Why HmiDigitalClock Is Missing on a Unified Basic Panel

HMI and touchscreens Published 5 min read

Short answer

The Style list on a Clock object only offers HmiClock because the MTP1000's configured module version is V18.0.0.3, and the digital style was introduced with Unified runtime V19.0.0.0. Update the module version in Devices & Networks, or build the clock as an output-only I/O field driven by JavaScript until you can update.

On this page
  1. Why does my V19 project only offer the analog clock style?
  2. How do I update the module version to V19.0.0.0?
  3. How do I verify the digital clock after the update?
  4. Can I display digital time and date without updating the firmware?
  5. Why does a tapped time field pop up a date and time dialog that does nothing?
  6. Which fix should I choose?
  7. Questions asked

The digital clock style is missing because your MTP1000 Unified Basic project carries module version V18.0.0.3, and the HmiDigitalClock style was introduced with Unified runtime V19.0.0.0. TIA Portal V19 does not unlock new elements by itself: it starts the panel at the last compatible module version, and the element catalog is filtered by what that version declares. The fix is Update module version in Devices & Networks to V19.0.0.0, on both the project and the panel image; until then, an output-only I/O field driven by a JavaScript scheduled task gives you the same display.

Why does my V19 project only offer the analog clock style? #

Only HmiClock appears under Properties → Appearance → Style because the Style list is generated from the module version the project declares for the device, not from the TIA Portal release you installed. When you add an MTP1000 that shipped with an older runtime, TIA Portal V19 loads the V18.0.0.3 module descriptor, and that descriptor exports only the analog clock. The V19.0.0.0 descriptor is what adds HmiDigitalClock and the dedicated date display element.

This is a catalog filter, not a fault. Nothing is broken in your installation; the engineering environment is simply showing you the V18 element set. The same logic decides every element on a Unified panel, which is also why image and project version checks matter before downloads — the same discipline applies when you verify the HMI project version running on a panel (article:how-to-verify-the-hmi-project-version-running-on-a-panel).

How do I update the module version to V19.0.0.0? #

The update is a five-step job in the project tree:

  1. Archive the project first, so you can return to the working V18 configuration if the download fails.
  2. Open Project tree → Devices & Networks and double-click the MTP1000 to open the Device View.
  3. Right-click the panel in Device View and choose Update module version, then update to the new version.
  4. Select version 19.0.0.0 in the dialog and confirm. If V19.0.0.0 is not offered, the support package supplying that descriptor is not installed — install the current Unified Basic support package via the Options menu, restart TIA Portal, and repeat. Update media and SIOS entries for WinCC Unified V19 are listed on the Siemens support portal.
  5. Rebuild the HMI, download to the panel, and let it reboot into the V19 runtime.

Two things must match: the module version in the project and the OS image on the panel are separate settings, and updating only one leaves you where you started. The panel side is done with the matching V19 image for Unified Basic panels, loaded the way you would for any Update OS operation on the device.

How do I verify the digital clock after the update? #

Check the catalog before you wire anything:

  • Device View reports module version 19.0.0.0 for the MTP1000.
  • A Clock object's Style list under Properties → Appearance now offers both HmiClock and HmiDigitalClock.
  • The date display element is present in the Toolbox → Elements catalog.
  • In runtime, the clock updates each second on the panel's system time, and the date follows the configured locale, time zone and DST rule.
  • Alarm and log timestamps use the same time base as the displayed clock.

If timestamps disagree with the display, the panel clock drifted rather than the element failing — that is a time-source problem, and the checks in the SNTP clock sync article for Windows CE panels transfer directly (article:troubleshooting-sntp-clock-sync-on-a-windows-ce-panel).

Can I display digital time and date without updating the firmware? #

Yes, as a workaround: an output-only I/O field bound to a string tag, written each cycle by a JavaScript scheduled task that reads the panel's system time. This works on V18.0.0.3 and needs no firmware change. Treat it as temporary — the module version update is the supported fix — but it is stable enough to commission while you plan the upgrade window.

Configuration:

  • Drag an I/O field onto the screen and set its mode to output field only. An input-capable field invites operators to submit values the script will immediately overwrite.
  • Bind the process value to a string tag, for example a WString tag named Tag_TimeString (an illustrative name — any project tag of string type works).
  • Set the display format pattern, for example HH:mm:ss, under the field's appearance properties.

The script, attached to a scheduled task (or a fast cyclic event), declares its own variables and writes the panel time into the tag:

// Illustrative script using documented Unified scripting calls
var d = new Date();
var hh = ('0' + d.getHours()).slice(-2);
var mm = ('0' + d.getMinutes()).slice(-2);
var ss = ('0' + d.getSeconds()).slice(-2);
Tags('Tag_TimeString').Write(hh + ':' + mm + ':' + ss);
var dt = d.getFullYear() + '-' + ('0' + (d.getMonth() + 1)).slice(-2) + '-' + ('0' + d.getDate()).slice(-2);
Tags('Tag_DateString').Write(dt);

Where the script runs decides whether it works at all: scheduled tasks and screen scripts have different execution contexts in Unified, and the differences are covered in more depth in a separate article on WinCC Unified JavaScript errors in scheduled tasks versus screens (guide:wincc-unified-javascript-errors-in-scheduled-tasks-vs-screens).

Why does a tapped time field pop up a date and time dialog that does nothing? #

Because the field is a display, not a setting. Touching an I/O field on a Unified Basic panel in operate mode opens the date/time adjustment popup; if an operator submits a change, it applies for one cycle and the next JavaScript write restores the panel system time. That is expected behavior — the script is the single source of truth for the display.

Manual time setting does not belong in the faceplate at all. It belongs in the panel's own date and time settings in the control panel, where the change persists. Keep the I/O field output-only so the popup invitation at least writes nothing into your process tags.

Which fix should I choose? #

Update the module version to V19.0.0.0 when you can schedule a download — it gives you the supported HmiDigitalClock style, the dedicated date element and locale-correct formatting with no script to maintain. Use the JavaScript I/O field when the panel cannot be taken offline now; commission it as described, and plan the module version update as the permanent replacement. If your real problem turns out to be the panel hardware itself rather than the version, an industrial touchscreen monitor keeps the existing computer and swaps only the failing display unit (https://industrialmonitordirect.com/collections/all-monitor/).

Questions asked

Why does my TIA Portal V19 project still show only HmiClock on the Clock style list?

Because the Style list is filtered by the module version the project declares for the panel, not by the version of TIA Portal you installed. A Unified Basic panel added in V19 keeps the last compatible module version, V18.0.0.3, whose descriptor only exports HmiClock. HmiDigitalClock appears once the module version is updated to V19.0.0.0.

Do I need to update the panel's OS image as well as the TIA Portal module version?

Yes, both sides must match. The module version in the project and the runtime image on the panel are two separate settings. If you update the OS image on the panel but leave the module version at V18.0.0.3, the editor still hides the digital style; if you update the project without the matching panel image, the download will not run as intended.

Can operators set the time and date through the JavaScript I/O field clock?

No. The JavaScript task overwrites the field every cycle, so any value an operator submits through the popup reverts within one cycle. Manual time setting belongs in the panel's own date and time settings in the control panel, not in the display field. Keep the I/O field in output-only mode.

What if V19.0.0.0 is not offered in the Update module version dialog?

Then the support package that supplies the V19.0.0.0 module descriptor for Unified Basic panels is not installed in your TIA Portal. Install the current support package through the Options menu, restart TIA Portal, and repeat the update. The V19 update media and SIOS entries on the Siemens support portal list what is available for your installation.

Does the JavaScript workaround survive a restart or screen change?

Yes, as long as the scheduled task is configured at project level rather than tied to one screen, it restarts with the runtime and keeps writing the time string. The panel's system time survives a restart if it was set correctly; an SNTP or PLC-based time source keeps it accurate across reboots.

Keep reading

  • How-to

    Matching an HMI panel image to its TIA Portal project version

    The panel image must belong to the same TIA Portal release the HMI project was engineered in, so a V21 Update 2 project needs a V21 Update 2 image. The listing carries the V18 to V21 families, recommends V21 Update 2 for update, and from 4 September 2026 adds Service Releases with bug fixes only. Read the installed image from the panel, compare it with the project release, and move whichever side is behind.

    HMI and touchscreens

  • How-to

    Enable object access on a KTP700 Basic Panel with Visibility

    On a KTP700 Basic Panel you cannot use VBScript or the Control enable animation, so you gate operator access with an Animations > Display > Visibility animation instead. The on-screen keyboard layout is fixed on smaller panels and only resizes on larger Comfort Panels.

    HMI and touchscreens

  • Selection guide

    Do You Need SCADA Software for a Modbus HMI Project

    No. Modbus only proves a possible data link, so pick the runtime target first: a touch panel programmed by its own editor for machine-side parameter control, or a licensed PC SCADA runtime when the screens must run on a computer. The documented demonstration mode of a Vijeo Citect-class runtime stops after about 15 minutes with live devices, which settles a bench test but not continuous operation.

    HMI and touchscreens