Troubleshooting
Why Korean Text Fails to Display on a Comfort Panel
Short answer
Add Korean as a project language and enable it in the panel's runtime settings first. Then place one fixed Korean text in a system control such as a trend or alarm view: if that text still shows boxes, the fault is the font on the panel, not the language settings and not Windows CE.
On this page
A Comfort panel that shows Korean as boxes or blank text usually has the language switched on twice and the font missing once. Enable Korean as a project language and as a runtime language on the panel, then place one fixed Korean text in a system control such as a trend view or alarm view. If that fixed text renders correctly, the language settings are right and the fault sits in the dynamic texts. If it still fails, the panel lacks a font with Korean glyphs, and the fix is font deployment, not a Windows Embedded CE language package. Work the checks in that order and the panel itself tells you which half of the chain is broken.
Confirm the two language settings first #
Language selection and glyph rendering are separate layers, and both must be on before any font work makes sense. Check, in this order:
- Korean exists as a project language in the TIA Portal project, not only as a language you typed into a text field.
- Korean is enabled among the runtime languages on the panel, in the "Language & Font" editor where the runtime language order is set. A language that exists in the project but is not enabled for runtime never appears on the panel, no matter what font it uses.
- The runtime language order puts Korean where the operator's language-switch function can actually reach it.
- The font assigned to the Korean texts carries Korean glyphs. A Latin-only font renders every hangul syllable as a replacement box, which looks exactly like a deeper fault.
Enabling Korean is supported on Comfort panels; Siemens' FAQ on available WinCC (TIA Portal) languages lists German, English, Italian, French, Spanish and Chinese for the configuration interface, and that list governs the engineering interface, not the texts your runtime can render. Note the vendor's limit on the number of languages installed on a panel before you stack several. If you want the click-by-click path, the walkthrough for adding Korean language to a TP1200 Comfort HMI in TIA Portal covers the same editors on a sibling Comfort model. Transfer the project, and for the transfer stick itself check the USB stick requirements for a TP1500 Comfort panel, then switch the runtime language to Korean.
Testing fixed Korean text on a TP1500 Comfort project #
Inputs for this test, each from the reported case or the TIA documentation:
- Panel: TP1500 Comfort, the model in the reported case.
- Runtime languages already enabled: three, set in the "Language & Font" editor in the order English, Italian, French — the order the documentation uses for its example.
- New requirement: Korean text on some screens.
- Probe: one fixed, unchanging Korean text placed inside a system control, an alarm view or a trend view.
Rule in words: a runtime text renders correctly only when two things are true at once — its language is enabled in the panel's runtime settings, and the font the text uses carries the glyphs. A fixed text inside a system control removes tags, scripts and the dynamic text source from the test, so a failure there can only be one of those two layers.
Arithmetic: runtime languages to enable = 3 existing + 1 Korean = 4. Probe texts = 1. Possible outcomes = 2. Enable the 4 runtime languages in order, transfer the project, switch the runtime language to Korean, and read the 1 fixed label.
Result and decision: if the label reads correctly, language selection and rendering both work — chase the dynamic texts, their text sources and any strings arriving from the controller. If the label is missing or shows boxes, stop editing language settings entirely; the single fixed label has isolated the fault to the font, and that is where the next hour goes.
Fix the font when fixed text still fails #
Boxes or missing characters mean the panel has no font with Korean glyphs for the text it is drawing. Three points decide the fix:
- Siemens documents loading Asian fonts to the HMI device for Comfort panels, and the same entry warns that text sent directly from the controller — controller alarms and ProDiag — can still display incorrectly even after the fonts are on the panel. Treat project texts and controller texts as two separate tests.
- Copying a Korean font such as Gulim to the panel's font folder is a workaround that circulates for this exact symptom. Run it as a bench test first, and confirm with the vendor that the font is licensed for that deployment and that manual font placement is supported before it reaches a production line.
- The documented font registration procedure for Comfort panels that uses ProSave is written for Chinese characters. Do not assume it covers Korean; ask the vendor whether a Korean equivalent exists.
If the boxes appeared only after a firmware update, the rendering changed under you rather than the project; the notes on resolving TP900 Comfort font rendering issues after firmware V17 walk through that case. Bench-test font and language changes on a spare panel or in planned downtime: a font swap can change text widths and move objects on a live screen.
Leave the panel operating system alone #
Windows Embedded CE 6.0 documents multiple input language support, which is why the question of a CE Korean language package comes up. Installing an OS-level language package on a Comfort panel is not a documented fix for this fault, and the documented chain — project language, runtime language, font — resolves the display without touching the panel image. Raise the OS-package question with the vendor before installing anything at that level; a wrong package on a panel is a recovery job, not a font fix.
Escalate with evidence the vendor can act on #
If the fixed Korean label still fails after both language settings are confirmed and a Korean-capable font is deployed, send the vendor a support request with: the panel model and firmware version, the TIA Portal version, the project and runtime languages with their enabled order, the font name assigned to the Korean texts, photographs of the fixed-text probe result, and whether controller alarms render differently from project texts. That set answers every question a support engineer would otherwise ask one message at a time.
Questions asked
Does Windows CE on a Comfort panel support Korean?
Comfort panels run Windows Embedded CE 6.0, which documents multiple input language support, but changing the panel operating system is not the documented fix for this fault. Korean text renders once the runtime language is enabled and the assigned font carries Korean glyphs. Confirm any OS-level change with the panel vendor before touching the panel image.
Why do controller alarms still show squares after Korean screens work?
Text sent directly from the controller, such as controller alarms and ProDiag messages, is rendered separately from project texts and can still display incorrectly even after Asian fonts are on the panel. Test it with a forced alarm once fonts are deployed, and check which font the controller-side alarm configuration names.
Can the Chinese font registration procedure be used for Korean fonts?
The documented font registration procedure that circulates for Comfort panels is written for Chinese characters. Do not assume it extends to Korean. Ask the panel vendor whether an equivalent Korean procedure exists, and meanwhile make sure the project font itself contains Korean glyphs and reaches the panel with the project transfer.