Troubleshooting
Why Report System Error alarms are missing on Comfort Panels
Short answer
Report System Error alarms from a STEP 7 V5.x CPU reach an integrated WinCC flexible HMI directly, but a TIA Portal Comfort Panel reads them through a PLC proxy snapshot. Enable RSE in SIMATIC Manager, initialize the proxy data again in the TIA Portal HMI project, download to the panel, and the diagnostic alarms appear under HMI alarms > Controller alarm.
On this page
A Comfort Panel fed from a STEP 7 V5.x CPU goes silent on Report System Errors for one reason: the TIA Portal project reaches that CPU through a PLC proxy, and the proxy still holds the tag and alarm snapshot from before you enabled the function. Enable Report System Errors in SIMATIC Manager, then initialize the proxy data again in the TIA Portal HMI project and download it to the panel. The diagnostic alarms then arrive in the panel's alarm display under HMI alarms > Controller alarm — the same events you already see without trouble on an integrated WinCC flexible HMI. Below are the check, the fix and a bench test that proves the diagnostic path end to end.
Where the alarm chain breaks #
Report System Errors is a STEP 7 function you switch on in the hardware configuration of the SIMATIC Manager project: you define the message texts there, and the CPU then generates diagnostic alarms for events such as a hardware component removed or a station failure. On an S7-300 or S7-400 CPU such as the 315F 2PN/DP, an HMI integrated into the same SIMATIC Manager project — WinCC flexible in the reported working setup — reads those alarms straight from the CPU project, so every configured event lands in the alarms screen.
A Comfort Panel engineered in TIA Portal cannot do that. The CPU project stays in SIMATIC Manager while the HMI project lives in TIA Portal, and the TIA project reaches the controller through a PLC proxy: a copy of the PLC tags, alarms and system diagnostics that the panel addresses symbolically. The proxy is a snapshot taken when its data was last initialized. Any change you make in the SIMATIC Manager project afterward — enabling Report System Errors is exactly such a change — never reaches the panel until you initialize the proxy data again. That is why the same CPU reports alarms to a WinCC flexible terminal and reports nothing to a TP900 or TP1500 Comfort in the same plant. If you inherited this split when the HMI side moved tools, how to migrate a WinCC flexible project to TIA Portal explains what moves between the tools and what stays behind.
Confirm which configuration you have #
Before changing anything, confirm the panel really sits on the snapshot path:
- Check the PLC entry the HMI connection uses: a proxy instead of an integrated CPU means the TIA project reads a snapshot of the SIMATIC Manager data.
- Confirm the CPU is engineered in SIMATIC Manager under STEP 7 V5.x; a CPU configured wholly in TIA Portal has no proxy and no snapshot to refresh.
| Configuration | Alarm path | Observed result |
|---|---|---|
| CPU 315F 2PN/DP with an integrated WinCC flexible HMI | direct, from the CPU project | all Report System Error alarms appear in the alarms screen |
| CPU 315F 2PN/DP with a TP900 or TP1500 Comfort via a PLC proxy | through the proxy snapshot | alarms absent until the proxy data is initialized again |
| Same panel after the proxy refresh | through the refreshed proxy | diagnostic alarms appear under HMI alarms > Controller alarm |
Initialize the proxy data again #
Work through these four steps in this order:
- In the SIMATIC Manager project, enable and configure Report System Errors in the hardware configuration, then compile and download the CPU project.
- Open the TIA Portal HMI project and go to the PLC proxy configuration.
- Initialize the proxy data again, so the proxy picks up the new alarm and diagnostics configuration from the CPU project.
- Compile the HMI project and download it to the Comfort Panel.
Skipping step 3 is the failure behind nearly every report of this symptom: the CPU now sends the alarms, but the panel still holds the pre-RSE snapshot and has nothing to display. The function to look for is the one that re-reads the SIMATIC Manager data into the proxy, on the proxy's own configuration page in the HMI project.
Prove it with a real diagnostic event #
An ordinary operator-generated alarm on the panel proves only that the alarm display works. To verify the diagnostic path, trigger a real controller diagnostic event and watch the controller alarm class. Do this on the bench or during planned downtime — never pull a connector on a running machine.
Worked bench example: at 10:42:05 you switch off power to a configured, diagnostics-capable bench node. At 10:42:07 the panel's alarm display shows the station-failure entry under HMI alarms > Controller alarm, a two-second delay that covers the CPU diagnostics cycle and the panel's alarm update. You restore power at 10:43:00 and the corresponding leaving event closes the entry at 10:43:02. Those timestamps prove the chain end to end: CPU diagnostics, proxy, connection, alarm class, display. The example delays come from one bench observation; your own timing depends on the CPU's diagnostics cycle and the panel's update cadence, so record your own timestamps rather than assuming two seconds.
If the Controller alarm list stays empty #
Work through these in order:
- Confirm the proxy can go online: the panel cannot refresh a snapshot from a CPU it cannot reach.
- Confirm the CPU project with Report System Errors enabled was actually downloaded; a CPU still running the old project generates no diagnostic alarms.
- Check that the alarm display and the alarm logging are configured to show controller alarms, not only HMI user text alarms.
- If nothing at all arrives from the controller, prove the connection itself first, as in showing a PLC connection fault on a Comfort Panel alarm display, then come back to the proxy.
Questions asked
Why do Report System Error alarms reach WinCC flexible but not my Comfort Panel?
The WinCC flexible HMI is integrated into the same SIMATIC Manager project as the CPU, so it reads the diagnostic alarms directly. The TIA Portal Comfort Panel reads them through a PLC proxy snapshot taken before the function was enabled. Initialize the proxy data again and download the HMI project.
When does the proxy data have to be initialized again?
After any change in the SIMATIC Manager project that affects tags, alarms or diagnostics. Enabling Report System Errors is the classic case: the CPU starts sending diagnostic alarms, but the proxy still carries the alarm set from its last initialization. Re-initialize after every such CPU-project change, then download the panel.
Where do CPU diagnostic alarms appear on a Comfort Panel?
In the alarm display under the controller alarm class, the list reached as HMI alarms and then Controller alarm. If that list shows your own HMI text alarms but no controller events after a real diagnostics event such as a removed module, the proxy snapshot is the first thing to refresh.
Does this proxy step apply to an S7-1500 controller?
No. The proxy workflow here applies to a STEP 7 V5.x S7-300 or S7-400 CPU such as the 315F 2PN/DP. An S7-1500 is engineered wholly in TIA Portal, so the HMI reads its diagnostics over an integrated connection and there is no SIMATIC Manager snapshot to refresh.