Explainer
Why four data sampling objects don't fill one trend display
Short answer
A trend display draws from one data sampling object's recorded channels; it never merges several sampling objects on its own. Move the four BACnet temperature tags into one Data Sampling object, then select four channels in the trend display's settings. Live tag values prove the network path, not that sampling or the trend binding is correct.

On this page
- Can one trend display use four separate data sampling objects?
- What does a trend display actually bind to?
- How do you put four BACnet temperatures on one trend?
- How many samples will four channels record?
- Why does a live tag value prove nothing about the trend?
- How do you verify the four curves before sign-off?
- Questions asked
A trend display never merges data sampling objects on its own: it draws its curves from the channels of the data sampling object selected in its settings. Four separately created objects, one per BACnet temperature tag, therefore leave the display nothing to combine, because each object stores a history the trend never reads. The fix in an EasyBuilder Pro project is to record all four temperatures in one Data Sampling object and enable their four channels in the trend display. Live tag values on the screen prove only that the BACnet path from the controller works; they say nothing about sampling or about the trend's channel binding. This article gives the documented binding rule, the two possible layouts, a worked sample-count example, and the bench checks that settle the screen before sign-off.
Can one trend display use four separate data sampling objects? #
Not automatically: a trend display draws curves from the channels of a data sampling object, so four separately created objects are never merged by the display, and the reliable fix is to record all four temperatures in one Data Sampling object and select its four channels.
Sampling and rendering are two separate steps. The Data Sampling object records the tags selected for it, at its sampling period; the trend display renders channels of that recorded history. Nothing in the display combines histories it was never pointed at, so the number of sensors behind the tags is irrelevant until the objects themselves are arranged.
Your version's trend settings decide the fallback case. Where the trend display exposes one sampling source, four objects cannot feed it and consolidation is the only layout that works. Where the trend settings let each series pick its own Data Sampling object, the four-object arrangement can work: bind each series to the object that stores its tag and test every curve on the bench. EasyBuilder Pro documents the display drawing multiple channels of sampling data from a Data Sampling object, so the consolidated layout is the one the manual supports directly.
What does a trend display actually bind to? #
It binds to recorded history, not to tags: Weintek's EasyBuilder Pro manual states that trend display objects draw curves of the data recorded by the Data Sampling object, and that the feature can output multiple channel sampling data.
The project has three layers, each with its own failure mode. The tag layer holds the live BACnet value the driver refreshes. The sampling layer copies selected tags into history at the configured sampling period. The display layer renders channels of that history as curves. A fault in any one layer looks like a trend problem from the operator's seat, which is why the binding question and the value question need separate answers.
One Data Sampling object holds several tags as parallel channels, and the trend display's channel selection then decides how many of those channels appear. The manual documents multiple-channel output, so a four-channel selection sits within the documented behavior; the trend display's settings list shows the exact channels available in your build.
How do you put four BACnet temperatures on one trend? #
Create one Data Sampling object containing the four temperature tags, then enable four channels of that object in the trend display: the object supplies the shared history and the channel selection decides which curves render.
Work the change in this order:
- Confirm the four HMI tags show valid live values through the BACnet connection, because no sampling or binding can recover a value that never arrives.
- Open the existing data sampling objects and note which tag each one records.
- Create one Data Sampling object that records all four temperature tags, with one sampling period for the object.
- In the trend display's settings, select that object and enable its four channels, labeling each series with the sensor it represents.
- Download the project and confirm the running screen uses the edited objects.
Field labels and menu paths differ between software versions, so work from what each setting does: the Data Sampling object's tag list, and the trend display's source and channel selection. Keep the fifth sensor out of the plot unless it needs its own curve; nothing forces every recorded channel onto the screen.
| Layout | Trend settings that fit it | Decision |
|---|---|---|
| One Data Sampling object, four temperature tags | One selectable source with multiple channels | Use this layout; the EasyBuilder Pro manual documents it directly. |
| Four Data Sampling objects, one per tag | A per-series source selection | Workable only where the trend settings expose a source per series; bind and test each pair. |
How many samples will four channels record? #
Sample count is the time range divided by the sampling period, multiplied by the channel count: at a 5 s sampling period, a 2 h trend window needs 1,440 samples per channel, so four channels produce 5,760 sample points.
Worked example, with numbers chosen to show the arithmetic rather than any documented limit:
- Time range: 2 h × 3,600 s/h = 7,200 s
- Samples per channel: 7,200 s ÷ 5 s per sample = 1,440 samples
- All four channels: 1,440 × 4 = 5,760 sample points
Double the window and both counts double; halve the sampling period and they double again. What moves the decision is retention, because those 5,760 points must still be stored when the shift reviews the trend. The checks in verifying HMI historical trend retention before committing are written for exactly that step.
Why does a live tag value prove nothing about the trend? #
A live value proves only the driver path: the reading reaches the tag, but sampling stores a separate copy of the tags selected for recording, and the trend renders channels of that stored copy, so a healthy live value can sit beside an empty curve.
Sort the symptom by layer:
- Live value invalid or stale: the fault sits upstream of the trend — the sensor, the controller side of the BACnet server, or the tag's BACnet mapping.
- Live value valid, history missing: the tag is not in an active Data Sampling object, or that object is not sampling.
- History exists, curve missing: the trend display is bound to the wrong object, or the channel is not enabled.
The layer-by-layer method in Is It the Driver, the Tag or the Screen? Diagnosing HMI Values separates a BACnet value fault from a binding fault the same way. Change one layer per download so a corrected tag is never mistaken for a corrected binding.
How do you verify the four curves before sign-off? #
Verify on values you can tell apart: run the four temperatures at clearly different levels, confirm four distinct labeled curves, and check that samples created after the download appear, rather than trusting history left over from earlier project tests.
On the bench, give each channel its own distinguishable condition, even a modest offset between sensors, and watch each curve move against its live tag. Note the time you start watching and confirm the curves extend past it, so old history is not mistaken for fresh sampling. Check each series' label, color, and scale, because four temperature channels share one unit and can look merged when scales differ.
Decision: consolidate the four BACnet temperature tags into one Data Sampling object, select four channels in the trend display, and reserve the four-object layout for the case where your trend settings genuinely expose a source per series, tested curve by curve.
Questions asked
How fast can I sample BACnet temperatures before values repeat?
Sampling cannot record a change faster than the BACnet value updates: if the server refreshes a value every 2 s and the sampling period is 1 s, consecutive samples hold the same reading twice, so 10 s of record contains only five distinct values. Set the sampling period at or above the BACnet update rate when distinct points matter.
Does the fifth sensor have to stay off the trend?
No. Add it to the same Data Sampling object as a fifth channel, since a recorded channel does not have to be plotted. Leave its series disabled in the trend display while the screen shows four curves, and enable a fifth series later if the review needs it; the history is already being recorded.
Can a trend display draw a live tag that is not sampled?
No. The EasyBuilder Pro manual defines the trend display as drawing curves of data recorded by the Data Sampling object, and an unsampled tag has no recorded history to draw. To plot such a tag, add it to the Data Sampling object; the screen can still show its live value elsewhere.
What sampling period suits an 8 h trend with four channels?
For an 8 h window, 8 × 3,600 s/h = 28,800 s; at a 10 s sampling period that is 28,800 ÷ 10 = 2,880 samples per channel, and four channels produce 2,880 × 4 = 11,520 sample points. Confirm the project's logging retention stores that many points per channel, since the count scales linearly with window length and channel count.


