Why one HMI needs two serial ports for two PLCs
Short answer
A single Weintek HMI serves an FX1S and an FX2N in one project only when three documented facts line up: the panel has two independently usable communication channels, its driver list includes a Mitsubishi FX driver for each connection, and the documented port allocation allows both to run at once. Count channels, not connector shells, bind every screen object to a named device, and never branch one point-to-point cable to reach both controllers.
On this page
- Can one Weintek HMI talk to two Mitsubishi FX PLCs at the same time?
- How many usable serial channels does the panel really have?
- Which driver does each FX PLC need in the project?
- Can I branch one cable to reach both PLCs?
- Does showing both PLCs on one panel link the two programs?
- Example: what does one screen of four points per PLC cost at 9600 baud?
- What breaks first when the second PLC is added?
- How do you prove both connections before the machine runs?
- Questions asked
Yes — one panel can serve an FX1S and an FX2N in the same project, and it works only when three documented facts line up: the model has two independently usable communication channels, its driver list includes a Mitsubishi FX driver for each connection, and the documented port allocation lets both run at the same time. Connector count proves none of that. COM1 and COM2 are labels, a point-to-point cable does not turn into a shared bus when you branch it, and showing two PLCs on one screen does not make them exchange data. This article gives the feasibility test and the polling budget behind it; the wiring-level steps for the arrangement that passes are in Connecting One HMI Panel to Two PLCs Over Serial.
Can one Weintek HMI talk to two Mitsubishi FX PLCs at the same time? #
Yes, when the panel model documents two simultaneously usable communication channels and a Mitsubishi FX driver for each connection; feasibility is decided by the driver list and the documented port allocation, never by how many connector shells the panel has.
The HMI is the communication client of every device it serves: each PLC becomes one device entry in the project, and the panel holds both entries at the same time only where the vendor documents that. Two checks settle it before any cable is cut. First, the vendor's PLC connection guide for the panel series lists the supported drivers — confirm a Mitsubishi FX driver exists for the series your panel runs, not just for the brand. Second, the panel's hardware manual states the port allocation: which physical ports exist, which electrical standard each speaks, and which combinations are documented to run together. A project in which the first PLC already answers proves the panel runs and nothing more; it says nothing about the second driver, the second port or the second cable.
How many usable serial channels does the panel really have? #
Count communication channels, not connector shells: two labels such as COM1 and COM2 can hide one shared electrical interface, and the hardware manual's port allocation — not the printing on the panel — decides how many device connections run at once.
COM labels name logical interfaces. They do not fix voltage levels, pin assignments, or how many of them the runtime can drive simultaneously, and one connector shell can carry more than one electrical interface. Read the model's hardware manual for three things: the physical ports it actually has, the electrical standard on each, and the combinations the vendor documents as running at once. For the two-FX case, the practical starting point is a panel with two serial channels the manual documents as independent — one for each controller. If the model cannot document that, no cable arrangement will supply it.
Which driver does each FX PLC need in the project? #
Each controller gets its own device entry and its own driver: select a Mitsubishi FX driver for the FX1S, select one for the FX2N, and bind each entry to its own port, address setting and serial parameters.
In the panel's engineering software — EasyBuilder Pro on a Weintek panel — the driver is chosen per device entry in the project's device list, and the exact driver name for your series comes from the PLC connection guide, checked against the panel model and its runtime rather than the brand alone. The driver's documentation then fixes the serial parameters and the cable, and Mitsubishi's FX1S communication manual documents the RS-232C, RS-485 and RS-422 wiring on the PLC side. Match electrical standard to electrical standard, and never infer pins from connector shape. The pairing-specific faults — driver selection and cable — are collected in Fixing Weintek HMI to Mitsubishi FX PLC Communication.
Can I branch one cable to reach both PLCs? #
No — a point-to-point serial port serves exactly one device, and branching its cable to reach a second PLC ties two transmitters to one receiver with no addressing, so both connections corrupt instead of the port being shared.
Sharing one port among several devices takes two things at once: an electrical standard built for multi-drop, and a protocol that carries station addressing so each device knows which message is for it. Mitsubishi's FX1S communication manual documents RS-232C, RS-485 and RS-422 wiring, so a multi-drop electrical run can be built legitimately — but the driver and the PLC-side protocol must both document multi-device operation for that combination, and a branch on a point-to-point link is a splice, not a topology. Where station addressing does exist, sharing is normal: an RS-485 multidrop lets several panels serve one PLC port, as laid out in Connecting Multiple HMIs to One PLC Over 200 ft Serial. Decide it from documentation, never from connector shape.
Does showing both PLCs on one panel link the two programs? #
No — the panel is a client of each controller and nothing on it moves data between them, so the FX1S and the FX2N run independently unless the transfer is programmed in the PLCs themselves.
The same register address can exist in both controllers, and the device name on a screen object decides which one answers; the address alone does not. Treat every object as a pair — device plus address — because a field bound to the wrong device shows a plausible number from the wrong machine, and that fault is exactly the driver-tag-screen split worked through in Is It the Driver, the Tag or the Screen? Diagnosing HMI Values. If one controller needs the other's data, define that transfer in the PLCs, including what each side does while the link is down. The mirror arrangement — one device commanded by two controllers — follows its own feasibility rules, worked through in Control a PowerFlex 525 drive from two PLC controllers.
Example: what does one screen of four points per PLC cost at 9600 baud? #
A four-point read per PLC costs about 52 ms of line time per cycle at 9600 baud — 50 characters at 10 bits each — so refreshing four points every second loads that port to roughly 21%.
Assumed inputs, illustrative only: one read cycle moves 10 characters out and 40 back, serial framing at 10 bits per character (start, 8 data, stop), screens refreshing four points per PLC once per second. The arithmetic is standard, not a measurement of your driver:
- Bits per cycle: (10 + 40) × 10 = 500 bits
- Cycle time at 9600 baud: 500 ÷ 9600 = 52.1 ms
- Four points per second: 4 × 52.1 ms = 208 ms, about 21% of the channel
- The same cycle at 19200 baud: 500 ÷ 19200 = 26.0 ms, so 4 × 26.0 = 104 ms, about 10%
That is the wire-time floor only; the observed update interval runs longer by the PLC's measured response time and the driver's scan cadence, so read 21% as the irreducible share, not the total. The decision it gives: a light screen on each port fits with room to spare, while a screen that grows to 20 points per second at 9600 baud needs 20 × 52.1 = 1042 ms — more than the 1000 ms a second holds — so cut points, slow that screen's refresh, or step the port speed up, which halves the cycle time.
What breaks first when the second PLC is added? #
The first failure is almost never the cable: one connection was proven and the second was assumed, so a wrong driver, a busy port assignment or an object bound to the wrong device surfaces only once both run together.
Adding the second connection also loads the panel itself — two drivers share one processor, and heavy screens on both slow refresh on both, the mechanism traced in Why an HMI Freezes or Updates Slowly Over Serial. Match the symptom to the layer before touching hardware:
| Symptom with both connections live | Layer to check first |
|---|---|
| One PLC answers, the other never connects | Second device entry: port assignment, driver, cable |
| Both connect, a field shows the other machine's value | The object's device binding |
| Refresh slows once the second PLC was added | The polling budget on each port, per the example above |
| Values drop out intermittently with both running | Port allocation conflict, or the electrical run: shielding, grounding, length |
A blank field is not automatically a broken cable: read the panel's communication diagnostics, separate a failed connection from an invalid address, and inspect the object's configuration before replacing anything.
How do you prove both connections before the machine runs? #
Prove one controller at a time, then both together: a read-only point compared against the programming software's monitor, a write test with outputs inhibited, then each cable interrupted separately to see exactly what the operator sees.
- Build the FX1S device entry on its port and add one read-only object on a value you already know; compare the panel's number against the monitor value in the PLC programming software.
- Repeat for the FX2N on the other port before any full screen set is loaded.
- Run both connections together and add objects gradually, checking the device name on every object — on writes above all.
- Interrupt each path separately at the bench: confirm the panel flags the failed controller, the other connection keeps updating, and the configured loss indication appears. Restore the link and confirm values return with no queued write acting on its own.
Keep machine outputs inhibited through the write and interruption tests so a lost or restored connection cannot move anything. Proving the screens against live controller values before the panel goes on the machine is its own bench setup — Testing HMI Simulation Against a Live PLC lays it out.
Questions asked
Does the FX2N need an Ethernet module for this to work?
No. A serial connection works when the panel has a second usable channel and the right FX driver, and that is the simpler arrangement to commission. An Ethernet communication module on the FX2N is an alternative that frees a serial port and can shorten cycle times, but it adds a check of its own: the panel must document an Ethernet driver for the FX series, and the module must be one Mitsubishi documents for that PLC.
Can COM1 and COM2 run two different PLC drivers at the same time?
The labels name logical interfaces; they are not permission to run two drivers. The model's hardware manual states which physical ports exist and which combinations the vendor documents as running together, and the PLC connection guide maps drivers to ports for each series. Verify both documents for the exact model before building the project. The manual decides, not the printing on the connector.
What does the operator see when one of the two PLCs stops answering?
What a screen object shows during a communication loss is set per project, not automatic: it may hold its last value, show zeros or raise an alarm, and zeros on a setpoint display are the dangerous default. Decide the indication per object, make it visible to the operator, and prove it at the bench by pulling each cable separately while the healthy connection keeps updating.
How many PLCs can one HMI connect to at once?
There is no single number to quote. The ceiling is the simultaneous device-connection count the panel series documents, consumed per usable channel: two point-to-point serial channels serve two serial controllers, and an Ethernet channel may carry more where the driver and model document it. Read the connection guide for your series before promising a count to anyone.