Why a WinAC RTX IPC responds at two IPv4 addresses

Industrial networks Published 6 min read By IMDTouch engineering team

Short answer

Slot 4 cannot own it: WinCC Runtime Advanced is HMI software with no interface. The extra 192.168.1.2/255.255.255.0 is a static alias in the adapter's advanced TCP/IPv4 address list, active even while the dialog shows 'Obtain an IP address automatically'. Map the adapter with ipconfig /all, remove the alias from the advanced list, and if it returns, reconfigure the component that reapplies it.

On this page
  1. What each station slot owns
  2. Why the automatic setting never clears the alias
  3. Map every address to its owner
  4. Worked example: 192.168.1.2/255.255.255.0 against a 192.168.1.0/24 plant network
  5. Remove the alias and verify
  6. Questions asked

This is an address-ownership fault, not a broken panel. On the IPC277D touch panel running Windows Embedded Standard 7 SP1, WinAC RTX 2010 and WinCC Runtime Advanced V11, slot 4 cannot own an address: WinCC Runtime Advanced is visualization software with no network interface of its own. The extra 192.168.1.2/255.255.255.0 the adapter answers at is a static alias in the advanced TCP/IPv4 address list of the Windows connection — a list Windows keeps beside the primary address and applies no matter what the main dialog shows. That is also why 'Obtain an IP address automatically' keeps coming back: it describes only the primary address and never touches the alias. Map the adapter with ipconfig /all, confirm the alias in the advanced list, remove it there, and if it returns after a reboot, reconfigure the component that reapplies it.

What each station slot owns #

A PC station slot is a configured software component, and in this station only the IE General communication slots carry addresses. The address an IE General uses is set on that component in the hardware configuration of the SIMATIC PC Station and reaches the adapter when the configuration is downloaded; slot assignment for these components is covered in Configuring WinAC RTX IE General slots in TIA Portal. The idea that slot 4 kept a preconfigured address cannot hold — a runtime slot stores no address. Read the configured station against what the adapter actually answers at:

Station slot Component Address it carries
Slot 2, subslot 2.2 (IF2) IE General 192.168.0.10/255.255.255.0
Slot 3 IE General 192.168.0.11/255.255.255.0
Slot 4 WinCC Runtime Advanced none — visualization software, no interface

The slot 3 download explains the first address the adapter reports. No slot in this station owns the second one, so its owner is on the Windows side.

Why the automatic setting never clears the alias #

Windows stores additional static addresses in a separate list from the primary address: the connection's TCP/IPv4 properties, Advanced tab, IP address list. Entries there survive reboots and dialog changes, and selecting 'Obtain an IP address automatically' changes only the primary address — a dialog that reopens showing automatic is reporting honestly. Microsoft's guidance for stray additional addresses is to delete each one in the TCP/IPv4 properties until only the primary remains; nothing else clears that list. With no DHCP server on this machine, the DHCP Enabled and Autoconfiguration Enabled lines in ipconfig /all show what actually filled the primary address. The 'Alternative configuration: Automatic' tab is the same fallback selector; leave it Automatic unless the customer's address plan says otherwise.

Map every address to its owner #

  • Run ipconfig /all and record, per adapter heading: description, physical (MAC) address, every IPv4 address with its mask, DHCP Enabled, Autoconfiguration Enabled, and gateway.
  • Match the physical address to the port your cable uses, so you edit the connection that faces the machine network. Two addresses on two ports is a deliberate two-network design such as configuring dual LAN HMI ports for two PLC networks; two addresses on one port is an alias that needs an owner.
  • Open the station configuration console — Start > Simatic > SIMATIC NET > Settings starts 'Set PC Station' — and read which physical adapter the slot 3 IE General is assigned to.
  • Expect the IE General address under that adapter heading; any address with no owner in the station project or the customer's address plan is the alias.
  • Open the mapped connection's advanced TCP/IPv4 settings: an alias listed there belongs to Windows and can be removed on the spot; a clean list with the address still active means a component reapplies it at startup.

An address on the wrong interface is its own fault class — why a PC fails to reach an HMI when Wi-Fi owns its address is the wireless twin of the same mistake.

Worked example: 192.168.1.2/255.255.255.0 against a 192.168.1.0/24 plant network #

Inputs: the alias the adapter reports is 192.168.1.2 with mask 255.255.255.0, taken from the ipconfig /all output; the customer's plant network for this example is 192.168.1.0/24 with a controller at 192.168.1.50 — an example allocation, and the arithmetic below is what you rerun against the real plan.

Rule (the IPv4 subnetting rule of RFC 950): two IPv4 addresses share a subnet when address AND mask gives the same network address for both, and a conflict additionally requires the alias to fall inside that subnet's host range.

Arithmetic:

  • 192.168.1.2 AND 255.255.255.0: 192 AND 255 = 192, 168 AND 255 = 168, 1 AND 255 = 1, 2 AND 0 = 0 → network 192.168.1.0
  • 192.168.1.50 AND 255.255.255.0: 192, 168, 1 as above, 50 AND 0 = 0 → network 192.168.1.0
  • Host range of that /24: network 192.168.1.0, broadcast 192.168.1.255, usable 192.168.1.1 through 192.168.1.254 — the alias sits inside it.

Result: alias and controller share one subnet with the alias in the host range, so with both on the same wire two MAC addresses answer ARP for one IPv4 address and connections to either device fail intermittently.

Decision: on a customer plan inside 192.168.1.0/24, the alias comes off the adapter before the panel ships. On a plan outside it, for example 10.82.4.0/24, the network addresses differ and there is no IP collision — the alias still ships only if the customer's plan reserves it in writing. Run the same two-line AND for the IE General address and the gateway against the real allocation before delivery.

Remove the alias and verify #

  1. Work from the panel's own display and keyboard, not across the network, and at a planned stop if the panel is already talking to a running line — removing an address can drop your session and the machine's communication paths in one keystroke.
  2. Record the state you are leaving: the ipconfig /all output and the station project.
  3. Alias listed in the advanced TCP/IPv4 address list: select it, choose Remove, leave only the primary address, and close every dialog with OK.
  4. List clean but the address still active: stop editing dialogs and open the saved configuration of the communication software or startup entry that reapplies it; change it there.
  5. Reboot and run ipconfig /all again — persistence across a reboot is the test, not a dialog screenshot.
  6. From a separate laptop on the same switch, ping both addresses; a ping from the IPC to its own address says nothing about the wire.
  7. Move an IE General address only in the hardware configuration and download the station again; a download applies the configured addresses but never cleans a stray Windows alias.

The decisions: alias present in the advanced list — remove that entry. List clean, address still active — reconfigure the component that reassigns it. Customer plan owns that subnet — remove the alias before delivery unless it is reserved. Two genuine networks needed — two ports, configured deliberately.

Questions asked

Is two IPv4 addresses on one adapter ever legitimate?

Yes. The advanced TCP/IPv4 settings keep a list of additional static addresses per connection, and a machine that must serve two subnets through one port uses it deliberately. The fault here is ownership, not the count: an undocumented address on a machine headed to a customer network. Any address that stays belongs in the customer's address plan and in the advanced list, where the next technician can find both.

How do I confirm a duplicate-address conflict on the customer network?

Take a separate laptop onto the customer switch, clear its ARP cache, then ping the suspect address and read the ARP entry it learned. The physical address shown should belong to the panel's port; if it belongs to another device, both machines are answering for one address and one of them must be re-addressed. Intermittent connectivity that recovers when either device goes offline is the same fault seen in operation.

Does removing the alias break the WinAC or WinCC communication?

Not if only the unowned address goes. PLC and HMI traffic run through the address configured for the IE General component, which lives in the hardware configuration and is reapplied by the station download, not through the Windows advanced list. Record the settings first, remove the alias, reboot, and confirm both runtimes exchange data with the controller before the panel leaves the bench.

Keep reading

  • Explainer

    Panel PC PROFIBUS and PROFINET IO RT together explained

    Yes. A panel PC configured with PROFIBUS DP12 can run as a PROFINET IO RT controller on one of its two onboard Gigabit Ethernet ports at the same time. What it cannot do is PROFINET IRT; decide the question by your application's required real-time class, not by the presence of PROFIBUS.

    Industrial networks

  • Troubleshooting

    Why Two Bridged VMs Cannot Ping Each Other in a PLC Simulation

    Both bridged guests carried the same MAC address, so the bridge could not forward frames between them: VM-to-VM and VM-to-simulated-PLC pings failed while every host-side test passed. Generating a new MAC address on one guest restored communication; distinct IPs, a shared subnet mask and ICMP-friendly firewall settings are the follow-up checks.

    Industrial networks

  • Troubleshooting

    Why a PC Fails to Reach an HMI When Wi-Fi Owns Its Address

    The wired programming connection fails because the laptop's Wi-Fi adapter already owns 192.168.0.20, the exact HMI address, so Windows treats the target as local and never sends packets out the Ethernet port. Disable Wi-Fi or move the HMI to an address no local interface owns, such as 192.168.0.25, and the connection returns.

    Industrial networks