Troubleshooting
Why WinCC Unified WebRH opens an empty login page
Short answer
When the WinCC Unified welcome page loads but the WebRH runtime page stays blank, the web server and the project are running and the fault sits in the login hand-off or the browser. Restart the runtime host and reload the project first, which cleared one reported system, then match the URL to the identity-provider access method and retest in Edge, which cleared a second system where Firefox stayed blank.

On this page
An empty page after the WinCC Unified welcome page means the web server answered and the project is running — SIMATIC Runtime Manager shows it as running — so the fault sits downstream, in the login hand-off to the runtime screen or in the browser that renders it. Two actions clear it in the field: restart the runtime host and reload the project, which cleared one reported system, and open the same page in Microsoft Edge, which cleared another where Firefox stayed blank. Between those, check that the URL you open matches the identity-provider access method set in WinCC Unified Configuration — computer name by default, IP address as the alternative. The checks below run in the order that costs the least time, and each outcome ends in a decision.
Confirm the failure boundary #
Open https://localhost in the browser. If the WinCC Unified welcome page renders, the web service is up and serving pages; if SIMATIC Runtime Manager lists the project as running, the runtime is loaded. A blank page after you click "WinCC Unified RT" — or a direct opening of https://localhost/WebRH — is therefore not a dead server and not a failed project load. It is a failure in the hand-off between the welcome page's login flow and the runtime screen, or in the rendering of that screen.
Hold that boundary before changing anything. A blank page is a different fault from the browser showing the IIS page instead of your HMI runtime, where the server answers with the wrong content, and different again from a Unified simulation that will not open in the browser, where the runtime never starts. Here the server answers correctly and the content never appears. If even the welcome page fails to render, stop there — every check below assumes it loads.
Match the URL to the identity-provider access method #
WinCC Unified Configuration defines an identity provider for the web client's login, and its access method follows the computer name by default; the alternative follows the machine's IP address. A client that reaches the runtime PC only by address — no DNS entry, no name resolution — can render the welcome page and then fail the name-based login hand-off, because the two steps resolve the host differently.
Test both address forms on the failing client:
https://localhost/WebRH— the computer-name form.https://192.168.1.50/WebRH— the address form, with 192.168.1.50 as the example address; substitute the runtime PC's own address.
If the address form renders the HMI screen and the name form stays blank, align the pair: switch the identity-provider access method to the address form in WinCC Unified Configuration, or give the network working name resolution — the vendor documents DNS-record configuration for name-based access from outside networks. Pick one form and use it in every shortcut and bookmark. On the reported system both forms rendered with the default provider after a restart, so treat this as a check to run, not as the guaranteed cause.
Restart the runtime host and reload the project #
Restarting the runtime PC drops every Web client session and the local runtime screens, so pick a window in which operators can lose those screens — a blank page on one client does not justify pulling them on a running shift.
- Close the failing browser tab and keep the welcome page as your reference.
- Restart the computer or virtual machine that hosts WinCC Unified.
- Load the project to the runtime again from TIA Portal, and confirm in SIMATIC Runtime Manager that it shows as running.
- Reopen
https://localhost/WebRHand expect the HMI screen, not the blank page.
This is the action that cleared the reported case: a restart of the hosting virtual machine plus a project reload, with the identity provider left on its default. No log entry or configuration change was identified behind it, so treat it as recovery rather than a root-cause fix — and still make it the first step, because it costs one restart window and it is the only check that addresses host state directly.
Retest the browser and clear client state #
If the restart leaves the page blank, open the same URL in Microsoft Edge. On one reported system Edge rendered the HMI while Firefox stayed blank and the restart had not helped; on another system the identical project ran in Firefox without trouble. Siemens documents several modern browsers on Windows, Android, iOS and macOS as supported for the Unified PC Runtime web client, so a single engine is not a stated requirement — the Edge test isolates a machine-specific rendering or session fault, and it does not put the project, the license or the runtime in question.
If you retest the failing browser, update it first and retest after clearing its cache. Watch also for the neighboring failure with its own documented causes: when the browser shows a SwacLogin error message instead of a blank page, the vendor lists a deleted browser cache, an insecure connection such as HTTP, and a client device that cannot authorize among the causes, and the same documentation directs you to the identity provider's URL and to HTTPS. Name which of the two symptoms you see — a blank page and a SwacLogin error share the client-side territory but not their cause lists.
Worked example: four loads on one runtime PC #
This is a bench example with example values. Runtime PC UNIFIED-RT-01, example address 192.168.1.50, no DNS record on the bench, project running, welcome page rendering in both browsers. Two address forms times two browsers gives four loads, and one failing cell names its variable:
| Load | URL | Browser | A failure here isolates |
|---|---|---|---|
| 1 | https://localhost/WebRH |
Edge | the name-based login hand-off |
| 2 | https://192.168.1.50/WebRH |
Edge | the address-based hand-off |
| 3 | https://localhost/WebRH |
Firefox | the name form under a second engine |
| 4 | https://192.168.1.50/WebRH |
Firefox | the address form under a second engine |
Read the matrix by where the blank cells fall. Loads 1 and 2 render while 3 and 4 stay blank: the engine is the variable, so keep that client on Edge and update or reinstall Firefox — nothing on the runtime side changes. Loads 1 and 3 stay blank while 2 and 4 render: the name form is the variable, so move the identity-provider access method to the address form or add the DNS record. All four stay blank after the host restart and project reload: the client matrix is exhausted. The two reported systems sit at the first and last of those readings — one cleared at the restart step before the matrix was needed, the other matched the engine row and cleared in Edge.
The decision for each case #
- Welcome page renders, WebRH blank, and the host has been up through edits or a long idle stretch: restart the runtime host and reload the project, and expect the HMI screen at the same URL. This cleared the reported case.
- Restart and reload done, Edge renders, Firefox does not: keep that client on Edge and update or reinstall Firefox at the next maintenance window. The passing loads prove the project and the access method; with several modern browsers documented, no runtime-side change is warranted.
- The address-form URL renders and the name-form URL stays blank: align the identity-provider access method with the URL the clients actually use — switch it to the address form, or add name resolution and keep the name-based default — and standardize one form everywhere.
- Blank in both browsers on both address forms after a restart and reload: the welcome page and Runtime Manager have already proven the server and the project, so take the matrix results and the settings behind them to the vendor's technical support.
Every decision hangs on the same boundary: the welcome page proves the web server and Runtime Manager proves the project, so a blank WebRH page is always a hand-off or client fault, and the four-load matrix names which one inside a single restart window.
Questions asked
What does the home page's My WinCC Unified entry prove?
From the Unified home page, My WinCC Unified opens its login dialog in a new tab. If that dialog renders and accepts your login while the WebRH page stays blank, the login hand-off works and the failure sits in the runtime screen load itself, which points at the browser rather than the address form.
Should I leave the identity provider on the IP-address method permanently?
Only when clients reach the runtime PC by address alone. If you open the HMI by computer name, keep the name-based default and supply name resolution instead: the vendor's external-access documentation shows creating a DNS record that maps a name, with MyWinCC as its example domain, to the runtime PC's address.
Both address forms stay blank in both browsers after a restart. What do I collect before a support request?
Record the exact URLs you tested, both address forms, each browser and its version, the identity-provider access method shown in WinCC Unified Configuration, the project status in SIMATIC Runtime Manager, and whether the welcome page still renders. That set lets support separate a server fault from a client fault without repeating your bench work.
Why does the same project open in Firefox on one PC and stay blank on another?
The project, the address form and the access method are identical, so the difference is client state on the failing machine. Before replacing the browser, retest the failing one in a private window or a fresh profile: cached session data and extensions are the usual leftovers, and a clean profile rebuilds both.