Why WinCC Unified screen titles mix up between clients

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

The mixed titles come from one shared internal tag: every client session reads and writes the same stored value, so the last client to change screens sets the title everywhere. Set the tag's Scope to Local session in the HMI tag table, load the project and start fresh sessions; each client then keeps its own title. Keep shared scope only for values that describe the plant rather than the viewer.

On this page
  1. Why do WinCC Unified screen titles mix up between clients?
  2. How do you prove the titles run through one shared tag?
  3. Where do you set an internal tag to Local session?
  4. Do you reload the runtime and restart clients after the change?
  5. When must a title tag stay shared across sessions?
  6. How do you verify each client keeps its own title?
  7. Which mistakes bring the mixed titles back?
  8. Questions asked

Mixed-up screen titles on WinCC Unified clients come from one shared internal tag: every client session reads and writes the same stored value, so the last client to change screens overwrites the title on all of them. The fix is a single property. In the HMI tag table, set the title tag's Scope column to "Local session" and each client session then holds its own copy of the value. The sections below give the mechanism, the two-client test that proves it, where the setting lives, when a tag must stay shared, and the acceptance checks.

Why do WinCC Unified screen titles mix up between clients? #

The titles mix up because the internal tag behind them has shared scope: all client sessions read and write a single stored value, so whichever client writes last sets the title that every client displays. An internal tag keeps its value in the memory of the HMI device rather than reading it from a controller, and the scope property decides how many stored values exist for that one tag.

Worked example, one shared tag and two writers. Each screen writes its own name into the shared title tag when it opens. Client A opens its overview at 10:00:00 and the screen writes the example text Furnace 1 overview. Client B opens a detail screen at 10:00:05 and writes Filler detail into the same tag:

Time Event Stored value in the tag Title on client A Title on client B
10:00:00 A opens its overview, the screen writes the title Furnace 1 overview Furnace 1 overview Furnace 1 overview
10:00:05 B opens its detail screen, the screen writes the title Filler detail Filler detail Filler detail

Two writes went in and one value survives: the second write replaced the first, and both title objects read it. The pictures stay correct because each session draws its own screen; only the label, read from the shared tag, is wrong. That is why the fault shows up as mixed titles rather than as a navigation fault.

How do you prove the titles run through one shared tag? #

Run a two-client test: open different screens on two clients, change the screen on only one, and watch the other client's title; if that title changes too, both titles read one shared tag. Do it on the engineering bench or a quiet shift, with two runtime clients started from the same project:

  1. Open a different screen on client A and on client B, then note both titles.
  2. Leave B untouched and navigate A to a third screen.
  3. Read both titles again.

Three outcomes, three causes:

  • B's title changes although only A navigated: both titles read one shared tag. That is the scope fault, and the setting in the next section fixes it.
  • Only A shows a wrong title: the fault is in that screen's references, where the title object reads a different tag than the screen writes, and the method for diagnosing whether it is the driver, the tag or the screen applies.
  • B's visible screen changes as well: the navigation state itself is shared. A session-local title tag still fixes the label, but audit the navigation variables too.

Where do you set an internal tag to Local session? #

In the HMI tag table: display the Scope column and select the Local session entry in the title tag's row, which is a four-step change documented for Unified tags:

  1. Open the HMI tag table that holds the title tag.
  2. Display the "Scope" column if it is not shown.
  3. In the "Scope" column, on the title tag's row, select the "Local session" entry.
  4. The same property can also be set in the tag's Inspector; both places write the same setting, so use whichever is open.

The tag keeps its name, data type and connections; the scope only changes how many stored values the runtime keeps. Nothing needs rewiring, as long as every writer and every reader already use this one tag.

Do you reload the runtime and restart clients after the change? #

Yes: load the changed project to the runtime first, then start fresh client sessions for the test, so the result does not depend on state retained by sessions that predate the change. Scope is project data, and the runtime serves the new behavior only after the load; a session opened earlier does not prove the new path. In operation the same rule holds: sessions started after the download get the session-local behavior.

When must a title tag stay shared across sessions? #

Keep the tag shared when the value describes the plant rather than the viewer: machine mode, alarm status and controller-derived labels must read the same on every client. Decide by what the value represents, not by where it is displayed:

  • Viewer state, such as the screen this session is showing or the filter an operator picked, belongs to "Local session" scope.
  • Plant state, such as machine mode or alarm status, belongs to shared scope, and belongs in the controller when the PLC already holds it.

Do not make process data session-local just to silence conflicting writes; the clients would then display different copies of data that is supposed to be common. Sorting viewer-specific presentation state from plant state that belongs to everyone is the same decision behind how window titles stay local to each monitor in other HMI runtime software.

How do you verify each client keeps its own title? #

Pass five checks with two fresh sessions: independent initial titles, one-sided navigation, reversed write order, alternating navigation and a session restart, with no title ever crossing between the clients. After the load:

  1. Independent initial titles: open a different screen on each client; each title matches its own screen.
  2. One-sided navigation: navigate A while B stays idle; A's title changes and B's does not.
  3. Reversed write order: navigate B, then A; each client keeps the title written in its own session, no matter which client wrote last.
  4. Alternating navigation: move both clients through several screens in turn; no title from one session appears in the other.
  5. Session restart: close and reopen one client; its title initializes from its own screen logic without touching the session that stayed open.

If any check fails, a shared tag or a stale session is still in the path: audit the tag list and the session start, not the screen scripts.

Which mistakes bring the mixed titles back? #

Four mistakes cause most regressions: rebinding the display but not the writer, converting only one of several title tags, testing with a single client, and retesting a session that predates the download.

Mistake What you see Correction
Display rebound, writer not Title stale or empty Point the read and the write at the same session-local tag
Only one of several title tags converted Fault remains on selected screens Audit every tag that carries a client-specific title
Tested with a single client Defect looks fixed because no competing writer exists Test with at least two simultaneous sessions
Old session retested after the download Client runs the old configuration Start fresh sessions for the acceptance test

The decision, per case. A tag that carries what one session is displaying gets "Local session" scope, with both sides of the binding checked and the two-client test passed. A tag that carries what the machine is doing stays shared, and the conflicting writer gets fixed instead. One scope property, proven with two clients, ends the mixed titles.

Questions asked

Does Local session scope also work for a tag connected to the PLC?

No. Scope is a property of internal tags. A tag connected to the controller supplies the process value to every session, so all clients rightly see the same content. When each client needs its own title, keep that title in an internal tag set to Local session.

Can I create one tag name for each client instead?

Only when the application really assigns fixed roles to fixed clients. One tag name for each client couples every screen to a particular machine and breaks as soon as a client is replaced or added. Local session scope states the actual requirement, one value for each active session, without any per-client wiring.

Does Local session scope stop two scripts in one client from overwriting the title?

No. The scope separates clients from one another; it does not sequence writers inside a session. If two events in the same session write the title tag, the later write still replaces the earlier one in that session. Give the tag one writing event per screen change, or compute the title in a single place.

Are there session-local system tags as well?

Yes. The Unified runtime also provides system tags that are local to the current session, so a screen can show information about its own session without a controller connection. They behave like your own session-local tags: each client reads its own copy of the value.

Keep reading

  • Explainer

    Does One Shared Script Speed Up WinCC Screen Animations

    No for screen changes: opening a picture loads graphics, dynamic bindings and initial tag values, and consolidating animation scripts into one does not reduce that. Yes for steady-state runtime, but only when the grouped animations share one frame rate and phase, the trigger is scoped to the picture, and the shared counter has exactly one writer. Expect the visible running cycle to be three times the trigger interval.

    HMI and touchscreens

  • How-to

    Change the HMI screen from the PLC in WinCC Unified

    In WinCC Unified the Job Mailbox is gone. Give each target screen a screen number, link an HMI tag to the PLC integer command tag, and call ChangeScreenWithNumber from a value-change event on an object in a persistent base screen. Never call the UI system functions from a scheduled task or global module — those scopes have no UI context and raise "UI not supported in current scope".

    HMI and touchscreens

  • Troubleshooting

    Why a Unified Comfort Panel web client shows scrollbars

    On V17 Update 7 the panel-integrated web client has no fit-to-window setting, so a screen configured for the panel's native resolution overflows any smaller browser viewport. From V18 Update 1 you set size-fit on the Main screen window. Staying on V17, run the browser fullscreen or fit the layout from a UI.GetClientInfo script.

    HMI and touchscreens

Why COROS COMED Rejects S5L Files Before a WinCC Migration