Troubleshooting
Why a WinCC server IP change freezes all HMI clients
Short answer
Treat the synchronized freeze as a server-side fault with two leads: pin the process server to its fixed address instead of dynamic addressing, and find any add-on such as OPC software running on a demonstration license whose documented runtime limit matches the interval between freezes. Rebooting only resets the running session. Run the server without its SCADA software to rule the machine itself in or out.
On this page
All stations freezing at the same instant points at the shared process server, and the two findings you already have point at two different faults. An address that changes when WinCC starts means the server is picking up its network address dynamically instead of holding the fixed address every client was configured against; pin it. A freeze that returns about two hours after each startup matches the documented runtime limits of demonstration licenses on add-on software such as OPC servers and clients; find the component and put a proper license on it. Rebooting the server only ends the running session, which is why the fault always comes back. Work the leads below in order with the event log open, and the machine will tell you within one or two intervals which fault it has.
What the symptoms point to #
- Every station freezes at the same moment. A fault that reaches all clients together sits in the shared process server or in a service running on it, not in any single station.
- A reboot restores operation until the next interval. Rebooting ends a running session; it does not correct a configuration or install a license, so the fault returns on schedule.
- The server's address is replaced when WinCC starts. SCADA software does not assign addresses; the operating system does. The change belongs to the Windows network configuration, and the most common source is an adapter set to obtain an address automatically instead of holding a fixed one.
- The interval between freezes is fixed and restarts with the server. A timer that resets at every startup is the behavior of a demonstration license, not of a failing part or a random network event.
Before changing anything, record the WinCC version, every installed add-on with its license state, the intended server address, the address the server actually takes at startup, and the exact time from startup to each freeze. Those records decide every step that follows.
Why every client freezes together #
In a client/server layout the stations read process data from the server, not from the controller, so whatever stops the server from serving starves every screen in the same second. An address change does it on its own: each client holds its connection to the address it was configured with, and when the server turns up on a different address, all of those connections drop at once. The screens go static while the controller and the process keep running, the same dead-screen, live-process split described in Why a TP270 touch screen freezes but the PLC keeps running.
A demonstration license ends the data flow differently but with the same result: the limited component stops serving, and every station that depends on it stops updating. Both mechanisms produce one synchronized freeze, so treat the address change and the license state as separate leads and drive each to a verdict.
One safety note: while every client is frozen, nobody at the stations can see the process, so keep an independent indication of any value that needs an operator response until the fix has held through a full shift.
Pin the server to its fixed address #
- On the server, open the network adapter's IP properties and read the mode. Windows offers two: obtain an address automatically, which is the default, or specify one.
- Switch to specify and enter the intended address (for example 192.168.1.50), the mask that matches the network (for example 255.255.255.0), and the gateway if traffic leaves the segment.
- If plant policy keeps servers on DHCP, make a reservation instead: take the address the server currently holds and bind it to the server's network adapter on the DHCP server, so every lease hands back that same address.
- Check for a second network adapter. If one exists, confirm the fixed address sits on the adapter the clients actually reach.
- Restart the server and confirm the address before and after WinCC starts; restart once more and confirm again.
Decision: if the address now holds across starts and the freezes stop, the fault was addressing. If the address holds and the freeze still arrives on its old schedule, move to the license lead.
Find the component running on a demonstration license #
A runtime-limited demonstration mode is documented, ordinary behavior in OPC software. One OPC server vendor's support pages state that a configuration left in demo mode closes its client after two hours of running; another vendor documents a 30-minute demo timer in its OPC data client demo. A fixed interval that restarts with the process is exactly what an unlicensed add-on produces.
Check every component the server runs:
- Open the license or activation tool on the server and read the state of the SCADA runtime itself.
- List every add-on that bridges data: OPC servers, OPC clients, drivers, any third-party connectivity package.
- Read each state: full license, demonstration, expired.
- Compare each demonstration component's documented limit with your measured interval between freezes.
Any component in demonstration mode whose documented limit matches your interval is the prime suspect. Put the proper license on it, then run the server past the old freeze point at least twice before calling the fault closed.
Read the freeze interval from the event log #
The pattern is easiest to prove with numbers. The times below are a worked example of what the pattern looks like; take yours from the server's own event and diagnostic logs.
| Server start | Clients freeze | Interval |
|---|---|---|
| 05:40 | 07:40 | 07:40 - 05:40 = 120 minutes |
| 05:41, next day | 07:42 | 07:42 - 05:41 = 121 minutes |
| 13:15 | 15:15 | 15:15 - 13:15 = 120 minutes |
Three intervals within one minute of each other, each counted from the moment the server started, are a session timer. A DHCP lease does not behave that way: its renewal times follow the lease duration configured on the DHCP server, and rebooting the machine does not reset a lease clock to a fixed interval. A pattern like the table fits a license timer of that length, so the license lead comes first; an interval that drifts by tens of minutes points back to the network configuration and the address lead instead.
Prove it: run the server without its SCADA software #
The last test separates software from hardware:
- Stop WinCC and every supporting service, and leave the server sitting at the desktop.
- Wait past the freeze interval. If the machine still freezes with nothing running, the fault is in the base computer, not in the SCADA software.
- If it holds, start WinCC alone and wait the interval again.
- Start the add-ons one at a time, each followed by a full wait. The component whose start begins the countdown is the one to license or reconfigure.
One component at a time is slow, and it is the only method that turns a suspicion into a diagnosis; the same stepwise discipline is laid out in how to prove a PC-based HMI before replacing panel terminals.
If step 2 freezes, the machine itself is failing. When that computer is past repair, the like-for-like replacement is one of the industrial panel PCs built to run SCADA software continuously at the machine.
The decision for each case #
- The address changes when WinCC starts: set the fixed address, or the reservation where DHCP is mandatory. Pass mark: the address unchanged before and after WinCC starts, on two consecutive restarts.
- The freeze returns about two hours from every startup: a demonstration license is the cause until proven otherwise. Identify the component, install the proper license. Pass mark: two consecutive runs past the old interval.
- The interval drifts instead of holding: follow the address lead, then re-measure three intervals with the address pinned.
- The machine freezes with WinCC stopped: the fault is hardware; repair or replace the server computer.
- If the fault survives both corrections, hand the records — versions, license states, measured intervals, before-and-after adapter settings — to the vendor's support channel with the timing preserved.
Questions asked
Do all demonstration licenses run out at the same time?
No. Each product sets its own demonstration terms, and the documented lengths differ across OPC software: one vendor documents a 30-minute demo timer, and another documents a client that closes after two hours in demo mode. Measure your own interval and match it to the documented limit of the component you suspect, rather than assuming every demonstration mode shares one clock.
Should the HMI client stations also hold fixed addresses?
Yes. In a client/server layout a station holds its session by address just as the server does, so a client that changes its own address can drop out the same way. Set fixed addresses or DHCP reservations on every client too, and keep a written address plan for the whole line so a future reinstall or swapped network card does not quietly reintroduce dynamic addressing.
Where do I read the exact time from startup to freeze?
Use the server's Windows event log for the startup entry, and the SCADA or add-on diagnostic log for the moment data flow stops; the difference between the two timestamps is your interval. Take three consecutive intervals before you change anything, because a single measurement cannot tell a license timer from a lease event, and three give you the spread that identifies which lead to follow.
Does rebooting the server fix the problem permanently?
No. A reboot ends the running session, which resets a license timer and triggers a fresh address request, so both faults return on their own schedule. It is the right move to restore production, but treat it as recovery, not repair: the permanent fix is the pinned address plus a proper license on every component the server runs.
What should I hand over if the fault survives both fixes?
The WinCC and operating-system versions, the license state of every installed component, three measured intervals with their startup times, the adapter configuration before and after WinCC starts, and whether the machine freezes with the SCADA software stopped. That set lets the next diagnostic step, including the vendor's support channel, start from evidence instead of repeating your tests.