Troubleshooting
Why the USB Tethering Status Word Stays at 0 on an HMI
Short answer
Check LW-11381, the USB tethering status word — 0 no device, 1 disconnected, 2 connected, 3 fail, 4 OS not supported, 5 HMI not supported — instead of LW-11379, which proves nothing. When LW-11381 reads 1, write 1 to LW-11380 to start the connection; write 0 to stop. A dongle shown as compatible in EasyBuilder Pro can still fail on a different hardware or firmware revision, so prove each unit and revision.
On this page
- Why does LW-11379 stay at 0 when I plug in the dongle?
- What does LW-11381 report about the dongle?
- How do I start the tethering connection from the HMI?
- Example: two dongles fail on two panels while one phone connects — what does that prove?
- Why does a dongle the compatibility list accepts still fail?
- Where is the supported-dongle list?
- How do I verify the connection end to end?
- Questions asked
A USB stick that never comes up on a cMT panel is easy to diagnose against the wrong word. In the reported case LW-11379 sat at 0 and nothing changed it, but the USB tethering feature does not report through that word at all: it documents LW-11381 as its connection-status word and LW-11380 as the word that starts and stops the connection. Read the status first, because each of its codes sends you down a different branch — a recognized device just needs the start command, a no-device read is a detection or compatibility problem, and a not-supported code means the combination itself is out. Even a stick shown as compatible in EasyBuilder Pro can fail on a different hardware or firmware revision, which is exactly what happened when a listed-compatible model failed on two panels while an Android phone connected on both.
Why does LW-11379 stay at 0 when I plug in the dongle? #
LW-11379 is not the word that reports USB tethering, so its 0 tells you nothing about the dongle; read LW-11381, the tethering connection status, and use LW-11380 to start or stop the connection.
The tethering feature is driven by two 16-bit system words documented for it: a command word that takes the stop or start value, and a status word that reports the connection state. Read both in an online monitor or data table before you touch any screen object, because that separates a device-state problem from a display problem in one step.
- The status word changes but your screen does not: the device state is reaching the system word, so the object is bound to the wrong address or word length — re-check what it references, including the word that sat at 0 in the reported case.
- The status word sits on its no-device code even with the phone plugged in and USB tethering switched on at the phone: the panel is not seeing a tethering-capable interface, so work through the cable, the phone's setting and the device's operating mode.
- The status word stays on its disconnected code after you command the start: confirm the write to the command word actually issued, then watch which way the state tips — into connected, or into the failure code that points back at mode and firmware.
What does LW-11381 report about the dongle? #
LW-11381 is a 16-bit connection-status word whose six documented codes run from 0 for no device detected to 5 for an HMI that lacks the tethering feature, and each code points to a different next check.
| Code | Meaning | Next move |
|---|---|---|
| 0 | No device detected | Cable, power and operating mode; the start command cannot help here |
| 1 | Device recognized, not yet connected | Write 1 to LW-11380 to start the connection |
| 2 | Connected | Leave the tethering words alone and test the remote session |
| 3 | Connection attempt failed | Device mode and firmware first, then one retry |
| 4 | Device OS not supported | The device class is out; pick another from the supported list |
| 5 | HMI model not supported | The panel lacks the function; confirm the model's feature support |
Treat any read above 5 as a binding fault rather than a device state: the word is defined only for those six states, so a stray value means the object is looking at the wrong address or displaying a different word.
How do I start the tethering connection from the HMI? #
When LW-11381 reads 1, write 1 to LW-11380 to start the USB tethering connection, then read LW-11381 again: 2 means connected and 3 means the attempt failed.
- Connect the device and switch USB tethering on at the device itself — on an Android phone that is the tethering setting, not the file-transfer mode.
- Open LW-11381 in an online monitor and confirm it holds the disconnected code, the recognized-but-not-started state.
- Write 1 to LW-11380, the start value.
- Read LW-11381 again: connected confirms the link; the failure code sends you back to device mode and firmware.
- To close the link later, write 0 to the command word.
If the status word never leaves its no-device code, repeating the start command achieves nothing: the command acts only on a device the panel has already recognized.
Example: two dongles fail on two panels while one phone connects — what does that prove? #
Score the trial as four devices against two panel models: the listed-compatible E3372H went 0 for 2, the MF79N went 0 for 1, the DWM-222 went 1 for 1, and the Android phone went 2 for 2, which puts the fault on the device side of the cable.
| Reported outcome | MT8071iE | cMT2078X | Score |
|---|---|---|---|
| Huawei E3372H, listed as compatible | No connection | No connection | 0/2 |
| ZTE MF79N, tried in modem and tethering mode | Not tried | No connection in either mode | 0/1 |
| D-Link DWM-222 | Not tried | Connected | 1/1 |
| Android phone, same project on both | Connected | Connected | 2/2 |
Add the scores: the phone passes 2 of 2 panels, the listed-compatible E3372H passes 0 of 2, and 2 of the 3 dongle models fail outright. Two panels and one project that pass a 2/2 control are not the fault, so the failure travels with the devices on the far side of the cable. The decision follows: keep the panels and the project, and work the stick — update its firmware, put it in tethering mode, or substitute a unit taken straight from the supported list — while keeping the phone as the known-good control for every later trial.
Why does a dongle the compatibility list accepts still fail? #
A listed model number is a starting point, not a per-unit guarantee, because vendors keep the model code while shipping new hardware and firmware revisions, and the E3372H was reported failing on two different panels even though the list showed it compatible.
A stick keeps its model number across updates that change how it behaves, so the list answers whether the model exists in a compatible form, not whether the unit in your hand is one of them. The phone test from the example is what separates the two.
- Read the stick's hardware and firmware revision from its device information and compare it with the manufacturer's notes before trusting a listing.
- Update the stick to its current firmware; a D-Link DWM-222 was reported working as tethering once it ran the latest firmware, which is the mode the HMI's words expect.
- Determine which interface the stick presents to the panel; the tethering words drive a tethering-mode device, not one that powers up as a modem.
- Re-run the phone test after every change so you always know the panel side still works.
Where is the supported-dongle list? #
EasyBuilder Pro carries the supported-dongle list, so open the program and look there before buying or deploying a stick, then treat any hit as a candidate to prove on your panel and revision.
The list is the compatibility starting point, not a bench result, so budget a trial on the actual panel before the stick is specified into a project. One integrator also reported fewer surprises sourcing sticks and SIMs locally for installations in the US — a purchasing observation from one shop, not a compatibility rule.
How do I verify the connection end to end? #
Status 2 on LW-11381 proves only the USB link between the panel and the device, so test the remote session from its own client next and check cellular signal at the cabinet before touching the tethering words again.
Because a cellular link puts the panel on the public network side, keep it behind the same firewall and VPN rules as the rest of your remote-access path.
- No-device code with the stick attached: stay on detection and compatibility — mode, firmware, supported list — because the command word cannot act on an unrecognized device.
- OS-not-supported or HMI-not-supported code: the combination itself is out, so change the device class or confirm the feature on that panel model.
- Failure code after a start: do the firmware and mode work, then retry once.
- Connected code but a dead session: the USB link is proven and the fault is downstream — signal at the cabinet, or the remote-access configuration. When the machine link is healthy but remote access still misbehaves, work through why HMI remote access fails while PLC access still works before editing the tethering words.
Prove the branch you land on once at the desk, with the real stick, the real panel and a monitored status word, before the combination goes into a live cabinet.
Questions asked
Will supported dongles also work on an MT-series panel?
The dongle list is the same starting reference, but each panel family implements tethering in its own way, so treat model support as a separate check. A panel without the feature reports the HMI-not-supported status code, which is the quickest tell you can get: if that code appears, stop swapping sticks and confirm the feature on the exact model first.
Why does an Android phone tether when the stick will not?
The phone presents the USB tethering interface the panel's tethering words are built for, while many sticks power up as a modem that expects a cellular command set instead. Current stick firmware can add a tethering mode, which puts the stick on the same path as the phone; in modem mode the tethering status and command words never move at all.
How do I close the tethering connection cleanly?
Write 0 to the command word that starts the link with 1, then read the status word back to confirm the link dropped. Keep command and status displays separate in the project: an object bound to the command word shows only the last value written to it, so a healthy link can look dead on a screen that is really showing the command.
Can a connected status coexist with a useless remote session?
Yes. The status word describes only the link between panel and device, and signal quality at the cabinet decides the rest. One reported installation had a D-Link DWM-222 connecting correctly while delivering poor reception, so the link came up and the session stayed weak. If the status holds but sessions crawl or drop, chase coverage and antenna position before touching the project.