Troubleshooting
Why the HMI image updater login fails with invalid_request
Short answer
A browser sign-in to the portal that works proves nothing about the HMI Panel Image Updater, because the updater signs in in the background and cannot answer any prompt — an MFA challenge, a choice between linked accounts, or a passkey reminder. Run one fresh, complete browser sign-in and finish whatever it shows; if a prompt keeps returning, or none appears and invalid_request stays, skip further reinstalls and install the panel image from the offline package.
On this page
- Why does the HMI Panel Image Updater fail my login with invalid_request?
- Why can I still sign in to SiePortal in the browser?
- Why did a reinstall, a second PC and a second network change nothing?
- How do I catch the pop-up that is blocking the updater?
- How do I clear each type of sign-in prompt?
- What should I do when the updater still fails after a clean sign-in?
- How do I get panel images without the updater login?
- Fix the prompt or switch to the offline image — which one wins?
- Questions asked
The updater that fetched panel images without trouble now answers every attempt with invalid_request and a message about an unexpected authentication error, while the same account still opens the portal in a browser without a hitch. That combination has one explanation: the HMI Panel Image Updater signs in to SiePortal in the background, and a background sign-in cannot answer anything the account raises mid-flow. Browser access proves the account is alive; it does not prove the updater's request can finish. Work in this order: run one fresh, complete browser sign-in and deal with whatever screen it raises, retry the updater, and if a prompt keeps returning, or no prompt appears and the error stays, stop reinstalling and pull the panel image with the manufacturer's offline package instead. The error text names no culprit, so you catch the cause in the browser, not in the updater.
Why does the HMI Panel Image Updater fail my login with invalid_request? #
The updater signs in to the download portal in the background, so any account whose browser sign-in shows an extra screen — a multi-factor challenge, a pick-one-of-several linked accounts, or a passkey activation reminder — kills that background sign-in with invalid_request.
The updater does not open a browser window and hand you the login screens. It performs a background login to SiePortal: one request that expects a straight exchange of your credentials for a working session. The global Siemens ID added configuration options that assume a human sits in front of the flow — a second factor after the password, a decision when one ID is linked to several SiePortal accounts, an enrollment push. In a browser, the portal stops and shows that screen. In a background request there is nobody to show it to, so the login service rejects the request, and the updater surfaces its catch-all pair: The application has encountered an unexpected authentication error and invalid_request.
The message is generic and names no prompt or setting. When a login that worked for months starts failing, the realistic cause is that the account's sign-in configuration changed, not that the tool or the password broke. Three interactions cover practically every case:
- A multi-factor authentication challenge, where sign-in demands a second factor such as an authenticator approval after the password.
- A linked-account selection, where one Siemens ID opens more than one SiePortal account and the portal asks which one.
- A passkey activation reminder, where the portal interrupts a normal sign-in to push passkey setup.
Why can I still sign in to SiePortal in the browser? #
Browser sign-in proves only that the account can complete an interactive flow, where the portal can stop and ask you something; the updater cannot stop and ask, so a passing browser login says nothing about whether the updater's own flow will finish.
An interactive flow can pause, display a screen and wait as long as it needs to. A background login sends one request and expects the service to answer it; when the service instead requires an interaction, the request cannot proceed and comes back invalid. Nothing in that says the credential is weak, the password expired or the account is locked — a broken account fails in the browser too, and yours does not.
Two traps make the browser check lie to you. A tab that is already signed in can skip the very screen you are hunting, because the living session satisfies it silently. And answering a prompt by hand in the browser teaches the updater nothing, because it runs its own flow from scratch next time. The same constraint sits behind why an AdvancedHMI auto-start requires an interactive sign-in: a process that runs with nobody at the screen cannot answer the questions an interactive sign-in asks.
Why did a reinstall, a second PC and a second network change nothing? #
Those tests rule out the PC and the network, which is exactly why they are worth reading once and not repeating: the failure travels with the account, not with the machine, so another cache cleanup or reinstall cannot fix it.
Read each result as its own verdict:
- The same account signs in through the portal in a browser — the credential is valid, so this is not a password or lockout problem.
- The same error on a second computer — not a corrupted installation or a poisoned cache on the first one.
- The same error on a second network — not a firewall, proxy or DNS rule at the first site.
- Complete removal including the cache files, then a reinstall — local application state was never the cause.
- Version V2.1 installed, the current release at the time of the fault — an outdated build is not the trigger.
Five dead ends point one direction: the failure lives with the account and the login service, not with anything you can wipe. One influence those tests cannot fully exclude is a security policy that follows both computers, such as managed browser settings or domain policy applied at both desks. Check that only if a fresh browser sign-in shows no prompt at all and the updater still fails, because a policy that injects an extra step would show itself in that fresh sign-in first.
How do I catch the pop-up that is blocking the updater? #
Sign out completely and run one fresh, end-to-end browser sign-in with the affected ID, and watch every screen it raises; the pop-up the portal shows you is the same interaction the updater's background login cannot answer.
- Sign out of every portal tab and close the browser. A session that is still alive can skip the screen you are hunting for.
- Start a fresh sign-in with the affected Siemens ID. Straight entry to the account means no prompt; anything that appears between the password and the portal home page is the suspect.
- Classify what appeared: a second-factor request, a choice between linked accounts, a passkey reminder, or another account action. Note the wording; never capture codes or passwords in a screenshot.
- Finish the screen and check which account you land in. With several accounts linked to one ID, you must land in the one you actually use for panel image work.
- Sign out and run the whole sign-in a second time. A one-time reminder stays gone; a recurring challenge returns, and a returning prompt is account configuration, not bad luck.
If every fresh sign-in lands you directly in the account with nothing asked, the pop-up theory is dead for this account, and the remaining checks live two sections down.
How do I clear each type of sign-in prompt? #
Each prompt has its own clearing move: complete the multi-factor challenge, settle which linked account you intend to use, or finish the passkey enrollment the portal is reminding you about — and never switch off a required second factor just to please one desktop tool.
| What the portal shows | What it is asking | What clears it |
|---|---|---|
| Multi-factor authentication challenge | A second factor on top of the password, configured in the account's security settings. | Approve the authenticator prompt or enter the requested code, then sign in again. A challenge set as mandatory returns at every sign-in, and no desktop setting removes it. |
| Linked-account selection | One Siemens ID is linked to more than one SiePortal account. | Choose the account you use for panel image downloads, then review the account links in the portal's account management so future sign-ins land where you expect. |
| Passkey activation reminder | An enrollment nudge interrupting the normal sign-in sequence. | Complete or dismiss the enrollment through the choices the portal offers, then run another fresh sign-in to confirm the reminder is gone. |
Clearing works when the interaction is a one-time reminder or a settleable choice. A mandatory recurring challenge cannot be answered by a background login no matter what you delete locally, which is exactly why cache cleanup feels productive and changes nothing: the login service raised that prompt on the account side, not on your PC.
What should I do when the updater still fails after a clean sign-in? #
If a fresh sign-in raises no prompt at all and the updater still returns invalid_request, stop reinstalling and treat it as a compatibility problem: check the version you run, report the exact failure to the portal support channel, and move your image work to the offline route meanwhile.
Retry the updater immediately after the clean sign-in, while the account state is settled. A success closes the case, because the prompt was the whole problem. A repeated invalid_request with no prompt anywhere in the browser moves the fault from account configuration to tool compatibility: changes to the login system can require an updater revision, and the version that counts as current is not a permanent guarantee. Compare your installed build against the current release on the updater's download page before you report anything.
Send the support channel a packet it can act on: the updater version, the exact error text, the date and time of the attempts, whether a fresh browser sign-in showed any prompt, and your second-computer and second-network results. Leave credentials, one-time codes and session tokens out of it entirely. While that conversation runs, the offline route in the next section keeps panels getting their images.
How do I get panel images without the updater login? #
Use the manufacturer's offline package, Image Downloads for SIMATIC HMI Operator Panels: Comfort / Mobile / Basic Panels, which installs a panel image without any updater login — identify your panel from its nameplate or device information, pick its image from the package, and follow its documented installation steps.
Fetching the package needs only the browser sign-in that already works for you; the updater and its background login play no part in installing the image. The package page lists its images by panel family and by generation, and its offline installation entries cover panel images for the V16 and V17 generations of Comfort, Mobile and Basic panels.
Work it in this order:
- Identify the panel from its nameplate or its device information pages; the full order number printed there decides which image applies.
- Pick the image for that panel in the generation your project was engineered in, because the image you install still has to match the project — that matching is exactly what matching an HMI panel image to its TIA Portal project version covers.
- Install it by the package's own documented steps, and treat the image as the panel's operating system rather than your project: back up the project and the panel's configuration before the image operation, and keep that backup outside the panel.
Fix the prompt or switch to the offline image — which one wins? #
Fix the prompt first when a fresh browser sign-in shows an interaction you can complete or settle once; go straight to the offline package when the prompt is mandatory and recurring, or when no prompt appears and invalid_request survives a clean sign-in.
- A one-time passkey reminder or a settleable account selection: clear it in the fresh sign-in, retry the updater, and stay on the online route.
- A multi-factor challenge that returns at every sign-in: leave the account's security policy alone, do the image work through the offline package, and revisit only when an updater release documents support for the current sign-in flow.
- No prompt in a fresh sign-in and an unchanged error: file the support packet from the section above and run offline in the meantime.
- Browser fine, updater broken, everything else untouched: the account needs no repair for your other work; only flows that cannot show a screen are blocked, and those stay blocked until the tool or the account changes.
Questions asked
Does invalid_request mean my Siemens ID password is wrong?
No. A wrong password fails the browser sign-in too, and yours succeeds, so the credential is not the problem. This error means the sign-in request cannot be completed as a background exchange, which happens when the account raises an interaction such as a second-factor challenge, an account selection or a passkey reminder. Interactive logins keep working; only flows that cannot display a screen fail.
Can the updater reuse my browser session so the prompts get answered?
No documented setting hands the updater your browser session or lets it open a login window for you to answer. Its sign-in is its own request, so a prompt has to be settled at the account level: completed once if it is a reminder, configured away if it is a recurring challenge, or avoided by installing panel images from the offline package.
Will a future updater release work with mandatory multi-factor sign-in?
That depends on the tool's release history, not on anything you can configure. Changes to the sign-in system can require an updater revision, and those revisions do not arrive on a schedule you can plan around. Watch the updater's download page for a build newer than V2.1 and keep the offline image package as your working route until one appears.
Which of my linked accounts should I settle on before retrying?
The one you actually use for panel image work. Sign in once in the browser and read the account name on the page you land on; the portal's account management area lists every account linked to the ID and is where a wrong default gets corrected. Settle it, confirm a fresh sign-in lands in the right account, then retry the updater.
Does this failure affect every panel image the updater tries to fetch?
Yes. Every fetch goes through the same background sign-in, so the error blocks the download step for all panel families rather than one model. It touches nothing else: portal use in the browser, other tools with interactive logins and the offline image package all keep working while the updater itself stays blocked.