IMDTouchKnowledge BaseShop main store

Explainer

Why an HMI panel runs its own project beside a LOGO 8

HMI and touchscreens Published 6 min read

Short answer

A LOGO 8 program never moves to the panel: it is downloaded to the LOGO and runs there. The HMI panel needs its own engineering software, such as WinCC in TIA Portal, and its own visualization project that exchanges data with the controller over an Ethernet connection. Engineer and download the two projects separately, then point the panel connection at the LOGO's IP address.

On this page
  1. Two projects, two devices, one connection
  2. What goes into the panel project, and what stays out
  3. Where the LOGO! program actually goes
  4. Match the versions on both sides
  5. A documented combination you can copy
  6. When the LOGO!'s own display or web pages are enough
  7. The decision
  8. Questions asked

The LOGO! control program never runs on the HMI panel. It is downloaded to the LOGO! and executes there, whether or not any panel is attached. A panel added to a LOGO! installation — including a 12-inch one on a thermal installation — needs its own engineering software and its own visualization project, which reads values from and writes commands to the controller over an Ethernet connection. So the LOGO! program is not inserted into the panel software: you engineer two separate projects, download each one to its own device, and configure the connection between them. This page separates the two projects, gives a documented panel-plus-LOGO! combination with the versions and addresses it used, and ends with the decision for each case.

Two projects, two devices, one connection #

Two pieces of software and two pieces of hardware do this job, and each project has exactly one download target:

Job Engineered in Runs on
Control logic: heating stages, pumps, valves, interlocks LOGO!Soft Comfort project LOGO! controller
Screens, setpoint entry, operator commands Panel project in WinCC inside TIA Portal HMI panel
Data exchange Connection entry and tags in the panel project Ethernet link between the two devices

The LOGO! executes its program from its own memory. The panel project renders controller values on screens and sends operator commands back as writes to the controller. Nothing in the LOGO! project file belongs inside the panel project, and nothing in the panel project changes how the LOGO! logic behaves.

What goes into the panel project, and what stays out #

The panel project holds the screens, the tags that reference the controller data those screens show, and one connection entry pointing at the LOGO!'s IP address. The engineering tool must document a connection to LOGO! for the version you own; if that connection entry is missing from your tool version, the combination stays closed until you update the tool — the situation described in when the HMI software has no driver for your PLC.

Operator commands belong only to the functions you deliberately expose: starting and stopping a stage, changing a setpoint. Keep every protective and interlocking function in the LOGO! project so the machine stays safe when the panel is off, disconnected or showing stale values.

Where the LOGO! program actually goes #

Download the control project from LOGO!Soft Comfort to the LOGO! itself, over Ethernet for the LOGO! 8 generations. The controller's Ethernet parameters are set in the Ethernet connections configuration under the Tools menu, where you fill in the IP address, subnet and gateway; that address is what the panel project's connection entry points at later.

For a first connection that will not come up, the documented routine for LOGO! 0BA8 Ethernet problems is to connect the PC straight to the LOGO! with no router in between and to disconnect the PC from any other network while you transfer.

The instinct to insert the LOGO! program into the panel software mixes up two different things: how a project reaches a device (a download) and how two running devices exchange data (a driver connection). Separating the HMI transfer method from the PLC driver covers that distinction for any panel.

Match the versions on both sides #

On the controller side, the programming tool has to know the hardware generation: LOGO!Soft Comfort V8.3 supports LOGO! 8.2 and earlier hardware, and LOGO! 8.4 hardware requires LOGO!Soft Comfort V8.4 or later. With the wrong tool for the generation, the LOGO! is not even detected for a transfer, let alone for a panel connection.

On the panel side, confirm before you buy that the panel model, its firmware and its engineering tool version document a connection to your LOGO! generation. The combination used in the worked example below — WinCC Advanced in TIA Portal 15.1 against LOGO! 8.FS4 with a KTP400 — is one pairing that was built and run; it is not a claim that every panel or every tool version connects to every LOGO!. Verifying the engineering tool before committing to a panel is exactly the discipline in checking HMI engineering software before a panel replacement.

A documented combination you can copy #

One published walkthrough puts a LOGO! 8.FS4 controller and a Siemens KTP400 panel on one Ethernet link, with LOGO!Soft Comfort V8.2 as the controller tool and WinCC Advanced in TIA Portal 15.1 as the panel tool. That is this page's split in practice: two tools, two projects, two download targets, one Ethernet connection.

Give the two devices addresses on the same subnet, for example the LOGO! at 192.168.0.1 and the panel at 192.168.0.10 with a 255.255.255.0 mask (example values). The check is arithmetic: both addresses fall between 192.168.0.0 and 192.168.0.255, so their network portion, 192.168.0, is identical and the devices exchange data directly. If the panel were instead set to 10.0.0.10, its network portion 10.0.0 would differ from the LOGO!'s 192.168.0, and no data would flow until one address moved into the other's subnet.

For the click-by-click side of the panel project, a walkthrough of configuring LOGO! panel visualization in TIA Portal shows the connection, tags and screens being built against a LOGO!.

When the LOGO!'s own display or web pages are enough #

Two options live entirely inside the LOGO! and skip the second project altogether. The LOGO! TDE text display communicates with LOGO! 8 directly and gives status text and basic operation at the cabinet with no panel project at all. The LOGO!'s own programming environment also develops the control logic and a web visualization in one place, so the pages transfer with the program and open in a browser on a PC or tablet.

For a job described as watching the installation run and acting on a few functions, start here: a handful of values and commands is exactly what these two cover. A 12-inch panel project earns its keep when you want multiple screens, trends or recorded values, or a touch workflow sized for an operator who did not program the machine.

The decision #

  • A few values and a few commands: build nothing new. Use the LOGO!'s own display or its web visualization and skip the panel project entirely.
  • A graphic panel at the machine: two projects, downloaded separately. Keep the control logic in LOGO!Soft Comfort and download it to the LOGO!. Build the screens in WinCC Advanced in TIA Portal with a version matched to your LOGO! generation, point the connection entry at the LOGO!'s IP address, and download the panel project to the panel. Interlocks stay in the LOGO! project.
  • The visualization outgrows a panel, or you want PC-class hardware at the machine: the architecture does not change — the LOGO! keeps the logic, and a touchscreen computer runs only the visualization project, which is the role of industrial panel PCs.

Questions asked

Does the machine stop if the HMI panel is switched off or the Ethernet link drops?

No. The control program runs in the LOGO's own memory and keeps executing without the panel. What you lose is the screens and the operator commands, not the control itself. That is also why every protective and interlocking function belongs in the LOGO project: it has to act even when no panel is connected, while the panel side only ever reads and writes data.

Can one panel visualize the LOGO and a larger PLC at the same time?

Often, yes, but only through documented connections. A panel project can hold more than one connection entry, and each entry needs an engineering-tool driver for that exact controller family and generation, with the panel's ports and connection limits supporting the combination. Check the documented connection list of your tool version before promising both controllers to one panel.

Do I need panel software just to watch a few LOGO values?

Not for a handful. The LOGO's web visualization is developed in the same tool as the control logic and opens in a browser on a PC or tablet, and the LOGO TDE text display talks to the controller directly with no second project. Move to a full panel project when you want several screens, trends or recorded values, or a large touch display.

Which tool does which job, and which versions pair with which LOGO generation?

LOGO Soft Comfort builds and downloads the control logic to the controller; WinCC inside TIA Portal builds the panel project for a Siemens panel. The controller tool must know the hardware generation: LOGO Soft Comfort V8.3 supports LOGO 8.2 and earlier, while LOGO 8.4 hardware requires LOGO Soft Comfort V8.4 or later.

Keep reading

  • How-to

    Displaying safety controller status on an HMI panel

    Read status out of the safety controller's communication interface — Modbus TCP or RTU is the common route — with a matching HMI driver, and map each exported signal by location, width, bit position and polarity after checking raw words against the controller's online diagnostics. Keep every object read-only: the safety function stays in the controller and the display stays diagnostic.

    HMI and touchscreens

  • How-to

    Where to save C-more panel IP settings in the project

    The C-more project does store the panel's IP address and subnet mask: enter them under Setup > Touch Panel Network > Ethernet Port and save the project. That entry is a record, not a lock — the panel's System menu can still change the live values — and it is separate from the PLC destinations, so a controller address change still means editing each affected project and re-transferring it to every panel.

    HMI and touchscreens

  • Troubleshooting

    Why a Micro800 Program Runs but the C-More Panel Reads Nothing

    Work four layers in order: USB enumeration under CCW, the program's task assignment and Run mode, the IEC 61131-3 TIME conversion, and tag scope. Keep TIME inside the logic, convert DINT milliseconds once with ANY_TO_TIME at the preset, and make every panel-facing tag global. A clean download proves nothing until each layer checks out.

    HMI and touchscreens

Why a USB Joystick Cannot Drive PanelView Tags