IMDTouchKnowledge BaseShop main store

Troubleshooting

Why fwDH485 Fails to Start in WinCC Flexible 2008

HMI and touchscreens Published 7 min read

Short answer

The messages failed to install fwDH485 and failed to start fwDH485 mean the PC-side DH485 communication component is missing or cannot start; a Device Manager driver update does not prove it. Repair it through the documented WinCC flexible installer, make Use DH485 selectable in the SIMATIC HMI DH485 control panel, and only then test the serial link to the SLC 5/03.

On this page
  1. What the two messages actually mean
  2. Why the SLC 5/03 settings come second
  3. Repairing the fwDH485 component
  4. Isolating the fault on the reader's PC runtime case
  5. Common mistakes that waste the maintenance window
  6. Questions asked

When a WinCC flexible 2008 project reports "failed to install fwDH485" followed by "failed to start fwDH485, please install fwDH485", the fault is on the PC side: the local DH485 communication component did not install or cannot start. This is the first diagnostic priority, ahead of the SLC 5/03 channel configuration and the RS-232 cable. A Device Manager message that a driver "is updated" does not prove that the runtime component is present and startable, and "Use DH485" staying unavailable in the SIMATIC HMI DH485 control panel confirms the component installation is incomplete or unsupported on that PC.

What the two messages actually mean #

The sequence contains two separate failures: an installation request for fwDH485 failed locally, then an attempt to start it failed. The component fwDH485 is the software that gives WinCC flexible Runtime access to the DH485 protocol over the PC's serial interface. If it cannot start, no communication test can tell you anything about the controller, the cable or the protocol settings, because the failure happens at the PC end of the path before a single DH485 frame leaves the port.

The reported symptoms map to diagnostic conclusions as follows:

  • failed to install fwDH485: the runtime's local installation request failed. Inspect the communication-component installation and the Windows error details recorded at that moment.
  • failed to start fwDH485, please install fwDH485: the component never reached a running state. Check installation completeness, operating-system support and startup errors.
  • Device Manager reports the driver is updated: the device Windows manages has a driver package; that is a separate fact from runtime readiness. Identify which device and package were actually updated before treating it as evidence.
  • Use DH485 cannot be selected in SIMATIC HMI DH485: the configuration interface is refusing DH485, which points at the same incomplete or unsupported component installation.

The governing document is the SIMATIC HMI WinCC flexible 2008 Communication Part 2 manual, which has a dedicated chapter on Allen-Bradley communication. Read it for your actual runtime target: instructions written for a dedicated HMI device are not automatically instructions for a Windows PC running Runtime.

Why the SLC 5/03 settings come second #

RS-232 defines the electrical serial interface; DH485 defines the protocol the devices speak on it. Selecting DH485 in the HMI project does not change the electrical properties of a COM port, and an RS-232 cable alone does not create protocol compatibility. The complete path is: the WinCC flexible project connection, the runtime communication component (fwDH485), the PC serial interface, the connection hardware, and the controller's serial channel configuration. Each layer must match the documented arrangement.

A driver-start failure sits at the second layer. An incorrect controller protocol or a wrong cable can stay hidden behind it indefinitely, which is why the repair order matters: fix fwDH485 first, then verify the serial settings and the SLC 5/03 channel, using the DH-485 wiring and configuration steps in connecting an HMI to an SLC 500 over DH-485 serial. If the target is a Windows PC rather than a panel, confirm the runtime setup first, as covered in running a WinCC flexible 2008 project in PC Runtime.

Before changing software, record these facts and compare them with the applicable Siemens installation and communication documentation:

  • Windows edition and architecture, and whether that combination is supported for WinCC flexible 2008 with the DH485 component.
  • The WinCC flexible 2008 installation state on the PC.
  • Which physical serial interface the project uses, and that the Windows device properties and the HMI connection configuration identify the same one.
  • The protocol configured on the connected SLC 5/03 serial channel.
  • The cable or interface arrangement, checked against the documented connection diagram.

Repairing the fwDH485 component #

Do the repair in a controlled maintenance window. Back up the HMI project and write down the existing connection and controller channel settings before changing anything. Obtain installation media, updates and recovery instructions only from Siemens or its authorized distributors.

  1. Capture the failure details. Record both runtime messages and open the Windows diagnostic records for errors at the same timestamp. The goal is a detail entry that names the failing component or the rejected operation.
  2. Confirm the supported combination. Compare the recorded PC configuration with the applicable documentation. Resolve any mismatch between operating system, runtime installation and required communication components before repeating the test.
  3. Release the serial interface. Close Runtime and stop every other application that holds the intended port, including controller programming software and serial test utilities.
  4. Repair through the documented installer. Run the WinCC flexible installation maintenance or repair option with the permissions that installer requires. The expected result is a completion without a driver-installation error. Restart Windows if the procedure asks for it.
  5. Reopen the SIMATIC HMI DH485 control panel. Check the prerequisites described in the manual. The expected result is that Use DH485 becomes selectable for the documented configuration. If it is still unavailable, go back to the installation diagnostics; do not touch the controller settings.
  6. Start the project again. The expected result is that neither fwDH485 message returns. Only then proceed to communication testing with the SLC 5/03.

If the component still fails after a clean repair on a supported system, hand Siemens support the Windows configuration, software installation details, the exact messages and the diagnostic records. Repeating Device Manager driver updates without identifying the failing component does not isolate the cause.

Isolating the fault on the reader's PC runtime case #

This worked example takes the reported case: WinCC flexible 2008 on a Windows PC in Runtime, connecting to an Allen-Bradley SLC 5/03 over RS-232 with DH485, with both fwDH485 messages appearing at project start, a Device Manager claim that the driver is updated, and Use DH485 unavailable in the control panel.

The inputs, each taken from the reported case:

  • Failure messages at project start: 2 ("failed to install fwDH485", then "failed to start fwDH485, please install fwDH485").
  • Device Manager driver status: reports updated, 1 device.
  • Use DH485 in SIMATIC HMI DH485: not selectable.
  • Target: PC Runtime; controller: SLC 5/03; physical layer: RS-232; protocol: DH485.

The rule in words: the PC-side component is proven working only when the project starts with zero fwDH485 messages and Use DH485 is selectable; controller and cable checks are counted only after that.

The arithmetic is a count of outstanding local faults:

  • Local component faults before repair: 2 messages + 1 unavailable option = 3.
  • Local component faults after a successful repair: 0 messages + 0 unavailable options = 0.

The result: while the count is 3, the diagnostic budget goes entirely to the PC-side installation, because each of the 3 items is a local software condition that no controller-side change can affect. After the repair the count drops to 0, and only then does the SLC 5/03 channel protocol and the serial settings become the next thing to verify against the Allen-Bradley chapter of Communication Part 2.

The decision it leads to: with 1 or more local faults outstanding, repair the WinCC flexible installation and do not change controller settings or wiring; with 0 local faults, test communication and troubleshoot the serial path. The Device Manager "updated" status counts for nothing in this tally, because it is not one of the two proofs of component readiness.

Common mistakes that waste the maintenance window #

  • Updating drivers in Device Manager repeatedly. The runtime component is installed by the WinCC flexible installer, not proven by a Windows driver status.
  • Editing the SLC 5/03 channel configuration to chase an fwDH485 message. The failure occurs before any frame reaches the controller.
  • Leaving controller programming software open on the same COM port during the repair, so the component cannot claim the interface.
  • Applying instructions written for a dedicated HMI panel to a PC Runtime installation, or the reverse. The runtime target decides which documented procedure applies.

Once the local faults are cleared, the remaining work is ordinary serial commissioning: match the controller channel protocol and serial settings to the project connection, reproduce the documented interface arrangement, and confirm live data in Runtime before handing the station back to production.

Questions asked

Can I select DH485 in the project if Use DH485 is greyed out in the control panel?

No. The project connection depends on the same local DH485 component that the SIMATIC HMI DH485 control panel configures. If Use DH485 cannot be selected there, the component installation is incomplete or unsupported on that PC, and the runtime will report the fwDH485 failures again no matter how the project connection is set.

Should I reinstall Windows to clear the fwDH485 error?

Not as a first step. Run the WinCC flexible installer's repair or modify option first, restart when it asks, and confirm that Use DH485 becomes selectable. Reinstalling the operating system is only worth considering when the installer cannot complete on the existing system and Siemens support confirms the installation is beyond repair.

Does a Device Manager driver update mean fwDH485 is installed?

No. Device Manager reports only the device and driver package it manages. The fwDH485 component is a runtime communication component started by WinCC flexible, and its readiness is proven only when the project starts without the fwDH485 messages and Use DH485 is selectable in the SIMATIC HMI DH485 control panel.

Which manual covers the Allen-Bradley DH485 connection for WinCC flexible 2008?

The WinCC flexible 2008 Communication Part 2 manual, which has a dedicated chapter for Allen-Bradley controllers. Use it to confirm the supported connection hardware, the interface arrangement and the controller-side settings for your runtime target, whether a panel or PC Runtime.

Keep reading

  • Troubleshooting

    Why One FX3U Port Cannot Serve GX Works2 and WinCC Flexible

    No, one FX3U serial port carries one master conversation, so GX Works2 and an HMI cannot share it. Keep GX Works2 on the CPU programming port and give WinCC flexible a second serial port through an expansion board, or move the HMI to Ethernet. When both run on one PC, Windows hands the single COM port of the USB-RS232 cable to one application.

    HMI and touchscreens

  • Troubleshooting

    PanelView 600 Serial Connect Fails: DTE Versus DCE Cabling

    A PanelView 600 serial port is DCE equipment and a PC serial port is DTE, so the connection needs a straight-through cable, pin 1 to 1, pin 2 to 2, pin 3 to 3, not the null-modem crossover that connects a PC to a controller. Meter the finished lead end to end first; only then let RSLinx auto-configure and sort out DF1 versus DH-485.

    HMI and touchscreens

  • Troubleshooting

    Why an OP77B project transfer fails over PROFIBUS at 1.5 Mbps

    A failed OP77B download over PROFIBUS is a settings mismatch, not a dead panel: the PC adapter must run at the segment's baud rate, the DIP-set PROFIBUS address must match both the panel's Transfer settings and the STEP 7 slave entry, and the panel must sit in transfer mode with automatic transfer off for the first download. Clear the only-master setting when the S7-315 shares the segment.

    HMI and touchscreens