Why WinCC Professional Images Turn White in Runtime
Short answer
Images that keep their color in the editor but turn white in WinCC Runtime and Simulation, and images that break after the project moves to another path, are both symptoms of a stale or external image-resource association inside the project. Reimport each failing image through the project's own graphics management, then verify it in the editor, Simulation, Runtime and after relocation.
On this page
The white picture is not a communication fault, and the PLC is not involved. The failing image objects point at a graphics-file association that is stale or resolves only outside the project, so Runtime and Simulation cannot load what the editor still previews in the drawn color. The fix is to reimport each failing image through the project's own graphics management, confirm the file is stored inside the project, and verify the result in the editor, in Simulation, in Runtime, and once after the project has moved to another path.
What the two symptoms isolate #
The reported case carries two independent observations, and each narrows the fault:
- Some pasted copies of one picture render white in Runtime and Simulation while the editor keeps the drawn color. Every copy came from one file on disk, so the difference between copies sits in each object's own resource association, not in the file and not in the connection.
- Graphics break when the project is reopened from a different path. An association that survives only at one path is a dependency on where the project or the source file sits, which is content living outside the project.
Both observations land on the image resource. Neither touches tag values, the driver or the runtime itself.
Rule out the environment first #
The case already excludes the environment causes, and the documented baselines make that explicit rather than assumed:
- Operation was confirmed against the S7-1500 CPU, so the driver is not the suspect. If live values had frozen as well, WinCC Professional runtime not connecting to the S7-1500 would be the fault domain instead.
- Runtime and Simulation start and render screens, which puts the workstation past their documented gates: TIA Portal V16 lists a minimum of 8 GB RAM with 16 GB recommended for simulation, and on V13 the runtime is a separate, licensed install from the engineering system — the WinCC V13 Professional runtime command staying disabled is exactly that split.
- A flat white render of specific pictures is not the pattern of white boxes with red borders on populated pages; that is a different fault, and HMI objects showing white boxes only on populated pages covers it.
Why copies of the same picture fail differently #
A picture object does not carry pixels; it points at a graphics file registered for the project, and Runtime resolves the object through that association. Copying an object duplicates the association with it, so copies descended from a healthy instance render correctly and copies descended from an instance with a stale or external association render white. Correcting one instance repairs nothing else — each failing copy has to be repointed at a valid registered file.
The path-change breakage is the same fault seen from the other side: an association that resolves only while the project or the source file sits at one location is an external dependency, and registering the graphic inside the project removes it. A design-time reference that stops resolving at runtime is a general HMI failure class rather than a WinCC quirk — PLC symbol changes breaking SCADA tags in OFS is the same class of fault on the tag side.
The fix, step by step #
- Pick one failing copy and one healthy copy of the same picture. Compare their image, appearance, state and animation properties, and note which registered graphics file each points at.
- Import the source file again through the project's graphics management so the project registers its own copy, then point the failing object at the newly registered file. When the graphic uses transparency, the import decides whether the transparency survives, so apply the same care as importing HMI images with a transparent background.
- Run Simulation and Runtime from the current path and confirm the instance keeps its drawn color in both.
- Rename or move the folder holding the original file on disk, then run Runtime again. A graphic stored in the project still renders; a white render here means an external reference is still in play and step 2 did not take.
- Move or copy the project to its intended path, reopen it and confirm the graphic is intact, then apply the same reimport to the remaining failing copies.
Working the case: one blue logo, several white copies, one moved project #
The inputs, each from the reported case:
- A picture loaded from the computer and pasted as several copies across the screens.
- Some copies white in Runtime and Simulation while the editor shows the drawn blue.
- Graphics breaking after the project is reopened from a different path.
The rule in words: an instance counts as fixed only when it holds its drawn color in the editor, in Simulation, in Runtime, and after the project has been reopened from the new path — four conditions, all required before anything scales.
The arithmetic written out: checks for the test instance = 1 (editor) + 1 (Simulation) + 1 (Runtime) + 1 (reopened from the new path) = 4. With F failing copies on the screens, the full verification costs 4 + (F − 1) checks: four on the first instance, then one Runtime check on each remaining copy. Count the white copies and apply the formula to your own screens.
The decision: four correct renders mean the association was the fault — reimport the remaining F − 1 copies and give each its Runtime check. Any white render at any of the four stops the rollout, because more reimports will not change that result.
Verification and escalation #
Accept the correction when the test instance passes all four conditions and every remaining copy passes its Runtime check. If a reimported instance still turns white, stop and collect the set that separates a project fault from a version-specific product issue: the exact TIA Portal and WinCC Professional versions, the image file format, whether the graphic uses transparency, whether the file is stored in the project or referenced externally, and the healthy-versus-failing property comparison from step 1. That package is what a support case needs, and nothing in it can be skipped.
Questions asked
Why do only some copies of the same picture turn white?
A pasted image object carries the resource association of the object it was copied from, not the pixels of the file on disk. Copies descended from a healthy instance render correctly; copies descended from a weak association render white. Pasting from the desktop again can recreate the same weak association, which is why the reimport goes through the project's graphics management and each failing copy is repointed individually.
Should I fix the path-change breakage by putting the file back at its old location?
That makes the picture render again on that one machine, but it reinstates the dependency that broke on relocation, and the next move or the next computer breaks it the same way. The durable fix registers the graphic inside the project. Prove it by renaming the source folder and running Runtime: a project-stored graphic survives, an external reference turns white.
Could the white images be a licensing or PC problem?
Only if Runtime or Simulation refuses to start or the whole runtime deactivates. The documented gates are real: TIA Portal V16 asks for at least 8 GB RAM with 16 GB recommended for simulation, and on V13 Runtime is a separate licensed install from Engineering. Your runtime and simulation start and render screens, so those causes are excluded and the fault sits in the image resource.
What do I do if reimporting does not fix the image?
Treat one reimported instance as the whole experiment. If it fails any of the four checks, more reimports will not change the result: stop, leave the remaining copies as they are, and collect the versions, the file format, the transparency setting, the storage method and the healthy-versus-failing property comparison for support. That set is what separates a project fault from a version-specific issue.
Do report printouts use the same graphics?
Report printing in WinCC RT Professional has its own documented failure in which images added through standard methods do not print. The first corrective move is the same one: register the graphic through the project and confirm it on screen and in a test printout before relying on report logos and icons.