Why PanelView 600 Plus Alarms Stay Blank and Configure Mode Crawls

HMI and touchscreens Published 6 min read

Short answer

Blank alarms mean the alarm Trigger Type, whole-word trigger address and message value do not match the PLC bits — with Trigger Type on bit and the trigger on the whole word, the message value is the bit number plus 1. The close-to-five-minute Configure Mode exit is tag errors elsewhere in the application; deleting loaded runtime applications was tried and changed nothing. Re-map the alarms, clear every reported tag error, and both symptoms clear.

On this page
  1. Separate the two symptoms before you edit
  2. Pick one trigger scheme and keep its mapping consistent
  3. Map one alarm end to end
  4. Clear the tag errors behind the slow exit
  5. Verify the two fixes independently
  6. What not to change
  7. Questions asked

Both symptoms are configuration faults with two separate fixes. Alarms stay blank because the alarm Trigger Type, the trigger address and the message value do not match the PLC bits: with Trigger Type left on bit and the trigger pointed at the whole word B17:0, a message driven by B17:0/1 needs the value 2 on its message line — the bit number plus 1. The close-to-five-minute wait after Goto Configure Mode is the station timing out on tags it cannot resolve in the processor, usually on screens far from the alarm setup; deleting the unused runtime applications was tried and changed nothing. Re-map the alarms, clear every tag error the runtime reports, and both symptoms clear.

Separate the two symptoms before you edit #

The machine behind these symptoms is a PanelView Plus 600 running a FactoryTalk View Machine Edition application, with a MicroLogix 1200 on serial DF1 at 19200 baud, roughly 60 HMI tags and 10 configured alarms. Those figures set the scale of the checks below; they are not the cause. Where you start depends on which observation is in front of you:

Observation First cause to check Decision
Alarm banner stays blank while the PLC runs Trigger Type, trigger address and message value do not match the PLC bits Re-map the alarms with the bit-plus-one rule
Goto Configure Mode takes close to five minutes Tags the runtime cannot resolve, anywhere in the application Run test mode and clear every reported error
Deleting unused runtime applications changed nothing Application count is not the variable Stop deleting and start diagnosing

Pick one trigger scheme and keep its mapping consistent #

FactoryTalk View ME alarms can be driven two ways, and the message value means a different thing in each.

The value scheme uses one analog integer tag as the trigger; Alarm_word_1 is a typical example name. PLC logic writes the active alarm's number into the word, so message 1 fires on value 1, message 2 on value 2, and so on up to 16 messages on one word. Past 16, add a second word such as Alarm_word_2 and continue the count.

The bit scheme leaves Trigger Type set to bit but points the trigger at the whole word — B17:0, not B17:0/1. PLC logic drives the alarm conditions from bits 1 through 15, and the value on each message line is the bit number plus 1:

PLC bit in B17:0 Message value
B17:0/1 2
B17:0/2 3
B17:0/7 8
B17:0/10 11
B17:0/15 16

One word carries 15 messages this way, against 16 for the value scheme. Do not mix the two. The arrangement first tried here, digital tags with LSBit in the alarm setup, matches neither scheme, which is why the banner stayed empty and why re-mapping, not tag-type changes, is the fix.

Map one alarm end to end #

  1. In the alarm setup of the FactoryTalk View Studio for Machine Edition project, record one message's Trigger Type, its trigger tag or address, and the value on its message line.
  2. In the PLC, find the rung that drives that alarm. Suppose the conveyor-jam alarm sets B17:0/7.
  3. Apply the rule: value = bit number + 1 = 7 + 1 = 8. Leave Trigger Type on bit, point the trigger at B17:0, and enter 8 on that message line.
  4. With the bit clear, confirm the banner is quiet. Set the bit and the message appears; clear it and the message drops.
  5. Repeat per alarm. Ten alarms fit on one word: bits 1 through 10 give values 2 through 11, leaving bits 11 through 15 spare.

Run the forced-bit tests on a bench system or with the machine in a state where a wrong or missing message cannot hurt anyone, because the alarm display is part of the operator's protection.

Clear the tag errors behind the slow exit #

A healthy FactoryTalk View ME Station reaches Configure Mode in seconds, a short while at worst — never minutes. Close to five minutes, call it 300 s, is not the serial link's fault, and the arithmetic shows it: at 19200 baud with no parity and one stop bit, a character occupies 10 bits on the wire (1 start, 8 data, 1 stop), so the link moves 19200 ÷ 10 = 1920 characters per second. Over 300 s that is 300 × 1920 = 576,000 characters, against roughly 60 tags whose live traffic is a few hundred characters per scan. The minutes are timeout-and-retry cycles on tags the station cannot resolve in the processor while it shuts down.

  1. Run the application in test mode on a computer connected to the running processor, and watch the bottom of the screen for error text as it loads.
  2. Treat each reported error as a work item: a tag that cannot be found in the processor, an address that no longer exists, an object left pointing at a deleted tag. These errors routinely sit on screens nowhere near the alarm setup.
  3. If test mode is not available, enable the information function in the ME Station startup settings under the System tab of the project tree, repeat the exit, and read the errors the terminal reports.
  4. Fix or delete each offending tag, press Goto Configure Mode again, and time it. Seconds is the pass.

Live values that turn into question marks rather than error text point at the communication path instead of the tag definitions, the failure traced in PanelView Plus logic module shows question marks on live values. And if the terminal will not offer Configure Mode at all — no config button, or flash too full to load — that is a separate fault with its own fix in PanelView Plus 600 With No Config Button and Full Flash.

Verify the two fixes independently #

One passing alarm proves the mapping rule, not the whole table, so test each message:

  • For each of the 10 alarms: condition on in the PLC, intended message on the banner; condition off, message gone.
  • On the value scheme, exercise the numbers the PLC actually writes — for example values 1 and 2 for the first two messages — including the highest one in use.
  • Press Goto Configure Mode and time the exit against the original wait.
  • With the PLC quiet, confirm the banner raises nothing on its own.

What not to change #

  • Do not convert every alarm tag to analog on a guess. Analog belongs to the value scheme; the bit scheme keeps the bits and corrects the trigger address and message value instead.
  • Do not reuse the LSBit digital arrangement unchanged. It matched neither scheme here, and it will keep the banner empty.
  • Do not use bit 0 for an alarm. The mapping starts at bit 1, and a routine that sets B17:0/0 raises nothing.
  • Do not delete runtime applications to shorten the exit. Three of four were removed with no change, so application count is ruled out — spend the time on the error list instead.

Questions asked

Should the alarm tags be analog or digital on a PanelView Plus?

Either works, but only with its own mapping. An analog integer tag belongs to the value scheme, where PLC logic writes 1 through 16 into the trigger word and each message fires on its own number. A digital arrangement belongs to the bit scheme, where Trigger Type stays on bit, the trigger addresses the whole word such as B17:0, the PLC uses bits 1 through 15, and the message value is the bit number plus 1. Changing tag type without changing the mapping fixes nothing.

Why did deleting unused runtime applications not speed up Configure Mode?

Because the wait is not application count. The station spends those minutes timing out and retrying tags it cannot resolve in the processor before it exits, so the fix is to clear every error the runtime reports, often on screens far from the alarm setup. Deleting three of four loaded applications was already tried in this case and changed nothing, which rules that variable out.

Can bit 0 of the trigger word be used for an alarm?

Not in this scheme. The documented arrangement starts at bit 1 and runs through bit 15, mapping to message values 2 through 16. Bit 0 is left unused, so a PLC routine that sets B17:0/0 raises no message configured this way. Move the alarm to bit 1 or higher and set the message value to the bit number plus 1.

How many alarm messages fit on one trigger word?

Sixteen with the value scheme: message values 1 through 16 on one integer trigger word. Fifteen with the bit scheme: bits 1 through 15 give message values 2 through 16. Past those counts, add a second trigger word and repeat the same mapping on it.

Keep reading

  • How-to

    Keep a PanelView Plus Trend Logging After Screen Changes

    A PanelView Plus Trend object only records while its screen is visible. Configure a Data Log model to start at power-up, show it through an XY trend with pen 2 as the X axis, and give the log a bounded record limit so it overwrites the oldest records instead of growing without bound.

    HMI and touchscreens

  • Troubleshooting

    Fixing Goto Display Buttons Locked by HMI Global Connections

    While the Global Connections remote display number is active — its DINT tag still holding 21 — FactoryTalk View ME disables every other form of navigation, so Goto Display buttons stay dead whether or not the popup is visible. Write 21 with a one-shot on bit A and let a startup macro on display 21 reset the tag to 0; the popup stays up and the buttons respond.

    HMI and touchscreens

  • How-to

    Showing Tags From Five PLC-5 Processors on One PanelView Plus

    Yes. One PanelView Plus screen can show tags from all five PLC-5/25 processors, because each object resolves through its own shortcut to one controller's station address on DH+. Configure five shortcuts and prove one known live value from each processor before building production screens.

    HMI and touchscreens