Why the Modbus Server Device Is Missing in EasyBuilder Pro

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

Modbus Server disappears from the EasyBuilder Pro device list because the installed build is older than the driver: a project on build V6.07.02.320 showed no entry on any selected model, and installing EasyBuilder Pro 6.08 restored it. Update the software from the vendor's download before concluding that a panel model cannot run a Modbus server.

On this page
  1. Why is the Modbus Server device missing from the device list?
  2. Does the HMI model decide whether Modbus Server appears?
  3. How do you check which EasyBuilder Pro build is installed?
  4. Which update restores the Modbus Server device?
  5. How do you add the Modbus Server device once the entry is there?
  6. How do you verify the server before the third-party system connects?
  7. What if Modbus Server is still missing after the update?
  8. Questions asked

If Modbus Server is not in the device list, the engineering software is too old — the panel is not the limitation. In the case behind this article, a project on build V6.07.02.320 offered no Modbus Server entry, a second project built for a different model showed the same empty result, and installing EasyBuilder Pro 6.08 restored the entry in the original project. The check below follows the order you meet the problem: read the build number, rule out the model question, update from the vendor's own download, add the device through System Parameter Settings, and prove the server on a bench before a third-party system reads the panel's tags.

Why is the Modbus Server device missing from the device list? #

The entry is missing because the installed EasyBuilder Pro build predates the driver: the environment that showed the fault ran build V6.07.02.320, and the Modbus Server device only became selectable after the engineering software was updated to 6.08. The Device list inside System Parameter Settings shows the drivers compiled into the build you have installed, and drivers are not plug-ins you can add afterwards. The vendor catalogs more than 400 drivers in the software, and that catalog grows build by build, so no setting can reveal an entry the build does not contain. The evidence from the case makes the version the deciding factor:

Check Result
CMT-SVR-100 project on build V6.07.02.320 No Modbus Server entry in the Device list
Fresh project for the CMT3072XH, same build Still no Modbus Server entry
Software updated to the 6.08 line Modbus Server selectable in the same project

Two models, one missing entry, and one fix that arrived with the software update: the pattern points at the build, not at the hardware.

Does the HMI model decide whether Modbus Server appears? #

No. A test project created for the CMT3072XH, the same model used in the setup walkthrough the case followed, showed the same empty result on the old build, so changing the selected model cannot restore an entry the installed build does not contain. Model-dependent device lists do exist — some drivers apply only to particular panels — but that is not what happened here. When one entry is missing across two different models, the common factor is the software. Judge server capability only after the software is current: the vendor's connect guide documents the Modbus Server device as a standard entry added through System Parameter Settings, not as a special feature of one model, so a missing entry on an outdated build is not evidence that a panel cannot serve.

How do you check which EasyBuilder Pro build is installed? #

Read the build number from the about dialog in the software's help menu and compare it with the 6.08 line: any older build that shows no Modbus Server entry is a candidate for the update, whichever model the open project targets. Version strings compare left to right, and the reported case gives a clean worked example. The build V6.07.02.320 has the leading pair 6.07; the line that restored the entry in the case is 6.08; 6.07 precedes 6.08, so that build sits one minor line behind the software that carries the driver. Record three things before updating: the build shown in the about dialog, the model selected in the project, and whether a new empty project lacks the entry as well. If a fresh project for a different model also lacks the entry, the cause sits in the build — that comparison is what settled the reported case.

Which update restores the Modbus Server device? #

Install EasyBuilder Pro 6.08, as the full installer, from the manufacturer's own download page or its authorized distributors, and the Modbus Server entry appears in the device list of the existing project without recreating anything. Take the installer only from the vendor or its distribution channel: driver packs and documentation belong to the manufacturer's download area, and a mismatched or third-party package is a common way to end up with a build that still misses drivers. In the reported case the fix was exactly that — install the new build, reopen the same project, and the option was there.

How do you add the Modbus Server device once the entry is there? #

Open System Parameter Settings, add a new device in the Device list, choose Modbus Server as the device type, and set its interface to Ethernet for network clients or to the serial interface for a client wired to a COM port — the vendor's connect guide documents exactly this path. The steps, in order:

  1. Open System Parameter Settings in the project.
  2. In the Device list, click New.
  3. For PLC type, select Modbus Server.
  4. Set PLC I/F to Ethernet for a network client, or to the serial interface when the client hangs off a COM port.
  5. Confirm the entry and note which transport it sits on, because the client must reach the panel on that transport.

The device turns the panel into the answering side of the exchange: a third-party system connects as the client and reads the panel's data, the division of roles described in HMI Modbus TCP client and server roles with no device driver. Keep the roles straight during commissioning — the panel answers, the outside system asks.

How do you verify the server before the third-party system connects? #

Confirm it on a bench before production: with the panel and a test client on an isolated network, map two or three known tags in the server device, read those addresses from the client, and accept the result only when returned values match the tags the panel displays. Make one change on the panel and confirm it appears in the client's next read; a value that matches on both sides proves the mapping and the transport together. If the client reads values that look shifted or offset, the fault is almost always register addressing, the subject of Fixing Modbus TCP Addressing Errors Between an HMI and a PLC. Keep this test on an isolated bench network — pointing a test client at a live controller is how unintended writes reach production equipment.

What if Modbus Server is still missing after the update? #

Then the installed package is probably not the distribution the walkthroughs assume: regional and rebranded builds of the same software can name drivers differently, so search the device list for a server-type Modbus entry rather than expecting the exact label from a video or manual. Two related failures live one step away from this one. A driver that should exist but never shows up in any project is covered in why an exclusive device driver is missing from your EasyBuilder Pro, and a software list that differs because the panel or package came from another market is covered in why a regional-market HMI is missing from your software list. The decisions, in order: an older build without the entry — update the software; the entry present — add the device through System Parameter Settings and bench-verify before the plant connects; a current build from the correct distribution still without the entry — take it to the vendor's support channel with the build number and the selected model, because at that point the driver is genuinely absent from the build you own.

Questions asked

Does the panel's OS or firmware also need an update?

In the reported case, no. Installing the newer EasyBuilder Pro build on the engineering PC restored the entry, and no change on the panel itself was required. After updating, compile and download the project as usual; if the download step then reports a mismatch between the project and the panel's OS, apply the panel update that prompt asks for instead of mixing build lines.

Does the same fix apply to other missing device entries?

The same logic applies: a device entry that no project shows usually means the build predates the driver, so check the software version before treating the entry as unsupported. Two driver-specific causes have their own patterns: a driver that needs a particular package to appear, and a device list that differs because the panel or the software package came from another market.

Can a Modbus Server entry coexist with the controller drivers in one project?

Yes. The server entry lives in the same Device list as the controller drivers, so the panel keeps its normal connection to the PLC while answering a client's reads. Commission the two separately: confirm the controller link first, then bring up the server entry and test it from a client on the bench.

What should the third-party system's engineer be told first?

Give them the transport, the panel's address on that transport, and the register map with the data format of each address. Most first-connection failures trace to a format or an offset mismatch in the map, not to the server itself, so agreeing on the map before wiring up saves a return visit.

Keep reading

  • How-to

    HMI Modbus TCP client and server roles with no device driver

    With no dedicated driver, the HMI works as the Modbus TCP client and the controller's virtual Modbus TCP slave as the server that answers on port 502. Add and activate the virtual slave in PiCtory, add the generic Modbus TCP/IP device in EasyBuilder Pro, and take every register number from the server's process-image map — one register per two bytes of process image, so byte offset 20 is register 10.

    HMI and touchscreens

  • How-to

    Relaying serial PLC data through a C-more HMI to SCADA

    The C-more EA9 is a communications client: it polls the PLCs it is configured for and exposes nothing for Ignition or KepServer to browse. Make the panel the relay instead — add a Modbus TCP server as a second PLC device and copy FX3 tags into it with Tag Copy events triggered from the system clock tags, since scheduled copies run at best once per minute.