Test on a bench with the cable you built, before the terminal goes back on the machine, and accept the link on a single known value before any production screen is judged.
- Load the project with the correct FX driver, port and serial settings, and put the HMI online.
- Pick one PLC address, force a value into it from the programming software, and confirm the HMI display changes.
- Write to one test address from the HMI and confirm the PLC sees it, only if the application needs writes.
- Unplug and reseat the cable, and confirm the driver recovers on its own.
- Record the cable pinout, converter identity and serial settings with the project file so the next technician does not rediscover them.
A link that connects but shows wrong values is a different fault: check the address, data type and object binding, not the cable. For the same reason, keep a failed attempt and a confirmed link separate in your notes, so a wiring change that worked is not later confused with a settings change that did not.
When is replacing the HMI the right call? #
Replace only after a known-good cable and correct settings still fail on the same port, or when the HMI has no documented FX driver for any port it physically has. Neither condition is met by a first attempt with an unverified SC09 pinout, so the Weintek terminal in this kind of failure is normally kept and rewired, not swapped.
If the project does move to a PC-based operator station instead, the same verification order applies to the new serial port, and the cable work does not change. The practical decision tree: verified driver and correct pinout on a documented serial port first; driver or port mismatch second; new hardware last. If your target is a different FX model, note that the front-port interface and the BD-board options differ between models, and check the dedicated FX3G front-port guide before wiring.
For the driver and settings side of this same PLC family, the Weintek-to-FX communication guide walks the project configuration, and the general serial troubleshooting checklist covers the timeout and polling symptoms that remain after the cable is proven.
Questions asked
Can I use a Weintek HMI with an FX-128MR?
Yes. Weintek publishes a Mitsubishi FX-series driver, and the FX-128MR communicates over its programming port when the cable and serial settings match. The connection is a wiring and configuration task, not a compatibility wall: select the FX driver on a documented serial port of the HMI, wire the cable to the pin assignments in the two manuals, and set matching baud, data bits, parity, stop bits and station number at both ends.
Does the SC09 cable work for HMI communication or only programming?
The SC09 is Mitsubishi's programming and communication cable, built as a converter between an RS-232 side and the RS-422 side of the FX port, with connectors for the 8-pin round port and the DB25 port. It carries the same protocol an HMI driver uses, so it can serve an HMI link, but only if the pinout at the HMI end matches the assignments the HMI manual gives for its own connector. A cable that programs a laptop is not automatically wired correctly for a different HMI serial port.
My HMI connects but some values are wrong. Is the cable at fault?
No. If the link establishes and a test value tracks the PLC, the physical layer and driver are working, and a wrong or stuck value points to the tag: check the PLC address, the data type and the HMI object binding against the PLC program. Cable faults show up as no connection, timeout messages or intermittent drops, not as individually wrong numbers.
Can I copy a DB9-to-DB25 wiring diagram someone else used?
No. A description like DB9 RS-485 male to DB25 RS-422 male names the connector families, not the pin assignments, and different HMI models use different pins for the same signal. Take the pin numbers from your HMI manual and your FX manual, wire point to point, and confirm each conductor with a continuity test before connecting. That takes ten minutes and prevents a damaged port.