Troubleshooting
Why an MP 377 shows image is corrupted after a power loss
Short answer
Power lost during an OS update leaves an MP 377 in the boot loader's transfer mode: it prints image is corrupted, then waits for a new image, and it will not answer the network services a booted panel provides. Repeat the documented OS update from WinCC flexible or ProSave, enter the panel's MAC address in the transfer options, and hold power until the progress bar finishes.
On this page
An MP 377 that stops at ERROR image is corrupted and Waiting for image update after a power cut is not a dead panel, and its Ethernet port is not the fault. The power was lost while the operating system was being written into flash; the interrupted write left an image the boot loader rejects, and the loader has parked the panel in its transfer mode, listening for a replacement image. Recovery is an OS transfer, not a network troubleshooting job: repeat the documented OS update from WinCC flexible or ProSave, identify the waiting panel by its MAC address in the transfer options, and hold power until the write finishes. The sections below read the four boot lines, set up the transfer, and define what counts as fixed.
What the four boot lines tell you #
Each line on the screen names a stage of startup, and the sequence is the diagnosis:
- Enabling update mode — the boot loader started and chose the update path, so the loader itself survived the power loss.
- Loading image from flash — the loader attempted to read the stored OS image from flash memory.
- ERROR image is corrupted — that read failed its integrity check: the interrupted write left image content the loader refuses to start.
- Waiting for image update — the loader stopped here deliberately, holding the panel in transfer mode and listening for a replacement image.
Four lines carry the whole decision: the boot loader is alive, the stored image is bad, and the transfer function is running. The fix is a fresh image transfer through the documented procedure — not a repair of the network, not a different driver, and not a rebuild attempted from a PC that never connects.
Why the panel stops answering TCP/IP #
A normally booted MP 377 answers ping and accepts project transfers at the address configured in its project. Those services belong to the operating system, and the operating system is exactly what failed to load. The panel now sits in the boot loader's update environment, which listens for an image transfer rather than for a driver or a ping. That is why the documented procedure has you enter the panel's MAC address in the options before you initiate the OS update: without that entry, WinCC flexible cannot find the waiting panel, no matter how clean the cable and the switch are.
This inverts the usual network logic. A failed ping proves nothing about the Ethernet port, and a lit link LED proves nothing about the transfer service. Match the connection method to the boot state printed on the screen, not to the one that worked when the panel was healthy. The decision follows from the boot lines: skip the network hunt and set up the documented update transfer against the waiting panel.
Repeat the OS update against the waiting panel #
The transfer is quick to set up and unforgiving about identity — every step confirms that the panel, the tool selection and the image are one device and one release:
- Read the nameplate and keep it at hand. The device designation and order number identify the panel; the tool's device selection and the OS image must both match them. A transfer aimed at the wrong panel type is one of the documented causes of a failed update.
- Fetch the image built for that exact device and release — the same discipline as getting the right firmware file for a legacy HMI panel, from the manufacturer or its authorized distributors only.
- Connect the engineering PC to the panel's Ethernet port the way the procedure for this panel family specifies, and confirm link indication at both ends.
- Start the update from WinCC flexible with the Update OS command in the Project > Transfer menu, or run the same OS update from ProSave when no engineering session is open. Enter the MAC address in the options before you initiate the transfer.
- Let the panel restart as the update begins; a progress dialog appears on the panel while the image loads.
- Keep the plain image update as the first attempt. The same documented procedure offers a reset to factory settings for a panel the plain update will not bring back — hold that heavier variant in reserve rather than opening with it.
Judge the write by the progress bar, not the clock #
The screen can look abandoned while flash is being written. That stillness sits exactly where the last update died, so hold power, leave the cable alone, and let the tool drive the operation.
Worked example (illustrative sizing, not a measured figure for this panel): on a 100 Mbit/s link, a 64 MB image carries 64 × 8 = 512 Mbit, so the wire time alone is 512 ÷ 100 = 5.12 s. Protocol overhead and flash programming stretch the real write into minutes, and the flash write is the slow part. That gap is the trap: elapsed seconds cannot tell you whether the write has finished. The panel restarts itself once the image is in place, and only the tool's completion status plus that restart count as done.
Treat this write as the operation that must not lose power twice: a second interruption can reach the flash regions that keep the update path itself alive.
After the image loads #
A finished transfer is not yet a fixed panel. The panel should boot to its startup screen and accept a normal project transfer again. The OS update does not reinstall your application, so reload the runtime project from the engineering source or from the panel backup made before the original update; if that source no longer exists, the article on recovering an HMI program when the source file is lost covers what remains to try. Before the panel returns to service, find whatever dropped the power during the write, and take a fresh full backup so the next recovery, if one ever comes, is an image transfer plus a restore.
When the update will not take #
Refused transfers trace to three documented causes: the wrong panel type selected in the tool, the wrong communication interface or cable, and a panel that is not in a transfer-ready state. Work them in that order, and include the identification entry from the recovery setup — a missing MAC entry is the most common reason the tool never sees the panel at all. Detection failure points at interface and identification; detection without a completed write points at the image, the supply or the cable.
If detection succeeds but the write fails at the same stage on every attempt, the procedure is no longer the suspect — the flash is. On a panel of this generation, repeated write failures at one stage end the repair decision: replace the terminal. Bringing the machine back on industrial panel PCs returns it to service faster than coaxing a flash chip that no longer holds an image.
Questions asked
Does the OS update wipe the project stored on the panel?
Plan for yes. The update writes the operating system layer, and the factory-settings variant of the same procedure explicitly clears stored data. Even when a plain image update leaves the application untouched, the safest recovery plan reloads the runtime project from your engineering source or backup — treat anything stored on the panel as unverified until the machine proves it after boot.
Can I just set an IP address for the panel to make the transfer connect?
No. The address configured in the project belongs to the operating system that failed to load; the update environment does not read it. The documented transfer identifies the waiting panel by its MAC address, which is why the options field exists. Re-entering project addresses, re-cabling or rebooting into old configurations will not change what the transfer tool sees.
Can a second power cut during the recovery write finish the panel?
Yes, and it is the one real risk of this repair. The first interruption destroyed the OS image but left the boot loader intact; a second interruption mid-write can take the update path itself. Work on a supply you have checked at the terminals, and if the panel afterwards no longer shows the update screen, the loader's fallback is gone and the panel goes back for service rather than through another procedure.
Where does the OS image file come from?
From the panel manufacturer or its authorized distributors only — the image must match the exact device and the engineering software release. An image for a sibling model or a different release can be refused by the loader or load and then misbehave, and third-party copies are unverifiable. Match the order number on the nameplate to the image designation before you start the transfer.
How do I stop this happening at the next update?
Look for the cause of the first drop before you schedule anything: a loose 24 V DC terminal, a tripped breaker or a cycled maintenance switch will corrupt the next image the same way. Back up the panel before the update, and record the tool release, image designation and connection setup that worked so the next recovery is a repeat, not a rediscovery.