IMDTouchKnowledge BaseShop main store

Troubleshooting

Why the PDATA.FWX configuration file could not be loaded

HMI and touchscreens Published 7 min read

Short answer

The message means the panel could not read the runtime configuration file its project generated, so it shut the application down. Save a backup, delete the generated PDATA file from the project, compile again, and prove the project starts clean on the PC runtime before redownloading. If the panel still fails, delete its stale copy from the flash storage folder the message names and download again.

On this page
  1. Why does the TP1200 report this PDATA.FWX message at startup?
  2. Why does a successful download from TIA Portal still end in this error?
  3. Why does the same error appear when the project runs on my laptop?
  4. How do I rebuild the generated PDATA file in the project?
  5. Should I also delete the file from the panel's flash storage?
  6. What if the rebuilt project still fails on both targets?
  7. How do I keep this error from coming back?
  8. Questions asked

Your TP1200 is not damaged and the download is not the problem. The message names the generated runtime configuration file the HMI application must read at startup; when that file will not load, the panel ends the application by design. The repair is to regenerate the file, not to chase the transfer: save a project backup, delete the generated PDATA file from the project, compile again, and start the project on the laptop runtime before downloading anything. That order matters because the laptop reproduces the error, so the unusable file travels inside the project. Once the laptop starts clean, download to the panel; if the panel alone still fails, delete its stale copy at \flash\simatic\PDATA.FWX and download again.

Why does the TP1200 report this PDATA.FWX message at startup? #

The message means the panel's runtime started, tried to open the generated startup file at \flash\simatic\PDATA.FWX, could not read it, and ended the HMI application by design rather than continuing on a broken configuration.

PDATA.FWX is not a file anyone writes by hand. The engineering software generates it during compilation, and it holds the startup configuration the runtime reads before the first screen appears. The panel names it because it is the exact load that failed — not a screen, not a connection, not the project archive. Three consequences follow. A compile without errors says the tool finished its work, not that the output is loadable. A download without errors says the bytes arrived, not that they open. And because the file is generated, it can be replaced whole: nothing in this repair involves opening it, editing it or repairing its contents, which is why the fix is fast and never touches your screens, tags or scripts.

Why does a successful download from TIA Portal still end in this error? #

A completed download proves the transfer arrived, not that the panel can load what it received; compile status, transfer status and load status are three separate gates, and this error sits at the third.

Compile, transfer and load are three separate gates, and only the first two give you feedback before startup. The compiler reports problems in the tool, the transfer reports progress on the cable, and the load happens afterwards, silently, on the target. That is why re-downloading the same compiled output reproduces the same failure perfectly: you have moved an unreadable file reliably. The panel never complained about the transfer — it complained about the load, after the transfer had already succeeded. Once you accept that the download result tells you nothing about this error, the laptop test in the next section becomes the only diagnostic that matters.

Why does the same error appear when the project runs on my laptop? #

When the PC runtime on your engineering laptop reports the same message, the unusable generated file travels inside the project, so the panel's flash storage, its cable and its boot sequence drop out of the suspect list.

Two targets showing one message share one ingredient: the compiled project data. The panel's storage, its boot loader and its cable are all cleared, because the failure followed the project onto hardware they never touch. This test is also the gate for the whole repair — a project travels to the panel only after its own runtime starts without the message. If you also serve a visualization PC from the same project, one documented detail completes the picture: the PC loader takes its runtime file from the directory configured under Settings > Directories > Configuration file, so a moved, renamed or stale file there produces the same class of startup failure the panel shows.

How do I rebuild the generated PDATA file in the project? #

Save a backup of the project, delete the generated PDATA file from it, compile again so the engineering tool writes a fresh one, and keep the panel out of the loop until the laptop runtime starts clean.

Work the sequence in order and let each step prove the one after it:

  1. Save a backup copy of the project before anything is deleted. A backup only protects you if it actually contains the HMI data, so confirm the archive scope first — start from verifying HMI project data is inside your platform backup.
  2. Delete the generated PDATA file from the project. It is compile output, not editable source: screens, tags, connections and scripts are separate data and are untouched, which is the same output-versus-source separation described in why the compiled HMI project view is not for editing.
  3. Compile the project again. The tool regenerates the file from your source; confirm the compile finishes without errors.
  4. Start the project on the laptop runtime. If it starts without the configuration-file message, the rebuilt file loads. If the message returns on the laptop, stop here and go to the runtime reinstall step below.
  5. Download the rebuilt project to the panel, let the application start, then power-cycle the panel once to confirm a cold start loads as well.

Schedule the panel-side steps at a planned stop: from the moment the runtime stops until it starts again, that panel gives nobody a view or control of the machine.

Should I also delete the file from the panel's flash storage? #

Yes — once the project itself is proven good on the laptop, delete the stale panel copy at \flash\simatic\PDATA.FWX and download again; the next transfer recreates it.

The order matters. The laptop test already told you who owns the fault: a clean laptop run with a panel that still fails points at the deployed copy on the panel, which the transfer should overwrite but evidently has not. Open the panel's file explorer from its Control Panel, browse to the Simatic folder on the flash storage — the location the message prints — and delete PDATA.FWX there. On Windows CE operator panels of the documented kind, the same folder appears in the explorer as My Device > Flash Disk > Simatic. Then download the rebuilt project again and let it start. Both targets now load freshly written output from the same verified compile, which is exactly the end state you want.

What if the rebuilt project still fails on both targets? #

Split the targets one more time: a panel that still fails gets an operating system update from the engineering tool, and a laptop that still fails gets its PC runtime repaired or reinstalled.

A rebuilt file that loads nowhere is no longer a file problem, so stop regenerating and treat the platform under each target.

Panel side, the remaining variable is the panel's operating system image. The vendor documents precisely this escalation for the sibling message that names pdata.fwc: update the panel operating system from the engineering tool through Online > HMI Device maintenance > Update operating system. An image update is also the point to confirm the engineering tool still supports this panel; the checks in checking HMI engineering software before a panel replacement are the ones to run.

Laptop side, a PC runtime that rejects a freshly compiled project has an installation fault. Repair or reinstall the runtime from your original installation source and retest before suspecting the project again.

Keep the backup, and write down the exact message text, the path it prints and the tool and panel versions — that is the evidence set the next engineer will ask for.

How do I keep this error from coming back? #

Treat every generated runtime file as disposable compile output: never hand-edit it, never copy one between projects or panels, and archive only the editable project source you rebuild from.

Generated files never migrate. When the project moves to a new engineering PC or the machine gets a replacement panel, move the project source and compile on arrival; copying compiled output between machines is how a stale configuration survives a rebuild and comes back as this same message. Archive the source after every accepted change so the next rebuild starts from a known edit, and keep the panel image and the tool versions matched.

The pattern is not new, either. The ProTool generation reported the same kind of load failure for its runtime configuration file, and our article on resolving the ProTool runtime configuration file load error runs the identical backup, delete, recompile sequence. WinCC on the PC has its own member of this family; the WinCC 6.2 MCP file load error resolution applies the same replace-the-output logic to a PC-side file.

Questions asked

Will deleting the PDATA file erase my screens, tags or alarm texts?

No. Those live in the editable project source, which this procedure never deletes. The PDATA file is compile output describing how the runtime starts; the next compile rebuilds it from the screens, tags and connections you keep. That separation is why deleting the generated file is safe and why the project backup you save covers everything of value.

Why did this error start after the panel ran fine for months?

The message reports the load failure, not the cause; nothing in it distinguishes an interrupted write from a leftover file of an earlier compile. The repair does not need to know: regenerating the file replaces it wholesale, so either origin is cleared by the same delete, recompile and download sequence.

Can I copy a working PDATA.FWX from an identical panel instead of recompiling?

No. A generated runtime file belongs to one compiled project on one target. Swapping copies between panels is not a supported recovery, and a copy from another panel can carry startup configuration that no longer matches this project's compile. Copy the project archive instead, open it in the engineering tool, compile and download — slower by minutes, correct by construction.

Does this error stop the PLC or the running process?

No. The termination in the message is the HMI application ending itself, not a controller command. The PLC keeps running its loaded program; what you lose is operator visibility and control from that panel until the application starts again. That blind window is why the rebuild and redownload belong at a planned stop rather than in the middle of production.

Keep reading

  • Troubleshooting

    HMI Project Opens With a Repeating Error Popup: Isolate It

    A repeating error popup that returns after you close it is a project-open fault, not a crash. Record the exact file the message names, open the unchanged project on a second PC, then remove only that file from a diagnostic copy. If the copy opens, that file carries the defect; if it still fails, build a new project and copy the file in.

    HMI and touchscreens

  • How-to

    Fixing a WinCC PC station download comms error from TIA Portal V13

    When TIA Portal V13 compiles but the download to a WinCC PC station fails, the transfer channel to the runtime loader is broken while the HMI itself is healthy. Compile to file, copy the .hmi PData file to the path shown in the WinCC Runtime Loader settings, restart runtime from the loader, then align the firewall, channel settings and PC station IP to restore normal downloads.

    HMI and touchscreens

  • Troubleshooting

    Why HMI USB Downloads Fail and Touch Stops Responding

    A panel that drops USB downloads, shows question marks on numeric tags and ignores touches is usually not broken: fix the data cable, the selected COM port and the PC software installation first, and treat read-only PLC tags as a button write-action fault. In the reported case a clean reinstall restored downloads and cleared the display.

    HMI and touchscreens