Troubleshooting
Why an EasyBuilder Pro simulator fails to connect to a LOGO! OBA8
Short answer
The online simulator connects to a physical LOGO! OBA8 only after the LOGO! network project's display connection is set as a server with an operator panel selected, and EasyBuilder Pro is set to OBA8, not LOGO 7. Point the driver at the LOGO!'s static IP address and run the simulation over Ethernet.
On this page
The failure is in the LOGO! network project, not in the HMI program. LOGO!Soft Comfort sets up each display connection as a client by default, and a client connection offers no way to pick an operator panel, so the Weintek driver has no peer to address. Set the LOGO!'s display connection as a server, tick the option to connect with an operator panel, and the online simulator connects to the physical OBA8 over Ethernet. In EasyBuilder Pro, select OBA8 for the PLC device, not LOGO 7, because the LOGO! 8 data mapping differs from the LOGO! 7 mapping.
Why the LOGO! side blocks the connection #
In LOGO!Soft Comfort, a network project's display connection defines who initiates. With the display left as client, the check box that lets you select an operator panel stays hidden, and an HMI driver cannot attach. Changing the display connection to server makes the operator panel selection appear; once a panel is selected, the LOGO! accepts incoming connections from that station. The same server-versus-client role logic comes up again in HMI OPC UA server vs client, where the direction of the connection decides what works and what silently does not.
Only one role needs to change. Keep the LOGO!'s own network inputs and outputs as they are; the change is confined to the display connection entry in the network project.
Why the device selection must be OBA8 #
In EasyBuilder Pro, open the system parameter settings, then the device properties for the PLC connection, and select OBA8 for the LOGO! 8 series. LOGO! 8 and LOGO! 7 use different data mappings: the same numeric address points at a different location in each, so a LOGO! 7 selection produces wrong reads and writes even if a link appears to work. If you are unsure which driver applies, the Weintek PLC connection guide lists the procedure and the required parameters for each supported LOGO! model.
Network setup and the connection test #
Give the physical LOGO! OBA8 a static IP address, put the PC running the simulation on the same subnet, and enter the LOGO!'s address as the PLC connection's target. For example, a LOGO! at 192.168.1.10 with a PC at 192.168.1.50 and a subnet mask of 255.255.255.0 are on the same subnet; the driver must be pointed at 192.168.1.10, not the PC's own address. Devices on the same subnet is the standard arrangement for direct Ethernet commissioning across PLC families.
Start the online simulation from EasyBuilder Pro. The Quick Start sequence is set the PLC device parameters, create the objects, then run offline or online simulation, and online simulation communicates with the real PLC over the network. Prove the link rather than assuming it: unplug the Ethernet cable from the LOGO! while the simulation runs. The simulator raises a communication error, and the screen recovers when the cable goes back. That error is the confirmation that the simulator was live against the physical PLC. The same pull-the-cable check belongs in any commissioning bench, alongside the wider discipline in testing HMI simulation against a live PLC.
If the connection still fails after the server change, check that nothing else on the network holds the LOGO!'s address, and that Windows is routing to the Ethernet adapter rather than a wireless one; an adapter owning the wrong default route blocks first connections in exactly the way described in why a PC fails to reach an HMI when Wi-Fi owns its address.
When the link works but the output does not move #
A connected simulator only proves transport. If toggling the button leaves the LOGO!'s Q1 off, the button is writing an address that the LOGO! program is not reading. Three things must line up: the button's address under the OBA8 mapping, the network input defined in the LOGO! program, and the logic that drives Q1 from that input. If any address was authored while the device was still set to LOGO! 7, rewrite it under the OBA8 mapping, because the numeric locations differ between the two series. If the LOGO! program never assigns Q1 from the network input, no HMI address can fix it; that logic change is made in LOGO!Soft Comfort and transferred to the module.
Worked example: say the LOGO! program has a network input assigned as the first digital input of the OBA8 mapping, and Q1 is a relay output driven by an AND of that network input with a local input I1. The button in EasyBuilder Pro is set as a momentary bit button writing that same mapped address, with the write address in decimal under the OBA8 device entry. Pressing the button sets the network input bit; the LOGO!'s AND block sees it, I1 is true, and Q1 closes. If the button had been written against the LOGO! 7 mapping instead, the same address would land in a different internal location, the AND block would stay low and Q1 would stay open with a healthy connection on screen.
Decision #
Run the checks in this order and stop at the first one that describes your symptom:
- Connection failed: set the LOGO!'s display connection to server and select an operator panel in LOGO!Soft Comfort, select OBA8 in EasyBuilder Pro, point the driver at the LOGO!'s static address on the same subnet, and rerun the online simulation.
- Connected but output dead: leave the connection alone and trace the button's address through the OBA8 mapping into the LOGO! program's network input and the logic that drives the output.
- Software-only simulators on both ends: abandon that path and connect to the physical LOGO!.
Questions asked
Can two simulators talk to each other, with LOGO!Sim on one PC and the Weintek online simulator on another?
No. The LOGO!Soft Comfort simulator and the EasyBuilder Pro online simulator cannot establish a working link with each other in this arrangement. The online simulation path that works is the PC running the simulator connected by Ethernet to a physical LOGO! OBA8 on the same subnet. If you need a second station, the driver also supports a real HMI connected alongside the simulator.
Which LOGO! selection does EasyBuilder Pro need for an OBA8?
Select OBA8 in the system parameter settings, under the device properties for the PLC connection. LOGO! 8 and LOGO! 7 do not share the same data mapping, so a LOGO! 7 selection points every address at the wrong location even though the driver connects. The driver list in EasyBuilder Pro covers a wide range of controllers, so the exact model string matters.
The simulator connects but my button still does not switch Q1. What now?
Connection and data mapping are separate checks. Confirm the button writes the address in the OBA8 mapping that corresponds to the network input your LOGO! program reads, and that the LOGO! program logic actually drives Q1 from that input. If any address was chosen while the device was set to LOGO! 7, re-enter it under the OBA8 mapping, because the underlying data locations differ.
How do I prove the simulator is really talking to the LOGO! and not showing cached data?
Unplug the Ethernet cable from the LOGO! while the simulation is running. The simulator should raise a communication error within its polling timeout, which confirms the live link, and reconnect cleanly when the cable goes back. This is the same idea as verifying a link by pulling it, rather than trusting a screen that happens to show values.