IMDTouchKnowledge BaseShop main store

Troubleshooting

Why TIA Portal V13 Keeps Reprompting for the Online Access Card

HMI and touchscreens Published 7 min read

Short answer

The prompt repeats because TCP/IP(AUTO) on a DHCP-assigned adapter lets the PG/PC access point re-bind after every tool switch. Set a static IP on the plant adapter, bind the access point to plain TCP/IP, and store the per-device path in Online & Diagnostics so SCOUT TIA and WinCC share one stable route.

On this page
  1. Why does the prompt come back after every switch between SCOUT and WinCC?
  2. Should I use TCP/IP or TCP/IP(AUTO) on the PG/PC interface?
  3. Should the engineering station get a static IP or DHCP?
  4. Which access point should the device use, S7ONLINE or DEVICE?
  5. How do I store the online path per device in Online & Diagnostics?
  6. What is the step-by-step fix for the repeating prompt?
  7. What else should I check if the prompt still appears?
  8. Questions asked

If TIA Portal V13 SP1 asks you to select the network card and browse for accessible devices every time you switch between SCOUT TIA and a WinCC download, the cause is almost always TCP/IP(AUTO) on a DHCP-assigned Ethernet adapter. Fix it by setting a static IP on the plant adapter, binding the access point to plain TCP/IP, and storing the per-device path in Online & Diagnostics. The dialog is not a bug in your project: it is TIA re-resolving the online route each time another tool releases it.

Why does the prompt come back after every switch between SCOUT and WinCC? #

Each tool takes the online reservation, and when it releases it, the PG/PC access point has to resolve the route again. With TCP/IP(AUTO), that re-resolution can land on a different adapter, and TIA Portal treats the change as a new topology, so it shows the adapter selection and the accessible-devices browse dialog. A fixed adapter with plain TCP/IP rebuilds the same route every time, so no dialog appears.

Three conditions together reproduce what you are seeing:

  • TCP/IP(AUTO) selected on the PG/PC interface. The Auto entry exists to find controllers when no project topology is loaded, but on a station with more than one NIC (office LAN, plant LAN, Wi-Fi) it silently follows the Windows IP stack. TIA Portal V13 SP1 then treats the switch as a topology change.
  • A DHCP-assigned plant adapter. When the lease renews between sessions, the address the stored assignment refers to is gone, so the access point falls back to the browse dialog. Setting a static address removes that state change.
  • An access point mismatch. If the device's online properties still point at S7ONLINE while SCOUT TIA uses the per-device configuration, the project-stored path is not honored and the adapter is queried again.

Any one of the three can bring the prompt back; together they make it appear on every download.

Should I use TCP/IP or TCP/IP(AUTO) on the PG/PC interface? #

Use plain TCP/IP on a commissioned machine. In the Set PG/PC Interface tool, under Used interface parameterization, select the Ethernet adapter entry that ends in . TCPIP . Auto .1 only when you are searching for an unconfigured device; for normal operation pick the adapter bound to a fixed address and the TCP/IP protocol, not the Auto variant. Plain TCP/IP binds to the configured adapter address and gives a predictable path; the Auto variant can follow whichever adapter the IP stack offers, which is exactly the behavior that re-prompts.

The trade-off is discoverability: TCP/IP(AUTO) will find a controller whose address you do not know, at the cost of stability. Once addresses are set, take the Auto entry out of the working configuration and leave it for initial commissioning.

Should the engineering station get a static IP or DHCP? #

Give the plant Ethernet adapter a static address in the same subnet as the SIMOTION and HMI devices, outside the DHCP pool. Set it through the adapter's IPv4 properties, then confirm with ipconfig /all in a command prompt. For example, if the SIMOTION sits at 192.168.0.20 with a 255.255.255.0 mask, assign the station 192.168.0.10 with the same mask, and enter a resolver address only if your plant network needs one.

What moves the decision is whether the adapter also serves the office network. If it must, add a second adapter for the plant subnet rather than sharing one DHCP-addressed card between both roles; the second fixed-address card removes the ambiguity that TCP/IP(AUTO) exploits. A refresh script that releases and renews the lease restores a lost connection for one session but does not stop the next prompt, because a renewed lease is itself the state change TIA reacts to.

Which access point should the device use, S7ONLINE or DEVICE? #

Set the access point to DEVICE on each SIMOTION, CPU and HMI object in the project. If a device still shows S7ONLINE, TIA Portal ignores the per-device online access you configured and re-queries the adapter instead, which is one of the three conditions that bring the prompt back. Open the device in the project tree, open its online properties, and change the access point for the interface you actually use; repeat for every device on the plant subnet. You only need to do this once per project, and it persists in the project file.

How do I store the online path per device in Online & Diagnostics? #

Right-click the device in the project navigation, open Online & Diagnostics, and configure the Online access entry: connection type TCP/IP, the static plant adapter as the interface, the PROFINET subnet, and the device's own address. For a SIMOTION at 192.168.0.20 you would enter that address as the target and select the subnet the station adapter belongs to. Once stored, the path is reused on every Go online and is shared between SCOUT TIA and the WinCC editor, so neither tool has to rediscover it.

Do the same on the HMI's communication settings so a WinCC Basic Panel download uses the stored route too. For the WinCC side of the configuration, the article on fixing WinCC runtime that connects to the PLC only through TIA Portal covers how the runtime resolves its route to the controller.

What is the step-by-step fix for the repeating prompt? #

Apply the four steps in this order; each one is independently verifiable.

  1. Set a static IP on the plant adapter. Adapter properties, IPv4, use the following address: 192.168.0.10 with mask 255.255.255.0 as an example, matching the machine subnet and outside the DHCP pool. Verify with ipconfig /all.
  2. Bind the access points to plain TCP/IP. In Set PG/PC Interface, assign both access points to the static plant adapter with the TCP/IP protocol. Do not leave either on the Auto variant.
  3. Set DEVICE on every device. In each device's online properties, change the access point from S7ONLINE to DEVICE for the interface in use.
  4. Store the per-device path. In Online & Diagnostics on each SIMOTION, CPU and HMI, set connection type TCP/IP, the static adapter, the subnet and the device address.

Then verify: go online to the SIMOTION from SCOUT, disconnect, download software to the Basic Panel from WinCC, and return to SCOUT. With all four steps in place, SCOUT reconnects without the adapter dialog. Repeat the alternation a few times; the route now rebuilds identically because nothing about the adapter or the access point changes between tools. If an upload from the panel itself still fails after the path is stable, the article on why an Ethernet project upload from an HMI panel keeps failing covers the transfer-side causes.

What else should I check if the prompt still appears? #

Disable every adapter except the plant Ethernet card. Wi-Fi dropping in and out, or a second NIC changing state, is seen by TCP/IP(AUTO) as an adapter change even mid-session. If the prompts stop with the other adapters off, the re-binding was the cause and the static configuration above will hold. On Windows 7 stations the wireless state change is a known trigger; the permanent answer is the same fixed adapter, not a workaround script.

Also confirm all devices on the subnet carry the same adapter type, adapter and subnet settings in their online access entries, and that the panel and controller addresses sit in the same subnet as the station. If a device keeps a stale configuration after a download, the behavior described in the article on PanelView keeping an old configuration after download is a different platform, but the same principle applies: the runtime uses the configuration loaded on the device, not the one you think you downloaded.

Safety note: when you assign the static address, take it from a range agreed with whoever runs the plant network, so you do not collide with an address the DHCP pool may hand to another device.

The decision, case by case: a single-NIC station on one plant subnet, take a static address, plain TCP/IP and DEVICE on every device, and the prompts stop. A multi-NIC or Wi-Fi-equipped station, add a dedicated fixed-address plant adapter before applying the same four steps. Initial commissioning of unknown devices, use the Auto variant to find them once, then switch the configuration to plain TCP/IP before the machine runs.

Questions asked

Does disabling the Wi-Fi adapter on the engineering station help stop the prompts?

Yes, and it is the fastest test. TCP/IP(AUTO) re-binds to whichever adapter the Windows IP stack offers, and a Wi-Fi connection dropping in or out counts as an adapter change. If the prompt stops appearing, the re-binding was the cause and the permanent fix below will hold.

Where does the DEVICE access point get set on the CPU?

Open the device in the TIA Portal project tree, open its online properties, and look at the access point field for the interface you use. If it shows S7ONLINE, the CPU ignores the per-device online access stored in the project and queries Windows again. Change it to DEVICE for each SIMOTION, CPU and HMI in the project, then verify with one Go online.

Can a batch file that releases and renews the IP fix this between downloads?

No, it only masks the symptom for one session. A script that runs ipconfig /release and then ipconfig /renew gives the adapter a fresh lease, which is exactly the state change that makes TCP/IP(AUTO) re-prompt. It is useful as a diagnostic to prove the lease is the trigger, but the durable fix is a static address outside the DHCP pool.

Why does the prompt only appear when I alternate between SCOUT and WinCC?

Each tool takes and releases the online reservation in turn, and each release tears down the route the PG/PC interface resolved last time. With a fixed adapter and plain TCP/IP, the route is rebuilt identically every time and no browse dialog appears. With TCP/IP(AUTO), the rebuild can land on a different adapter, so the dialog returns after every switch.

Keep reading

  • Troubleshooting

    Fix WinCC Runtime That Connects to the PLC Only via TIA Portal

    The runtime PC's PG/PC interface is bound to the wrong network adapter, so WinCC Runtime has no path of its own until a TIA Portal online session brings one up. Open Set PG/PC Interface in Windows Control Panel, assign the PLC-facing adapter to the S7 access point, restart the runtime, and confirm with ping plus a live tag. If ping already works, check the access point, the connection configuration, and PLC access permissions instead.

    HMI and touchscreens

  • How-to

    Run WinCC 7.0 PC Runtime over a PROFIBUS card

    No panel-versus-PC switch exists: launch WinCC Runtime on the PC, but the PROFIBUS link only works after the card driver is installed, the PC interface points at that card, and the WinCC connection carries the PLC's station address, rack and slot — then a moving tag value proves the link.

    HMI and touchscreens

  • Troubleshooting

    WinCC flexible Runtime shows ### on a copied target PC

    ### on a copied target PC means Runtime's S7 connection never opened; a passing ping proves IP reachability only. Open Set PG/PC Interface on the target PC, select the S7ONLINE (STEP 7) access point and bind it to the adapter wired to the S7-300. If the adapter list is empty, reinstall WinCC flexible Runtime from licensed media.

    HMI and touchscreens