IMDTouchKnowledge BaseShop main store

Troubleshooting

Why graph overview step display works but mode commands fail

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

A GRAPH overview that tracks steps but ignores mode and step commands has a working status path and a dead command path. Point the display at the instance that actually executes, confirm the executing GRAPH block is version 4.0 or later, and issue every operator action through the documented interface parameters — INIT_SQ to initialize, OFF_SQ to switch off, ACK_EF to acknowledge — with the calling logic owning the reset side.

On this page
  1. Two paths, one sequencer
  2. The checks in order
  3. Point the display at the executing instance
  4. Read the version that runs, not the version on disk
  5. Put every command on the documented interface
  6. Worked example: a request that latches itself
  7. Separate delivery from acceptance
  8. The decision for each case
  9. Questions asked

A GRAPH overview that follows every step correctly while mode and step commands do nothing has one proven path and one broken one, and the two are commissioned separately. The display path reads step status through tags on the sequencer's instance data block. The command path writes into the executing GRAPH block through its documented interface parameters, and it fails independently: a healthy display proves nothing about it. Fix it in that order — prove the overview watches the instance that actually executes, read the version of the block that runs, then move every operator action onto the documented command interface instead of a raw bit write into the instance data block. Run these checks with the machine in a controlled commissioning state, because a mode change is a real process command.

Two paths, one sequencer #

The GRAPH Overview object is documented in the WinCC Advanced scope for Panels, Comfort Panels and RT Advanced, and its documented job is to display the current program status of the executed steps of a GRAPH sequencer. Status is the whole contract. When the step number and step name track the sequence, the HMI connection, the tag bindings and the sequencer's status reporting are alive; none of that exercises the command side, which needs a correctly formed write to specific interface parameters of the same block, on the same instance.

That splits the failure into three command-side places: the version of the executing block, the association and shape of the command write, and the acceptance conditions in the PLC.

Symptom What it already proves Open first
Step number and name update correctly Connection, tag binding and status reporting work The command side only
Overview always shows automatic mode The mode request is not delivered, or is delivered and refused Command association, then acceptance conditions
Commands work once, then never again Delivery works and one request was taken The request field latching at TRUE without a reset

The checks in order #

  1. Watch the sequence online in the engineering tool and note the active step number and step name. The overview must show the same active step at the same moment; agreement here proves the display is bound to the instance that executes.
  2. Name that instance. When the sequence block is called as a local instance inside a parent block, its operating data lives inside the parent's instance data block, and every HMI tag has to resolve through that parent, not through a similarly named standalone DB. If the GRAPH instance DB tags do not appear in the HMI tag selection at all, that specific problem is covered in why GRAPH instance DB tags are hidden from WinCC in TIA Portal.
  3. Read the version of the block loaded in the CPU, not the version in the offline project: the command side needs an executing block at GRAPH version 4.0 or later. Establish what actually runs the way you would verify the HMI project version running on a panel — from online information, never from the disk copy.
  4. Check the runtime edition against the object's documented scope. Advanced covers the GRAPH Overview object for the documented panel and RT Advanced targets, so an edition change is not the fix for dead commands inside that scope.
  5. Assign every operator action a documented parameter before touching the screen; the mapping is in the section below.
  6. Check the operating user's runtime rights for those writes.
  7. Prove the whole chain with one controlled test: press a mode command online, watch the request field, watch the mode, watch the step.

Point the display at the executing instance #

A correct step display is one proven binding, not a proven screen. The fields that carry the step number and the step name are status fields: writing to them changes nothing, and reading them correctly says nothing about the write path behind mode and step commands. Compare online, in the tag or connection diagnostics of the runtime, where the overview's status association resolves and where its command association resolves; both must land in the same executing instance DB, in the fields the block interface defines for that purpose. The always-automatic display usually ends here: the mode indication is bound to a constant, to a copied tag, or to a field that only ever reports the default.

Read the version that runs, not the version on disk #

The threshold for this symptom is GRAPH version 4.0. An executing block below it does not provide what the overview's command side talks to, and no amount of HMI wiring repairs that. A project tree showing a current version proves nothing, because the CPU runs whatever was downloaded last; read the version from the online block information. Below the threshold, regenerate the sequence with a current GRAPH version and download it before touching anything else. At or above the threshold, the version is not the fault and the write path is.

Put every command on the documented interface #

The sequencer-control functions you can exercise in test mode in the engineering tool map onto the block's interface parameters: INIT_SQ initializes the sequencer, OFF_SQ switches it off, ACK_EF acknowledges a fault. That mapping is the documented command path, so the HMI has to drive the same parameters the tool drives in test mode, whether the write is triggered from a command element on the overview or from an ordinary button.

Three rules make it hold. First, the calling logic owns the command inputs: an HMI write into the instance DB competes with whatever the parent block writes on every call, and the parent wins. Second, each command parameter has a documented acknowledge counterpart in the same interface; the request must return to 0, and the calling logic is where that reset belongs. Third, one button writes one documented parameter through one tag; a button that writes a status field or an arbitrary bit is not a command, and the block either ignores it or misreads it.

Worked example: a request that latches itself #

Example values, not measured ones: a CPU cycle time of 10 ms, and a button that writes a maintained TRUE into OFF_SQ in the instance data block, with no acknowledge logic wired anywhere.

First press: the field goes 0 to 1. The block takes one request at that transition and switches the sequencer off. Nothing in the project returns the field to 0, so it stays TRUE.

Second press: the field is already TRUE, so the press is 1 to 1 — no new transition, no new request. At that cycle time a 500 ms hold spans 500 ms ÷ 10 ms = 50 scans, and exactly one of them, the first, carries the transition; the other 49 change nothing. Holding the button longer or pressing repeatedly cannot help.

The buttons are not dead and the connection is not broken: the request latches at TRUE because its reset side does not exist. Give the request a return path — wire the acknowledge counterpart in the calling logic, or pulse the field from the HMI and clear it when the acknowledge feedback appears — then press twice and confirm the second press is taken too.

Separate delivery from acceptance #

A command is delivered when the write reaches the executing instance, and accepted when the sequencer's state and permissives allow it; the always-automatic symptom hides in the gap between the two. Watch the command field online while the real operating user presses the button.

  • The field does not change: delivery is the fault — runtime rights, or the tag resolving to the wrong instance.
  • The field changes and the mode does not: the sequencer refused or deferred the request under its current state. That is sequence logic deciding, not the HMI failing; solve it in the sequence's permissives, never by forcing internal bits.

Rights are proven with the machine's operating user, not the engineering login, and rights that behave in simulation but not at runtime are their own troubleshooting path — see when HMI user management works in simulation but not on the panel.

The decision for each case #

  • Executing block below the version threshold: regenerate with a current GRAPH version, download, and re-test. Nothing on the HMI side fixes this case.
  • Version fine but commands written as raw instance-DB bits: re-map each action onto INIT_SQ, OFF_SQ and ACK_EF, or onto the matching mode and step command fields of the same interface, with resets owned by the calling logic. Delete the direct bit writes; they are the fault, not a workaround to tune.
  • Commands on the interface and still refused: check rights first, then watch the request field online. If it toggles and the mode does not follow, the sequencer is refusing under its permissives, and the fix is sequence logic, not the screen.
  • Advanced or Professional: Advanced covers the documented panel and RT Advanced scope for this object, so keep the edition and fix the path.

Questions asked

How long should a sequence command stay TRUE?

Hold a command at TRUE long enough to be read at least once — at a 10 ms cycle time that is anything above 10 ms — and return it to 0 as soon as the acknowledge feedback appears. What matters is the 1 to 0 return before the next request; the duration itself carries no weight. A maintained write with no reset path is exactly the latched-bit failure.

Which parameter brings the sequencer back to its first step?

INIT_SQ initializes the sequencer to its initial step and is the documented counterpart of the engineering tool's test-mode initialize function. Like every command parameter it must return to 0, with the reset owned by the calling logic or the acknowledge handling. After an OFF_SQ request has switched the sequencer off, INIT_SQ is the parameter that restarts it from the first step.

Can two operator stations command the same sequencer?

Yes, when both write the same documented interface parameters of the same executing instance through their own connections. Decide the split by the job each station does — mode changes and acknowledgment at one, display only at the other, for example. Watch for two stations writing the same command field, because the last write wins and the reset behavior becomes ambiguous.

Where do runtime rights for sequence commands get configured?

In the runtime user management of the HMI project, on the user who actually operates the machine. Give that user the operating and write rights for the sequence control area, then press a command while watching the command field in the PLC: a field that stays still under the operating user but moves under an engineering-level user points at missing rights.

Keep reading

  • Troubleshooting

    When HMI user management works in simulation but not on the panel

    The simulator reads user management from the project; the panel keeps its own local user data store that keep-current-values downloads never refresh. Download to the panel once with Reset to start values for runtime values, confirm the role's runtime rights for that HMI, then test one login and one permitted function.

    HMI and touchscreens

  • Explainer

    How WinCC and STEP 7 Work Together in a PLC Project

    STEP 7 configures and programs the Siemens PLC; WinCC builds the operator screens that read and write selected PLC variables over a configured connection. The boundary between the tools is the tag: STEP 7 owns the variable, WinCC owns the display and command objects bound to it.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Start and Stop buttons do not control an S7-300 output

    The Start and Stop buttons do nothing because E0.0 and E0.1 are S7-300 input image addresses: the CPU refreshes them from the input modules every scan, so an HMI write cannot survive. Step 7 simulation changes the simulated input state itself, which is why the LED follows it. Move the two commands to memory bits such as M0.0 and M0.1, latch them in the PLC, and let the program drive A4.0.

    HMI and touchscreens

Why Perspective Workstation Ignores Touch but the Browser Works