Why EasyBuilder Pro imports no user-defined tags

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

When an EasyBuilder Pro CSV import finishes but the user-defined tags stay absent, the file's columns do not match the address tag library format, and in this case the project also carried the Yaskawa MP Series Ethernet extension driver where an MP2600iec Modbus TCP connection needs the Modbus TCP/IP driver. Switch the driver, export a few manually created test tags as a CSV template, move the source values into the matching columns, re-import, and confirm the entries in the address library.

On this page
  1. The dialog confirms the file, not the tags
  2. Select the Modbus TCP/IP driver for this connection
  3. Build the CSV from an exported template
  4. A worked count that proves the import
  5. Assumptions that bring the failure back
  6. Questions asked

An EasyBuilder Pro import that finishes without an error is not a pass. When the dialog completes and the user-defined tags stay empty, two project faults produce exactly that result, and both were present in this case: the CSV does not follow the address tag library's column format, and the device list carries the Yaskawa MP Series Ethernet extension driver where an MP2600iec Modbus TCP connection needs the Modbus TCP/IP driver. A file that opens cleanly in a spreadsheet proves the content is readable, not that its values sit in the fields the importer maps. The fix is short: select the Modbus TCP/IP driver, export a few manually created test tags as a template, move the source values into the matching columns, import again, and confirm the entries in the address library.

The dialog confirms the file, not the tags #

The reported failure: the import runs from the Address menu, raises no error, and the user-defined tag list stays empty while the source file shows every tag name in a spreadsheet. That pairing rules out a corrupt or missing file and points at field mapping: the values exist, but not in the columns EasyBuilder Pro reads. The case involved a cMT2108X2 running EasyBuilder Pro V6.08.02.322 (build 2023.04.13), and nothing in the cause is specific to that build, because the CSV layout and the driver selection are project contents.

What the symptom tells you:

  • A completed import action means the file was accepted, not that entries were registered; the only pass criterion is the user-defined tags list in the address library.
  • A readable CSV confirms content, not field position, so a column mismatch can end with an import that appears to finish while the intended tags never appear.
  • The driver and the file are separate faults; neither one corrects the other, so fix them as separate items.

Select the Modbus TCP/IP driver for this connection #

Trace the request path first: the HMI sends Modbus TCP requests over Ethernet to the MP2600iec, and the driver chosen in the device list defines how EasyBuilder Pro addresses and interprets that endpoint. For a Modbus TCP path the driver is the Modbus TCP/IP driver.

The decision for each case:

  • MP2600iec over Modbus TCP: select the Modbus TCP/IP driver.
  • "YASKAWA MP Series - Extension (Ethernet)" selected for that connection: replace it, because it is not the driver for a Modbus TCP path.
  • What EasyBuilder Pro asks for at device setup follows from the driver; for a Mitsubishi Q PLC it requests a tag CSV, as covered in why EasyBuilder asks for a tag CSV for a Mitsubishi Q PLC.

Set the driver before judging the CSV. Tags imported against the wrong driver would carry addresses in the wrong scheme even if their rows landed, and a successful import indication establishes nothing about whether the project's driver matches the intended communication method.

Build the CSV from an exported template #

The address tag library's own export is the format specification, because your build writes the same columns it reads. Derive the template instead of guessing the layout:

  1. Add a few test tags manually in the address tag library.
  2. Export those tags as a .csv file.
  3. Open the export next to the source file in a spreadsheet.
  4. Move each source tag's values into the corresponding template columns and keep the header row as exported.
  5. Import the corrected file through the Address menu.
  6. Open the address library and confirm the entries under user-defined tags.

The same column discipline applies whenever a CSV from another tool meets a live project, a sequence covered in importing a PLC tag CSV into an existing HMI tag database. Modbus TCP/IP is a register-based driver, so its tags enter through this library route and there is no separate tag import button under it.

A worked count that proves the import #

Illustrative numbers, since the export from your build decides the real layout. Suppose the exported template's header row carries 20 comma-separated fields, the source file built elsewhere has 12 columns, and it holds 40 tags. Each row then lacks 20 - 12 = 8 fields in the positions the importer maps, and the first import lands 0 of the 40 tags in the user-defined list, a fail by count. After the values move into the template's columns and the file is imported again, the list shows the 40 new entries; keeping the 3 manually created test tags, the user-defined list totals 3 + 40 = 43 rows.

The decision rule: imported equals intended, 40 = 40, passes; any shortfall fails and sends you back to the column comparison rather than to another export from the controller. Then check one entry's name and address against the form the Modbus TCP/IP driver expects, using your manually typed test tags as the reference.

Assumptions that bring the failure back #

  • A CSV that opens cleanly will import cleanly. False: readable content can sit in columns the library never reads. Check the file against a CSV exported from manually created test tags.
  • The earlier MP2300 import proves this project is equivalent. False: it proved the old file fit the old project, and this connection additionally carried the wrong driver. Check the driver named for the MP2600iec Modbus TCP path.
  • Any Yaskawa Ethernet driver suits a Modbus TCP connection. False for this path: the extension driver is not the choice. Check the device list before diagnosing the file.
  • The import dialog's completion is the result. False: the result is the user-defined tags list. Check the address library after every import.

In every case the sequence is the same: correct the driver, fit the file to the exported template, import, and pass only when the library shows the count you intended.

Questions asked

Will changing only the Modbus TCP/IP driver make the missing tags appear?

Only if the CSV already matches the address tag library format. Treat the driver and the file as two independent faults: switch the driver, import the original file, and count the entries. If they appear, the file was fine and the driver was the sole cause. If the user-defined list stays empty, the columns are wrong, and the exported-template comparison is the next step.

How many test tags does the template export need?

Three is enough in practice. What the export gives you is the header row and column order your build writes, not a row count to imitate. Include the address types you plan to import, such as a read register and a write coil, so every relevant column shows a filled example you can copy field by field.

Why is there no tag import button under the Modbus TCP/IP driver?

EasyBuilder Pro shows an import button below the driver for tag-based PLCs such as a CompactLogix, and the CSV template procedure is not needed there. Modbus TCP/IP is register-based, so its tags arrive through the address tag library and that library's CSV export format instead.

Does updating EasyBuilder Pro fix a silent tag import?

No. The failure was reported on V6.08.02.322 and the causes are project contents: the CSV column layout and the selected driver. A newer build does not remap columns or swap a driver for you. Correct those two items in the project, then verify the count in the address library.

Keep reading

  • Explainer

    Why an exclusive device driver is missing from your EasyBuilder Pro

    A device driver written by an HMI distributor for its own customers ships only inside that distributor's EasyBuilder Pro build. There is no supported procedure to import it into a generic release such as 6.09.01.556, so keep the project on the distributor's software that contains the driver and take upgrade-path questions to the distributor that owns it.

    HMI and touchscreens

  • How-to

    How to Create and Export GX Works3 Labels for a C-More HMI

    Define the name as a global label in the GX Works3 label editor and give it a device target such as Y5; typing the name on a coil only creates an untargeted entry. Export the global label CSV, then hand-map each row into the C-More tag import template, because the two CSV schemas do not match. Separately, confirm the C-More Mitsubishi driver covers the FX5 before trusting any serial retry.

    HMI and touchscreens

  • How-to

    Organizing Omron NX1 Tags for a Symbolic Weintek HMI

    Treat a published Sysmac structure as the DB: declare one STRUCT that holds only the variables the panel reads and writes, set the Network Publish attribute on those variables, transfer, and import the tags online into the configured NX1 device in EasyBuilder Pro. Bind objects to the imported symbols and match their types. Keep a union out of the interface; its members share one storage block sized by the largest member, so its end address must be computed.

    HMI and touchscreens

Fixing a PanelView Plus selector that does not respond