Why WinCC Unified Login Autofill Ignores Edge Settings

HMI and touchscreens Published 6 min read

Short answer

The login dialog runs in Station Configurator's embedded Chromium browser, which keeps its own saved form data, so Edge's clear-on-close setting never reaches it. Clear or disable auto-fill from the embedded browser's own "…" menu where the version provides it; where it does not, contain the station with the documented kiosk-mode lockdown.

On this page
  1. Where the saved user name actually lives
  2. The documented clear path in the embedded browser
  3. What these settings actually govern
  4. Six checks that settle it
  5. Lock the station when the clear function is absent
  6. The decision, case by case
  7. Questions asked

The User field keeps its suggestion because the login dialog is not rendered by the Edge window on the taskbar. The PC runtime that Station Configurator launches uses an embedded, Edge-based browser, and that surface keeps its saved form data in a profile of its own. Turning off Windows and Edge data collection and switching on Edge's clear-on-close cleaned the manually opened Edge window and left the Station Configurator suggestion in place, which is exactly what two separate stores produce. Clear or disable auto-fill from the embedded browser's own "…" menu where your version provides it, prove the result with the six checks below, and where the build exposes no clear function, contain the station with the documented kiosk-mode lockdown instead of more Edge settings.

Where the saved user name actually lives #

A form suggestion is browser-managed form data: the browser recognizes the field and offers a previous entry. It is not a saved password and it is not browsing history, which is why history and telemetry settings leave it untouched. In the reported V20 case the user name came back while the password never did, so two fields, two stores, one retaining.

Two browser surfaces exist on this station:

  • The Edge window you launch manually, governed by your Edge profile settings.
  • The Station Configurator runtime surface, described as Edge-based, with a profile of its own.

A clean field in one proves nothing about the other. The prompt's language is a third confirmation: it followed the system language rather than the Edge language setting, because the embedded surface takes its locale from Windows. Identify the store by the field's behavior, never by the prompt's language or appearance.

This article is about the PC runtime station Station Configurator launches; where that runtime should run in the first place, including remote options, is a separate choice covered in where WinCC Unified runtime can run and its remote options.

The documented clear path in the embedded browser #

Siemens documents the procedure for RT Unified under the title "Disable auto-fill and clear cookies and web cache (RT Unified)" in the Station Configurator documentation, V21:

  1. In the Station Configurator window, click "…" in the browser bar, not in a manually opened Edge window.
  2. In "Settings", open "Privacy, search and services" > "Clear browsing data" > "Choose what to clear every time you close the browser".
  3. Include the saved-form-data (auto-fill) category in what is cleared on close, so the User field stops being offered after each session close.

For a one-time clear, the same menus open a "Clear browsing data" window where you choose the categories yourself. The WinCC Unified notes on use describe leaving every option off except the one you mean to remove, with an example that keeps only "Cached images and files", then clicking "Clear data". For login data, invert that example: select the saved-form-data item and leave the rest off.

Whether your build gives you this menu is observable in one click. If "…" in the Station Configurator window opens "Settings", the path above applies. If it does not, no built-in clear function has been reported for that surface: a V19 station exposed none, not even through Windows app management, and the V20 case was not resolved from the Edge side. The one mistake to avoid is running Edge's menu steps and calling the embedded profile clean.

What these settings actually govern #

Setting you changed What it governs Effect on the login suggestion
Windows and Edge data-collection toggles Telemetry and diagnostics collection None
Edge "Clear browsing data on close" The manually opened Edge profile None; this is the reported V20 result
"Keep current user management data in runtime", under "Runtime values" Whether the runtime keeps the currently logged-in user across runtime restarts None; deselect it to force a fresh login after restart
Desktop PIN in the Station Configurator web interface Desktop access at the station None; an access restriction, not a data clear

"Keep current user management data in runtime" is the runtime layer, not the browser layer: while it is set, a runtime restart does not end the session. Deselect it under "Runtime values" when the station must come up unauthenticated, and expect the User-field suggestion to survive, because it lives in the embedded profile.

Six checks that settle it #

Do this on a bench runtime with a test account, never a production credential for an auto-fill test. Enter a throwaway name once, for example autofill_test_01, and reproduce the suggestion before changing anything.

The arithmetic: 2 browser surfaces x 2 login fields = 4 data checks, plus 2 operating-system escape paths = 6 checks in total. The station passes at 6 of 6, and every miss names the layer that still needs work.

  1. Embedded surface, User field, after a full runtime restart (close and reopen, not just logoff): the test name is not offered.
  2. Embedded surface, password field: nothing offered. The reported condition retained the user name only; any password suggestion is a separate credential-storage finding.
  3. Manual Edge window, User field of any login form: clean, recorded to document the separation between the two stores.
  4. Manual Edge window, password field: clean.
  5. USB path, with lockdown applied: the "New USB device inserted" notification appears but File Explorer does not open.
  6. Screen keyboard, with lockdown applied: the Settings button does not reach Windows settings.

Checks 5 and 6 verify the containment boundary, not the data clear. Record auto-fill and lockdown as two separate results, so a later change to one cannot hide a regression in the other.

Lock the station when the clear function is absent #

If the embedded surface exposes no "…" settings menu, stop treating Edge cleanup as the fix; the decision is containment. Two layers, in the order reported to work on this platform:

  • Desktop access: a PIN configured in the Station Configurator web interface restricts the desktop. Useful, incomplete, and it does not touch the suggestion.
  • Operating-system access: the Station Configurator V20 documentation page "Block access to the operating system for kiosk mode" covers closing the paths that survive a desktop restriction, including the "New USB device inserted" notification that opens File Explorer and the Settings button on the screen keyboard, with registry-based controls. Windows Kiosk mode is the reported practical choice for blocking other applications without shell commands and with more configuration flexibility.

Make lockdown changes on the bench with a local administrator account you can still reach, because an over-restrictive kiosk configuration locks you out as effectively as it locks out the operator.

The decision, case by case #

  1. The "…" menu in the Station Configurator window opens "Settings": apply the documented clear-on-close with the auto-fill category included, run the six checks, and ship at 6 of 6.
  2. V20 station without that menu: no built-in clear is reported. Configure the documented kiosk-mode operating-system blocking, pass checks 5 and 6, and record the suggestion as accepted until remediation.
  3. V19 station: same decision, because no cleanup function was reported there either, not even from Windows app management.
  4. Audit forbids any persisted operator name on the station: lockdown now, plus a plan to bring the station to a version whose documentation includes the auto-fill procedure; V21 documents it.
  5. The station must also start unauthenticated: additionally deselect "Keep current user management data in runtime" under "Runtime values".

Questions asked

Does the saved User-field suggestion mean the password is stored too?

No. In the reported case the user name was offered and the password was not; they are separate stores. Test each field on its own after a full runtime restart. A project download does not help either: it erases the runtime's local user-management database (the UMC database), not the embedded browser's saved form data. If a password field ever offers a stored value, treat that as its own credential-storage finding.

Why does the autofill prompt appear in the wrong language?

The embedded browser takes its display language from Windows, not from Edge's language setting, so the prompt follows the system language, which is also a quick way to tell which surface you are looking at. No Edge language change will govern it. Change the Windows display language only if the station's operator language requires it; judge the retention problem by the field's behavior.

Should I switch off 'Keep current user management data in runtime' to stop the suggestions?

No, that checkbox is the runtime layer, not the browser layer. While it is set, the runtime keeps the currently logged-in user across runtime restarts; deselecting it under 'Runtime values' makes the station come up unauthenticated after a restart. The User-field suggestion lives in the embedded browser profile and survives the change, so use it for fresh-login requirements, not for clearing form data.

Is the desktop PIN in Station Configurator the same as kiosk mode?

No. The PIN configured in the Station Configurator web interface restricts desktop access, but the 'New USB device inserted' notification still opens File Explorer and the Settings button on the screen keyboard still reaches Windows settings. The documented containment for those paths is the kiosk-mode operating-system blocking in the Station Configurator V20 documentation; Windows Kiosk mode is the reported practical choice for blocking other applications.

Will upgrading remove the saved login data by itself?

Do not count on it as an automatic cleanup. What the upgrade buys is the documented procedure: the auto-fill clear-and-disable path appears in the V21 Station Configurator documentation for RT Unified, while no built-in clear was reported on V19 and none was found from the Edge side on V20. After any upgrade, run the embedded-field checks before declaring the station clean.

Keep reading

  • Selection guide

    Where WinCC Unified Runtime Can Run and Remote HMI Options

    The Unified runtime executes only on a PC, a Panel IPC, a Unified Comfort Panel or the MD-34 tablet; a browser or Sm@rtServer VNC client displays it and never replaces the host. With no PC in the cabinet, a Unified Comfort Panel is the host and the tablet browser is the client. If a safety function must travel with the operator, no Unified mobile panel exists and the design stays Comfort-based.

    HMI and touchscreens

  • Troubleshooting

    Create a desktop shortcut for WinCC Runtime Advanced

    The .fwx prompt means the shortcut starts the runtime executable with no project attached. Start runtime once from the engineering software so the HMI subfolder receives the generated runtime file and a working runtime shortcut, then copy that shortcut's Target into your desktop shortcut. Verify the same runtime release and license exist on any other computer before copying it there.

    HMI and touchscreens

  • Troubleshooting

    How to Recover a WinCC On-Screen Keyboard Placed Off-Screen

    Set PosLeft, PosTop, PosRight and PosBottom to 0 under the Windows account that runs the HMI, then restart Windows: the keyboard reopens at a sensible default. The values live under HKEY_CURRENT_USER\SOFTWARE\Siemens\SimaticHmiIM on a documented WinCC V17 station, but the subkey varies, so search for PosLeft under HKCU\SOFTWARE\Siemens when the key is not there.