Explainer
Why iR I/O Modules Do Not Attach Directly to a cMT HMI
Short answer
No iR-series I/O module attaches directly to a cMT-SVRX-820/822 or a cMT-FHDX-820. The HMI reads the I/O over Ethernet through an iR-ETN, iR-ETN40R or iR-ECAT coupler, so a single digital input still takes two boxes: the coupler plus an iR-DI16-K. A 24 VDC sensor sits comfortably inside the module's 15 to 28 VDC on-window.

On this page
No iR-series I/O module attaches directly to a cMT-SVRX-820/822 or a cMT-FHDX-820. Both are faceless units with Ethernet and serial communication ports but no I/O expansion slot, so there is nothing on the HMI for an iR module to plug into. What works is an Ethernet coupler: the HMI connects to an iR-ETN, iR-ETN40R or iR-ECAT, and the I/O modules sit behind that coupler. For the single digital input you have in mind, that means two boxes on the rail — the coupler and an iR-DI16-K — working hand in hand. Below is why the split exists, what the input accepts electrically, and how to bring the link up and prove it.
Why there is no direct attachment #
Direct attachment would need an expansion backplane on the HMI, and these models do not have one. The cMT-SVRX series installation guide documents the unit's communication connections — among them the COM2 and COM3 serial ports — and none of those connections is an I/O bus. The iR family is built the other way round: its modules are remote I/O that work through a remote communication module, the piece that holds the network interface and supports multiple communication protocols, with connection options for digital and analog I/O. The HMI therefore never sees an iR-DI16-K as a wired input. It sees the coupler as a device on the network and reads the module's channels as addresses through it.
The three couplers that connect #
The cMT-SVRX-820/822 and cMT-FHDX-820 reach iR I/O through one of three Ethernet couplers: iR-ETN, iR-ETN40R or iR-ECAT. All three are documented options for these HMI models. Choose by the protocol your network already runs; when nothing else decides it, take the iR-ETN — it is the coupler the vendor uses to demonstrate exactly this cMT-to-iR link, which makes it the right default for one digital input. The coupler's own documentation supplies the protocol settings and the address table for the modules behind it, and the I/O module adds no network settings of its own.
One digital input is still two boxes #
Yes, the two modules go hand in hand. The iR-ETN provides the communication; the iR-DI16-K provides the channels, 16 digital inputs per module. Neither works alone: the coupler has no input terminal to wire a signal to, and the module has no network face for the HMI to poll. One procurement note: the vendor's product page prints the module as iR-DI16-K while some other material writes iR-DI16K, so order by the designation the product page uses.
The iR-DI16-K input in numbers #
| Input parameter | Published value |
|---|---|
| High-level input voltage | 15 to 28 VDC |
| Low-level input voltage | 0 to 5 VDC |
| Response time, OFF to ON | 5 ms |
| Response time, ON to OFF | 1 ms |
| Input impedance | 5.6 kΩ |
The published windows match the thresholds IEC 61131-2 sets for 24 VDC discrete inputs; the band between the two windows is undefined, so a signal that parks there can read either way. Because the input senses voltage, a dry contact on its own reads nothing: wire it in series with a supply inside the on-window so the closed contact delivers a valid high. Matching a driver to an input's guaranteed window is the same check you make when a PLC output can drive a VFD digital input directly.
One limit to respect: this is a standard remote input, not a safety-rated device. E-stops, guard doors and light curtains stay on their safety circuits — the HMI may display their state but never substitutes for them.
Checking a 24 VDC sensor against the iR-DI16-K input window #
The case: one sensor switching a 24 VDC control supply is the only signal, and the question is whether it wires straight into the module.
Inputs, with sources:
- Sensor output: 24 VDC when active, 0 VDC when idle — the machine's existing control supply, taken as the example signal.
- Input impedance: 5.6 kΩ — the module's published data.
- On-window of 15 to 28 VDC, off-window of 0 to 5 VDC — same source.
- Response times: 5 ms off-to-on, 1 ms on-to-off — same source.
The rule: a channel is guaranteed on when its terminal sits in the on-window and guaranteed off when it sits in the off-window, and the current it draws follows Ohm's law — current equals voltage divided by resistance.
The arithmetic:
- On-state margin: 24 V − 15 V = 9 V above the threshold, with 28 V − 24 V = 4 V of headroom below the ceiling.
- Off-state: 0 V ≤ 5 V, a valid low.
- Channel current when on: 24 V ÷ 5 600 Ω = 0.0043 A, about 4.3 mA.
The result: the sensor lands inside the on-window with 9 V of margin and draws about 4.3 mA, both comfortably within the published limits.
The decision: wire it straight in — any sensor or wetted contact whose off-state stays below the off limit and whose on-state lands in the on-window needs no conditioning. Fit an interposing relay only when the source can idle in the undefined band between the windows, and keep pulses shorter than the off-to-on response off this input: they are not guaranteed to register, so fast events belong in hardware built to count them.
Bringing the link up and proving it #
- Wire the input: sensor or wetted contact to the chosen channel of the iR-DI16-K, seated behind the iR-ETN.
- Address the network: static addresses for the coupler and the HMI on one private subnet.
- In EasyBuilder Pro, add the coupler as a device with its address and map the input channel to the address its manual assigns; the vendor's tutorial for the iR-ETN walks through this cMT link.
- Prove it on the bench: toggle the field signal and watch the mapped address follow in both directions.
- Pull the coupler's Ethernet cable with the input high and record what the address does — the published module data does not define link-loss behavior, so your bench note is the spec you design against.
Before ordering the coupler, check the machine's PLC. If it has a free input, wire the sensor there and let the HMI read it over the connection that already exists — the Modbus route described in writing WAGO 750 PLC digital outputs from a Weintek HMI — and the single input costs no extra hardware.
Questions asked
Can the cMT-SVRX serial ports read iR modules instead of using Ethernet?
No. The COM2 and COM3 ports documented in the cMT-SVRX installation guide serve serial controllers, and every iR coupler listed for these HMIs — iR-ETN, iR-ETN40R and iR-ECAT — is an Ethernet device. There is no serial path into the iR family, so reserve one Ethernet port for the coupler and keep the serial ports for PLCs that actually speak serial.
What IP addresses should the coupler and the HMI use?
Any private subnet works; for example, give the coupler 192.168.2.10 and the HMI 192.168.2.20 with subnet mask 255.255.255.0. The vendor's network note for the cMT-SVR describes two Ethernet ports, each set by DHCP or a static IP. Choose static addresses for an I/O link so a DHCP server outage cannot strand it, and keep the coupler off any subnet shared with office traffic.
What does the HMI show if the coupler drops off the network?
The published iR data does not define a link-loss state, so treat the behavior as unproven until your bench pull test records it: the mapped address may hold its last value, drop to zero, or raise a communication status you can use. Design the screen so a frozen value cannot pass for a live one — for example, animate the indicator only while the coupler's communication status reads healthy.
Can the unused channels on the iR-DI16-K take more signals later?
Yes. The module carries 16 input channels behind the single coupler, so after the first one there are 15 positions ready for future dry contacts or sensors on the same voltage window, with no extra hardware. Add another module only when the channels run out or the job needs analog I/O, which the same coupler family also serves.