Explainer
Why EasyBuilder Pro Embedded Windows Need Indexed Scrolling
Short answer
EasyBuilder Pro on a cMT3162X does not confirm native scrolling of an embedded window larger than its frame. The supported design is the index feature: fixed on-screen objects reference LW-0 plus the runtime index value, so data scrolls through memory while the graphics stay in place.
On this page
- Can an embedded window in EasyBuilder Pro scroll when it is larger than its frame?
- How does the index feature scroll through LW and RW registers?
- How do you size the index increment for your records?
- How do you configure and test an indexed scrolling screen?
- When is a Recipe View object the better choice for member records?
- What is the decision for each case?
- Questions asked
EasyBuilder Pro on a cMT3162X does not confirm native scrolling of an embedded window that is larger than its frame, so a screen that holds 20 of your 50 member records cannot be made to scroll the extra records into view graphically. The supported design is the index feature: the visible input objects stay fixed on the screen, and the index value redirects them to successive locations in HMI memory. This article explains how that works, how to size the index increment for your record layout, and when a Recipe View object is the better choice.
Can an embedded window in EasyBuilder Pro scroll when it is larger than its frame? #
The documentation does not confirm that EasyBuilder Pro provides native scrolling of a larger embedded window inside a smaller frame, so that behavior cannot be relied on in a project. What it does support is two data-oriented alternatives: index registers on LW or RW objects, and the Recipe View object for record-oriented storage. That is why the separate explanation of why an oversized HMI screen cannot show a scroll bar also applies here — the limitation is structural, not a setting you overlooked.
The practical consequence for a 50-member entry screen is that you stop trying to move graphics and start moving data. The same three input fields stay in place and display member 1, then member 2, and so on, as the index advances. This is a different mental model from a scrolling page, but it reaches all 50 members from one screen, which is what the design needs.
How does the index feature scroll through LW and RW registers? #
The index feature makes an object reference its configured register plus the current index value, so an object configured for LW-0 displays LW-0 plus the index at runtime. Jogging the index during runtime therefore changes which memory location the fixed object displays. In the terms the manual uses, the index register redirects the displayed address without the object moving on screen.
This works on HMI-local LW registers and on the HMI RW registers, and the same data-transfer mechanisms that move values between the PLC and HMI registers apply to the records once they are indexed. In the worked example below, one runtime value controls where all the indexed objects read at once, which is what lets a first-name, last-name and email triplet move together through the member list.
How do you size the index increment for your records? #
The index increment must equal the number of registers one member occupies, and in this example that is three, because each member has a first name, a last name and an email field. If member 1 is stored at LW-0 through LW-2 and member 2 at LW-3 through LW-5, an index value of 3 moves the display from member 1 to member 2: the object configured for LW-0 reads LW-0 + 3, which is LW-3, and the email object configured for LW-2 reads LW-2 + 3, which is LW-5.
The register count per member is not defined by the documentation — it comes from your own object mappings. Count the registers each field is mapped to, including any padding between members, before choosing the increment. An unsupported increment mixes fields from adjacent members on screen, for example a first name from member 4 next to an email from member 5, so verify the layout before commissioning the screen.
How do you configure and test an indexed scrolling screen? #
Configure the index first, then verify it with distinguishable data before the screen goes near a machine. The steps below are illustrative for the 50-member entry screen:
- Map the visible first-name, last-name and email objects to the registers of member 1, for example LW-0 through LW-2 in this example layout.
- Apply the same index mechanism to all three objects so they move together through the member data.
- Add controls that jog the index up or down by the member stride of three registers each press, and a display that shows the current member number so the operator knows which record is open.
- Enter distinguishable data into each member, jog the index, and confirm that every field shows the corresponding member without mixing fields from adjacent records.
- Repeat at both ends of the range — member 1 and member 50 — and confirm the index controls do not walk the display past the allocated register block.
One related design that reuses the same mechanism is popup screens selected at runtime by an index value, which suits machine stations or recipes that need a whole window per item rather than three text fields; the article on configuring indexed popup screens in EasyBuilder Pro for M580 walks through that configuration.
When is a Recipe View object the better choice for member records? #
A Recipe View object is the better choice when the 50 members need record-oriented management after entry — recall, save and transfer as named sets. The index design is for continuous data entry backed by LW or RW registers; the Recipe View design is for records that live as structured entries with a browsing and selection workflow. The decision condition is simply how the completed records will be used downstream: if some other screen or process selects a member by name, evaluate Recipe View; if the data is only entered and read back by address, index registers are enough.
If the fields are strings on a Siemens PLC, indexing behaves differently because string storage and addressing change how a record stride is counted, and the article on configuring cMT3162X indexed lists with Siemens strings covers that case in detail.
What is the decision for each case? #
The decisions, per case, are: embedded-window scrolling — not confirmed by the documentation, so do not design around it; indexed LW or RW objects — supported, and the right choice when your inputs are backed by HMI registers and one member stride is applied consistently, as with the three-register stride in the example; Recipe View — supported, and the right choice when the members need record-level recall and management. For this 50-member screen, the index design with a three-register stride and fixed input objects delivers all 50 members from one screen.
One safety note: member data on these screens should never replace a safety-rated identifier or interlock check — a mis-indexed record can display the wrong member with no visual warning, so keep personnel-critical decisions out of indexed data entry.
Questions asked
Can I scroll a large embedded window inside a smaller frame in EasyBuilder Pro?
Native graphical scrolling of an embedded window is not confirmed by the documentation. The established alternative is the index feature: keep the objects fixed, map them to LW or RW registers, and jog the index value so the objects read successive record locations in HMI memory.
What does an object configured for LW-0 actually address when an index is applied?
It addresses the configured register plus the current index value, so LW-0 with an index of 3 reads LW-3 at runtime. In the worked example where each member occupies three registers, an index that advances by three steps one whole member at a time.
When should the 50 member records use a Recipe View object instead of index registers?
Use a Recipe View object when the entered members need record-oriented management after entry, such as recall, save and transfer as named sets. The index design is for continuous data entry backed by LW or RW registers, so choose based on how the completed records will be used.