IMDTouchKnowledge BaseShop main store

Explainer

Why the unit and format pattern are missing from a Unified I/O field

HMI and touchscreens Published 5 min read

Short answer

WinCC Unified has no separate Format pattern or Unit property for an I/O field: both live in the single Output format parameter, entered as one literal pattern such as {I4} A. The grey shading you cannot remove belongs to the style's rendering template, so pick the Bright or Dark style or make the field background transparent.

On this page
  1. One parameter instead of two
  2. A worked example: integer plus unit
  3. Removing the shading: it belongs to the style
  4. Making the field background transparent
  5. Buttons follow the same rule
  6. The decision
  7. Questions asked

If you are migrating an I/O field from a KTP1200 Basic Panel to an MTP1000 Unified panel, the Format pattern and Unit properties you knew have not disappeared by accident: WinCC Unified merges both into a single Output format parameter under Properties > General. Enter one literal pattern, for example {I4} A for a four-digit integer followed by amperes, and the field renders the value and the unit together. The grey shading you cannot remove is not a property at all: it is drawn by the rendering template of the selected style, so you switch style or make the background transparent instead of hunting for a setting that does not exist.

One parameter instead of two #

On Basic and Comfort panels, the I/O field gives you a Format pattern in the General properties and a Unit field in Appearance. The documentation for WinCC Unified (RT Unified) defines output formatting under Properties > General > Output format for floating-point, binary and hexadecimal data, and there is no separate unit property listed beside it. Every output-format decision, pattern and unit alike, is written into that one field as a literal pattern.

This is the same display goal as the thousands-separator settings on classic TIA Portal output fields, reached through a different mechanism; the article on showing thousand separators in WinCC TIA Portal output fields covers that classic case.

A worked example: integer plus unit #

Take a tag that holds motor current as an integer and you want the panel to read 12 A.

  1. Select the I/O field and open Properties > General.
  2. In Output format, enter {I4} A. The {I4} part is the integer pattern with four positions; the space and the A are literals printed after the value.
  3. Download to the panel and display a known tag value of 12. The field shows 12 A.

Check the arithmetic of the pattern against the value: 12 is a two-digit integer, four positions are reserved, so the field left-pads or right-aligns within those four positions and then prints the literal space and A. If the tag value rises to 1200, all four positions are used and the field shows 1200 A; at 12000 the pattern is too narrow, so widen the position count in the pattern before commissioning rather than trusting the field to grow.

For a floating-point tag the same principle applies with the floating-point pattern form in the Output format field; write the decimals you want directly into the pattern instead of looking for a decimals property. The four display formats documented for RT Professional I/O fields do not carry over as separate settings on Unified targets.

Removing the shading: it belongs to the style #

In the documented V19 Update 3 environment, the shading inside an I/O field with the Extended style comes from the style's rendering template, and the exposed properties offer no way to switch it off. Rendering templates are files based on .svghmi technology that define the appearance of a style item in detail, and some of their parameters are not exposed for editing.

You have three working paths:

  • Switch the screen or project style to Bright or Dark. Neither applies that I/O field shading. Their other visual characteristics differ, so check the rest of the screen after the switch.
  • Make the field background transparent, which leaves only the value visible, as described below. This solves a white-background layout without changing the style.
  • Build your own style with the WinCC Unified Corporate Designer application, which creates custom styles and rendering templates; a Compatibility Style is also available for download there. This is the supported route when you need a corporate look across many screens.

Making the field background transparent #

To show only the value over a white screen background:

  1. Expand Appearance in the I/O field properties.
  2. Set the border width to 0.
  3. Open the background color selector and click More colors.
  4. Set Transparency to 100 percent.

The field now shows the number and nothing else. Verify on the panel, not only in the engineering view, because the rendering differences between styles are what caused the problem in the first place.

Buttons follow the same rule #

The same style mechanism constrains buttons: the base appearance is defined by the style and is not directly editable. If a screen needs a flat button, the common workaround is a rectangle styled with the fill you want, with its background color changed while it is pressed to give feedback. A rectangle has no built-in press feedback, so test the press behavior on the panel before deployment.

If the field is also refusing input rather than just looking wrong, that is a different fault; the article on a WinCC flexible IO field not editable on the panel covers the input-side checks for classic panels, and on Unified you additionally check the style and the operating-mode settings of the field.

The decision #

Migrating a KTP1200 screen to an MTP1000: write the unit into the Output format pattern ({I4} A reproduces the Basic Panel result) and do not search for a Unit property. Needing a plain value on a white background: set border width to 0 and background transparency to 100 percent. Needing to kill the Extended style shading project-wide: switch to Bright or Dark, or invest in a Corporate Designer style; do not attempt to remove it from the field properties, because the setting is not exposed in the documented versions.

For the number-format side of the same problem on classic WinCC panels, the guide to displaying thousand separators in WinCC V7.5 I/O fields shows the format pattern syntax those targets use, which is what the Unified Output format parameter replaces.

Questions asked

Where is the Unit setting for an I/O field in WinCC Unified?

There is no separate Unit property. Type the unit directly into the Output format parameter under Properties > General, after the format pattern. For an integer value shown in amperes, enter the pattern {I4} A, and the panel displays the value followed by the letter A in the same field.

How do I make a WinCC Unified I/O field fully transparent?

Under Properties > Appearance, set the border width to 0, open the background color selector, choose More colors, and set Transparency to 100 percent. Only the displayed value remains visible over the screen background, so a white background shows through the rest of the field.

Can I remove the shading of an I/O field with the Extended style?

Not through the exposed properties. The shading is drawn by the Extended style's rendering template and is not configurable in the documented versions. Switch the screen to the Bright or Dark style, which do not apply that shading, or build your own style in the Corporate Designer application.

Can I change the appearance of buttons in WinCC Unified?

A button's base appearance comes from its style and is not directly editable. For a flat look, engineers commonly substitute a rectangle with the required fill and change its background color while it is pressed to reproduce press feedback. Verify the press behavior before deployment, because a rectangle has no built-in button feedback.

How do thousands separators work in WinCC Unified compared with classic panels?

Classic panels use a separate format pattern with a decimal-point code, and Unified folds everything into the single Output format parameter. The way separators are written for classic TIA Portal output fields is covered in the linked guide, and the same display goal is reached in Unified by writing the pattern in the one Output format field.

Keep reading

  • Troubleshooting

    WinCC Flexible Migration Fails at 9% on Missing SQL Database

    A migration that stops at 9% with an SQL database message means TIA Portal could not open a database the WinCC flexible source project depends on. Read the Migration log, restore access to that exact database or remove the obsolete external connection in WinCC flexible 2008, then start Migrate project from the project level and rerun.

    HMI and touchscreens

  • Troubleshooting

    Why COROS COMED Rejects S5L Files Before a WinCC Migration

    The COMED error means the editor cannot decode the file's internal structure: the S5L lists came from another editor or COROS release, or were renamed. Open them in the COROS version that created them, then import through the WinCC Dynamic Wizards, reconciling every variable against the recovered source count.

    HMI and touchscreens

  • How-to

    Showing Thousand Separators in WinCC TIA Portal Output Fields

    Digit grouping in a WinCC output field is presentation only: set it in the field's format pattern in TIA Portal when the target supports one, otherwise in the target runtime's regional settings, and verify with a known value on the deployed panel or PC runtime. The PLC value stays unchanged.

    HMI and touchscreens