Troubleshooting
Why an Edge App Fails to Install on a Unified Comfort Panel
Short answer
An Edge app fails to install on a Unified Comfort Panel because one of three separate limits is exceeded: free storage for the package plus unpacking, total panel RAM shared with everything else, or the 768 MB cap on data memory across all installed apps. Compare each limit against the panel's own readings.
On this page
- Three separate limits decide the install
- Check storage with unpacking room included
- Check the panel's shared RAM
- Check the app's data-memory limit against the installed total
- Worked example: a 537 MB package with a 200 MB data limit
- Fix the failed limit and install again
- When every check passes and the install still refuses
- When the app installs and then stops
- Questions asked
An Edge app fails to install on a Unified Comfort Panel for one of three separate reasons, and the refusal rarely names which one: the package does not fit free storage once unpacking space is counted, the panel's shared RAM is already committed, or the app's configured data-memory limit pushes the installed total past the panel's documented 768 MB data-memory ceiling. The third is the one most often missed — the Operational Quantities Memory figure the package carries — and the fix is to set that limit under the ceiling with room to spare, re-export the app and install again. Work the three checks in order against the panel's own readings and the blocked limit identifies itself.
Three separate limits decide the install #
One precondition sits before all three checks: Edge management has to be running. The Enable SIMATIC Edge option ships deactivated, and until it is switched on the panel has no Edge management screen and nothing to install into.
After that, a refusal is one of three limits, and they fail independently — an app can pass two and fail the third, which is why a glance at package size settles nothing.
| Limit | Where the panel shows it | What blocks the install |
|---|---|---|
| Storage | upper right of Edge management | package plus unpacking room exceeds free space |
| Total RAM | RAM figure in the panel summary | configured limit or real usage exceeds what is left |
| Operational Quantities Memory | configured in the app package | installed apps' reserved total would pass the data-memory cap |
Work them in this order:
- Storage first — the cheapest to fix, and its refusal is easy to misread as a memory problem.
- Shared RAM second — it decides whether the app can run alongside the panel's other work at all.
- The app's data-memory limit third — it is set in the package, not on the panel, so it travels with every export you try to install.
Check storage with unpacking room included #
The .app file must fit inside the Storage limit shown in the upper right of Edge management, and installation needs temporary room to unpack the package, so plan on free space of about twice the package size for the duration of the install. When the install finishes, the unpacked app is what remains and the temporary copy goes away.
Decision: if the Storage reading is under twice the package size, remove apps and data you no longer use, or rebuild the package with fewer bundled assets. Do not touch the app's data-memory limit to fix a storage refusal; the two limits measure different quantities.
Check the panel's shared RAM #
The RAM figure shown in the panel summary is the total available to everything on the panel: Edge apps, the WinCC runtime project and the panel's own functions. No share is reserved for your app. The install refuses when the app's configured limit is larger than the RAM the panel has left; a stop shortly after start means actual usage outgrew that same reading.
Decision: with the production WinCC project loaded and the other apps running, the app's measured usage has to fit inside the RAM the panel reports free. If it does not, cut the panel's other workload first — an idle project, an app nobody uses — before touching the app itself.
Check the app's data-memory limit against the installed total #
Operational Quantities Memory is the RAM an Edge app reserves for its data at runtime, and it is the figure the install check enforces. The documentation for these panels caps the total data memory that all installed apps may reserve at 768 MB, and the panel refuses an install whose configured total would land above that cap.
That mechanism explains refusals that look wrong: an app with a modest limit still fails when the apps already installed have reserved most of the cap. Subtract every installed app's configured limit from the cap; the new app has to fit in what remains. As working practice, keep a single app to roughly 700 MB even where a higher figure would technically pass, so later installs keep room.
The limit is set on the app, not the panel. It lives in the app version's System settings in Industrial Edge App Publisher, and in a Docker Compose file it appears as mem_limit, with mem_reservation alongside it. Change it there, rebuild, re-export — the corrected figure travels with the new package.
Worked example: a 537 MB package with a 200 MB data limit #
This works the case in the shape it arrived: a Node.js app packaged by Industrial Edge Publisher. The package size and the configured limit below are example values — read yours from your own package and panel; the cap is the documented one.
Inputs:
- Package size: 537 MB for the .app file (example value for an app of this kind).
- Configured data-memory limit: 200 MB (example value; measure your own app before relying on a figure this low).
- Panel data-memory cap: 768 MB, documented for Unified Comfort Panels.
- Free storage: the Storage figure in Edge management, read from your panel.
Rule in words: installation needs free storage of about twice the package size, and the memory check adds the new app's configured limit to the limits already reserved by installed apps, refusing when the sum passes the cap.
Arithmetic:
- Storage during install: 2 × 537 MB = 1074 MB, about 1.07 GB free.
- Headroom this app leaves under the cap: 768 MB − 200 MB = 568 MB for all other installed apps combined.
- The same app configured at the full cap would leave nothing for any other app, and the install would refuse on any panel that already runs one.
Result: the app installs only when the Storage figure shows at least 1074 MB free and the other installed apps' limits total 568 MB or less.
Decision: if storage reads under 1074 MB, free space or slim the package. If the installed apps already reserve more than 568 MB, lower this app's limit as far as its measured usage allows, or lower theirs. A 200 MB setting with both thresholds met installs; that is the whole check.
Fix the failed limit and install again #
- Read the three figures: the Storage reading in Edge management, the RAM figure in the panel summary, and the app's configured limit in the version's System settings in Industrial Edge App Publisher, or as mem_limit in its Docker Compose file.
- Correct only the failed check. Storage: free space or slim the package. Shared RAM: cut the panel's other workload. Data memory: lower the app's limit to sit above its measured usage and under the cap with headroom.
- Rebuild and re-export the package so the corrected limit travels with the .app file; no panel-side setting changes it.
- Install once for each change. A retry that succeeds after lowering the limit identifies the app configuration as the blocker; a retry that succeeds after freeing storage identifies staging space.
- If it refuses again, capture the complete message — the text names the refused resource and points at the next check, not at package size.
When every check passes and the install still refuses #
The remaining refusals are about the package, not the panel's resources. The common one is a container image built for the wrong CPU architecture, which fails before any memory limit is consulted — the Unified Comfort Panel CPU architecture for Docker images article works that case in detail. An export interrupted partway produces the same class of refusal, so rebuild and re-export once before digging further.
When the app installs and then stops #
A successful install followed by a stop is a different failure: the install check passed against the configured figures, and the app's real usage outgrew them at runtime. Watch the app's memory while it runs its normal workload — the panel's developer mode exposes the container's usage — and if it stops, read the app's logfiles and line the stop time up with any memory-exhaustion message.
Decision: raise the configured limit only within what the cap and the panel's free RAM allow. If the app cannot run under the cap, cut what it holds in memory — shorter buffers, shorter history and log retention — or move it to dedicated Industrial Edge hardware whose documented ceiling fits it. An app redesigned to fit beats an app living at the edge of a limit.
Questions asked
Can an Edge app on a Unified Comfort Panel get more than the panel's data-memory ceiling?
No. The 768 MB cap belongs to the panel, not the app, so no app setting raises it. If an app needs more data memory than the cap allows once every other installed app is counted, cut what the app keeps in memory, or move the app to dedicated Industrial Edge hardware, which publishes its own memory figures in its own documentation.
Why is storage tight on a panel that otherwise runs normally?
App storage sits on the panel's data memory card. For these panels the manufacturer recommends an SD memory card of at least 32 GB in that role, so a smaller or nearly full card leaves little room for packages plus the temporary space an install needs to unpack them. Read the free storage figure in Edge management before blaming memory.
Does lowering the app's data-memory limit risk a crash later?
Only if it drops below what the app really uses. The configured figure is a reservation the install check enforces; at runtime the app still has to live inside it, and a container that outgrows its reservation gets stopped. Measure usage while the app runs its normal workload, keep headroom above that measurement, and keep the reservation under the panel cap.