Transfer Parameters from Siemens MicroMaster 430 to MM440

David Krause20 min read
SiemensTutorial / How-toVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Transfer Parameters from Siemens MicroMaster 430 to MM440 via STARTER

The MicroMaster 430 (MM430) and MicroMaster 440 (MM440) share the same STARTER/DriveMonitor commissioning toolchain and a largely overlapping parameter structure, but they target different application classes (constant-torque heavy industrial vs. vector-controlled general purpose) and use different firmware branches. When a spare MM440 must replace a failed MM430, parameters can be cloned through the STARTER XML export/import path — but only with controlled reconciliation, not a blind overwrite. This reference covers the full procedure: compatibility, export, import, parameter mapping, commissioning, and verification.

1. Overview of the Parameter Transfer Problem

The MM430 and MM440 are both members of the Siemens MICROMASTER 4 family. They share:

  • The same USS/Modbus RTU/Profibus (via CBP module) fieldbus interface cards.
  • The same commissioning tool: STARTER (versions 4.x and 5.x) and the legacy DriveMonitor.
  • A common parameter number scheme in the P0000–P3999 range (P-prefixed parameters are commonly called r-parameters for read-only and P-parameters for read/write, e.g., r0000 is the parameter access level, P0010 is the commissioning parameter).
  • Parameter upload/download via the RS232 serial interface, the PC-to-drive USB-to-Serial adapter (Siemens 6SE6400-1PC00-0AA0), or Ethernet (via the Ethernet/IP module on the PROFINET side).

What differs is the application firmware, the default values for some motor-control parameters, and the BICO (Binector Connector) interconnection set. A direct in-place parameter copy without reconciliation is not supported by the drives and will result in either:

  • Default-value mismatches (motor nameplate data, ramp times, current limits).
  • Faults F0001 (overcurrent), F0002 (overvoltage), F0003 (undervoltage), F0004 (inverter overtemperature), F0011 (motor overload I²t), or F0051 (parameter EEPROM fault) at first run.
  • Loss of application-specific settings, especially BICO wiring on the MM430 Fast/Standard BOP/AOP parameter access paths.

The only robust transfer path is XML export from the source MM430, XML import into a freshly created MM440 offline project, parameter reconciliation, then download to the physical MM440.

Important: The MM430 firmware (2.02) and MM440 firmware (2.2) referenced in field cases are on different minor version branches. Always capture the source and target firmware version via r0018 (firmware version) before exporting, and verify the XML contains the same version string before importing.

2. MicroMaster 430 vs. MicroMaster 440 — Architectural Differences

Although both drives are MICROMASTER 4, the application targeting is fundamentally different.

Attribute MicroMaster 430 (MM430) MicroMaster 440 (MM440)
Target application Pumps, fans, conveyors, mixers (square-law / constant torque) General-purpose V/Hz, sensorless vector (SLVC), closed-loop vector with encoder
Default control mode Linear V/Hz (P1300 = 0), quadratic (P1300 = 2) for fan duty Linear V/Hz, FCC, SLVC (P1300 = 20), vector with encoder (P1300 = 21)
Typical firmware branch 2.0x (e.g., 2.02) 2.1x–3.2x (e.g., 2.2, 3.2)
Power range (covers your 110 kW case) 0.37 kW – 250 kW (frame size FS D–F) 0.12 kW – 250 kW (frame size FS A–F)
Operator panel default BOP-2 (basic) BOP / AOP (optional)
Frame size at 110 kW (400 V class) FS F (approx. 360 A rated) FS F (approx. 360 A rated)
Number of parameter indices used Lower; most parameters are scalar or 2-index (CDS/DDS) Higher; more CDS (Command Data Set) and DDS (Drive Data Set) entries, encoder-related parameters present
Key add-on parameters not on MM430 — P0400 (encoder type), P0408 (encoder pulses), P1500 (torque setpoint source), P1960 (rotating identification)

The MM440 firmware carries a larger parameter tree, including sensorless vector control, FCC (Flux Current Control), and encoder feedback. When you import MM430 XML into a MM440 project, parameters that do not exist on the MM430 (e.g., the encoder set) are inserted with MM440 default values, which is generally acceptable. The reverse — MM430 parameters that have no equivalent on the MM440 — is the actual problem; STARTER will mark these as "not imported" in the export/import status window.

3. Prerequisites

Before starting the parameter transfer, confirm the following:

  1. STARTER version: STARTER V4.x or V5.x with the SP (Service Pack) for MICROMASTER 4 support. STARTER commissioning tool download and documentation (Siemens Support). STARTER 5.4 + HF03 or later is recommended for MM440 firmware ≥ 3.2.
  2. PC-to-drive connection: Either
    • RS232 straight-through cable to the MM430/MM440 front panel RJ11 (or 6SE6400-1PC00-0AA0 PC-inverter connection kit), or
    • USB-to-serial adapter (FTDI-based recommended) for laptops without a DB-9.
  3. Drive firmware note: The r0018 firmware string of source and target. In STARTER, browse online to read r0018. MM430 firmware 2.02 and MM440 firmware 2.2 are both MM4 firmware branch 2.x; the parameter mapping is therefore wide but not 1:1.
  4. Project license (if any): A spare MM440 with the same power rating (110 kW, 400 V class, FS F) and rated current (≈ 360 A; check nameplate, depends on whether the drive is light-overload or heavy-duty rated — see Section 10).
  5. Original MM430 commissioning report (printed or PDF) with the motor nameplate data: rated kW, voltage, current, frequency, cos φ, speed.
  6. Access to the inverter at the cabinet with the BOP-2 or AOP removed or a STARTER online connection possible.
Safety: The MM440 capacitor bank retains dangerous DC bus voltage for 5 minutes after line disconnect (see MICROMASTER 440 operating instructions). Confirm the DC bus voltage at the test points (labelled "DC+" and "DC-" on the FS F chassis) is below 50 VDC before any work inside the unit. The FS F (110 kW) chassis weighs over 100 kg — use the lifting eye on top of the inverter and a hoist for any rack removal.

4. Pre-Transfer Data Capture from the MM430

Even if STARTER already contains the live MM430 project, capture the following data before exporting. This is your fall-back if the XML import diverges.

  1. Connect STARTER to the MM430 online. Right-click the drive → Online → Connect to target device.
  2. Navigate to Commissioning → Parameter list. Filter for P0010 = 0 (ready) and capture the full parameter dump to a CSV using Commissioning → Expert list → Print/Export.
  3. Record the following critical parameters and values by hand or in a spreadsheet:
    Parameter Meaning Why it matters
    P0010 Commissioning filter Must be 0 in operation; values 1/30 trigger parameter set writes
    P0100 Europe/N. America (50/60 Hz, kW/HP) 0 = 50 Hz / kW; 1 = 60 Hz / HP; 2 = 50 Hz / HP
    P0201 Rated power of drive (kW) 110.0 in your case
    P0205 Inverter rated current (A) ~360 A on FS F 110 kW; verify nameplate
    P0304 Motor rated voltage (V) e.g., 400 V
    P0305 Motor rated current (A) e.g., 205 A on a typical 110 kW motor
    P0307 Motor rated power (kW) 110.0
    P0308 Motor rated cos φ 0.85–0.89 typical
    P0310 Motor rated frequency (Hz) 50 or 60
    P0311 Motor rated speed (rpm) e.g., 1485 rpm on a 4-pole 50 Hz motor
    P0700 Command source selection 2 = terminal, 6 = fieldbus
    P1000 Setpoint source selection 2 = analog, 6 = fieldbus
    P1080 / P1082 Min / max frequency (Hz) e.g., 0.00 / 50.00
    P1120 / P1121 Ramp-up / ramp-down time (s) Application-specific
    P1300 Control mode 0 = V/Hz linear, 2 = V/Hz quadratic, 20 = SLVC
    P2000 Reference frequency (Hz) For fieldbus scaling
    P2150 etc. Process-controller gains (if used) For PID/pump applications on the MM430
  4. Save the MM430 project (Project → Save) and the online copy (Target system → Upload to PG/PC) so you have an offline copy containing the source settings.
  5. Note any BICO connections set on the MM430: P0730…P0733 (DO function), P0770…P0771 (AO function), P2800…P2890 (free function blocks on MM440). MM430 has a smaller free-function-block set, so anything wired on the MM430 to MM430-only parameters will not import.

5. Step-by-Step: Exporting the MM430 Project to XML

This is the offline path that worked in the field case where the source drive was no longer accessible online. The XML file is portable between PCs and can be archived.

  1. In STARTER, open the MM430 project (offline is fine).
  2. Right-click the MM430 drive object in the project tree.
  3. Select Expert → Save and Export… (or the menu path Project → Save and Export in STARTER 5.x). The wording varies slightly by STARTER version: in older versions it appears as Save / Export Project to XML.
  4. Choose a target folder (e.g., C:\Temp\MM430_export\). STARTER writes one or more XML files, with the main file ending in _DO.xml (drive object) and supporting index files for parameter indices.
  5. Open the export status window when prompted. STARTER will show warnings if any parameter fails to serialize. Typical warnings for an MM430 export are about read-only r- parameters — these can be ignored.
  6. Verify the XML header contains the firmware string. Open the *.xml in a text editor and search for <FirmwareVersion> or the equivalent attribute — confirm it matches the source r0018 reading.
Tip: The XML files STARTER produces are plaintext UTF-16. Do not edit them in a word processor — even a single character mismatch breaks the import. Use Notepad++ or VS Code in "plain text" mode if you must read them.

6. Step-by-Step: Importing the XML into a New MM440 Project

The most common failure in this procedure is the "Import function is not active" issue raised in the field report. This happens when the active project is not the correct target. The fix is to ensure you are inside an MM440 project, not the MM430 project you just exported.

  1. Close the MM430 project. File → Close (do not save again — the export already captured the settings).
  2. Create a new offline project: File → New Project. Name it e.g., MM440_110kW_clone.
  3. Insert a new drive: right-click the project → Insert Single Drive Unit. Search for the MM440 product family. Select the correct power class — for 110 kW this is typically MICROMASTER 440 / 6SE6440-2UD41-1GA1 (or the equivalent order number for the local mains voltage, 380–480 V 3-ph).
  4. Confirm the drive is inserted as an offline object (the green icon, not the yellow "online" icon). If the project was opened with auto-connect, click the disconnect button first.
  5. Right-click the MM440 drive object. The menu now shows Expert → Import as active (it is greyed out when the active drive is the wrong model).
  6. Select Expert → Import…. Navigate to the *.xml file from Step 5.
  7. STARTER raises a warning: You are attempting to overlay an incompatible (different) drive. This is expected and must be accepted. The dialog exists because STARTER is aware the parameter sets do not fully match.
  8. After import, STARTER displays the Import status window. Each line shows whether the parameter was imported, kept at default, or rejected. The count of "not imported" lines is the parameter reconciliation work for the next step.
  9. Save the project: Project → Save. Archive the resulting *.sdp file alongside the XML.
Why the Import button was greyed out: In the field report, the engineer had the MM430 project still active. STARTER only enables the MM430→MM440 import path when the active drive object is an MM440. Switching projects (or using Window → Switch Project) resolves the issue. This is the most common cause of "import function is not active" in the field.

7. Parameter Reconciliation Procedure

After import, manually verify the parameters that drive behavior. The reconciliation list below is the minimum check; add application-specific parameters as needed.

Parameter Source (MM430) Target (MM440) after import Required action
P1300 (control mode) 0 (linear V/Hz) or 2 (quadratic) 0, 2, 20, or 21 (depending on import map) Force back to source value. P1300 = 20 (SLVC) is more common on MM440 and may be incorrectly assigned.
P0100 (EU/US) 0 (Europe / kW) 0 or 2 (depending on regional template) Force P0100 = 0 for 50 Hz / 400 V EU motors.
P0201, P0205, P0206, P0207 110 kW, ~360 A May revert to MM440 default (e.g., 75 kW / 145 A) if XML is rejected Reset to drive nameplate values.
P0304–P0311 (motor nameplate) Customer motor data Imported correctly, but verify Cross-check every value against the captured record from Section 4.
P0700, P1000 2 / 2 or 6 / 6 Imported Verify: 2 = terminals, 6 = fieldbus (CB at P0918 / P0927).
P1080, P1082 (min/max freq) Application-specific Imported Verify min/max are application-correct, especially on pump duty where P1080 = 10 or higher may be needed.
P1120, P1121 (ramps) e.g., 20 s / 30 s Imported Verify; P1130–P1134 ramp rounding should also be checked.
P2000 (reference frequency) 50.0 50.0 or 60.0 Critical for fieldbus scaling — must match the SCADA/PLC scaling.
P2150–P2164 (PID) If MM430 used PID Imported as P2200…P2295 on MM440 (PID controller is renumbered) Manual rework required. The MM430 PID set in P21xx is mapped differently; the MM440 PID uses P2200 enable, P2251 gain, P2252 integral, etc.
P0730–P0733 (DO function) 52 = run, 53 = fault, etc. Imported Verify; MM440 has additional DO and BICO targets.
P0770–P0771 (AO function) 21 = freq, 24 = output current Imported Verify scaling at P0771 and P0773.
P1500 (torque setpoint src) 0 (no torque ctrl) on MM430 Imported; MM440 has P1500 populated Force to 0 if you do not need torque control. Setting P1500 non-zero on a V/Hz motor without a torque sensor will fault on first run.

For each "not imported" parameter in STARTER's status window, consult the MM440 parameter manual. The most common omissions are MM430-specific parameters with no MM440 equivalent (legacy free-function-block parameter slots, customer-specific firmware extensions).

Warning on P1500: Setting a torque setpoint source on a constant-torque centrifugal pump load without a torque sensor will cause F0001 (overcurrent) or F0090 (encoder loss) on the first run. Clear P1500 to 0 if the application is V/Hz or SLVC.

8. Drive Commissioning on the MM440 Hardware

Once the offline MM440 project is reconciled, download to the physical drive. The MM440 first-time commissioning sequence:

  1. Verify mains voltage at the disconnect: 380–480 V 3-phase ±10% (or 200–240 V for the 230 V class). Phase rotation L1-L2-L3 must match the drive's markings.
  2. Connect STARTER online to the MM440 via RS232. Right-click the drive → Online → Connect. The status icon turns yellow.
  3. Set P0010 = 30 to allow factory reset, then P0970 = 1 to clear all parameters to factory default if you want a clean slate. (Skip this step if you want to preserve any settings already on the spare MM440.)
  4. Reconnect, then download the reconciled project: right-click → Target system → Download to target device. STARTER prompts for P0010 = 30 first — accept.
  5. Wait for the green "Download complete" message. The drive will reset, then show "Ready to run" (display: 0000 or ready pattern).
  6. Set P0010 = 0 for normal operation. P0700, P1000, ramp times, and the process controller are now armed.
  7. Set the access level for the user: P0003 = 1 (standard) or P0003 = 3 (expert) per site policy.

9. Motor Identification and Verification

The MM440, when set to P1300 = 20 (SLVC) or P1300 = 21 (vector with encoder), requires motor data identification at first start. Even on V/Hz mode (P1300 = 0 or 2), a static motor identification improves low-speed torque.

  1. Set P1910 = 1 (motor data identification, static). The drive prompts: Press the green start button on the BOP to begin identification.
  2. Apply the run command but do not load the motor. The drive injects a brief current pulse and measures stator resistance (r1912), leakage inductance, and rotor time constant. The motor emits a single low-frequency hum for ~3–10 s.
  3. For P1960 = 1 (rotating identification), the motor must be uncoupled from the load. P1960 accelerates the motor to a configured speed and back, computing the moment of inertia. Skip this if the load is not decoupled.
  4. After identification, the drive returns to "Ready". The computed values are written to r1912–r1925 and copied to P0350–P0360 for the controller.

9.1 No-Load Test (Mandatory Before Coupling to Load)

  1. Verify the run command source matches expectations: with the fieldbus disconnected, force P0700 = 2 and P1000 = 2, then apply 24 V to DIN 0 (terminal 5) on the MM440. The drive should ramp to P1080.
  2. Step the setpoint to 25%, 50%, 75%, and 100% of P2000. At each step, log:
    • Output frequency (r0024)
    • Output current (r0027 or r0068)
    • DC bus voltage (r0026)
    • Motor torque (if P1300 = 20: r0031)
  3. For 110 kW at 400 V, the no-load current should be 30–50% of P0305 on SLVC, 25–40% on V/Hz. If the no-load current is above 60% of nameplate, the motor data is wrong or P0310/P0311 is mis-set.
  4. Verify the ramp timing matches P1120 and P1121 with a stopwatch. A discrepancy greater than 10% indicates ramp rounding (P1130–P1134) is not what the original setting implied.

9.2 Loaded Test

  1. Couple the motor to the load (pump, fan, conveyor).
  2. Run at process setpoint. Monitor r0027 (motor current) and r0034 (motor I²t utilization). r0034 should remain below 100% sustained. r0034 > 100% trips F0011 after the I²t timer expires.
  3. Verify the fieldbus (if used) reads the correct actual frequency. The PLC should be reading r0024 (or the fieldbus-mapped r0021). A scaling mismatch (PLC sees 100% when the drive is at 50 Hz) is a P2000 problem on the drive side, not a PLC scaling problem.
  4. Capture a STARTER trace of r0024, r0027, and r0034 for 60 s of normal operation. Archive this trace with the project as proof of commissioning.

10. Sizing and Current Verification

The 110 kW power class on both MM430 and MM440 maps to roughly 360 A rated output. Verify by reading the inverter nameplate (printed on the side of the unit) — Siemens part numbers for the 400 V class 110 kW range include:

  • 6SE6440-2UD41-1FA1 (MM440, 110 kW, 250 A heavy-duty, 290 A light-duty)
  • 6SE6430-2UD41-1FA1 (MM430, 110 kW, 250 A heavy-duty, 290 A light-duty)

These are for the 400 V / 480 V three-phase mains class. The exact part number depends on the regional variant and overload rating. Always cross-check against the physical nameplate.

For a 110 kW, 400 V three-phase motor with a typical 89% efficiency, the input line current is approximately:

I_line = (P_out / (sqrt(3) * V_LL * eta)) = (110000 / (1.732 * 400 * 0.89)) = 182.7 A (motor input)
I_inverter = I_motor / 0.97 (inverter efficiency ~97%) ≈ 188 A

The 250 A heavy-duty rating of the FS F drive gives 1.36× service factor above the motor FLA, which is the standard Siemens 110 kW configuration. If the replacement MM440 is the same FS F, the parameter set transfers cleanly. If the spare is a different FS, P0205 must be re-entered from the new nameplate and motor nameplate scaling (P2000) re-checked.

Note on phase topology: The Siemens FS F 110 kW MM430/MM440 are three-phase line-current devices. The 360 A figure occasionally seen in literature is the FS F 690 V class rating, not the 400 V class. Always read the nameplate, not the catalog number, before assuming current.

11. Troubleshooting Matrix

Symptom Likely cause Action
STARTER Import greyed out Wrong drive object active (MM430 instead of MM440) Close MM430 project, create new offline MM440 project, then Expert → Import
Import warning "incompatible drive" Firmware branch differs between source and target Accept the warning, proceed; reconcile the post-import parameter status window
F0001 overcurrent at first run Motor nameplate data not reconciled; P1500 set non-zero; P1300 set to vector mode without P1910 Reset P1500 = 0, set P1300 = 0 (linear V/Hz) for first run, run P1910 = 1 identification
F0011 motor overload (I²t) Motor current limit too low; P0640 (motor I²t factor) mis-set; load is heavier than nameplate Verify P0305 matches motor nameplate FLA; raise P0640 to 100%
F0051 parameter EEPROM fault Download interrupted; P0010 ≠ 0 at power-up Re-download with stable USB/serial cable; set P0010 = 0 and cycle power
Fieldbus scaling wrong (PLC reads 100% at 25 Hz) P2000 mismatch Set P2000 = P1082 (max frequency), re-download
Drive does not start despite ON command Run command source mismatch (P0700), OFF1/OFF2/OFF3 missing, fault not cleared Check r0002 (status word), r0052 (status word 2), r0054 (control word 1), clear faults with Ack (BOP) or P3981 = 0
PID controller oscillates after transfer MM430 PID parameters (P21xx) not mapped to MM440 PID (P2200/P2251/P2252) Re-enter PID gain (P2251), integral (P2252), derivative (P2253), setpoint source (P2250), feedback source (P2264), enable P2200 = 1
Encoder fault F0090 P0400/P0408 set but no encoder wired Set P0400 = 0 (no encoder) and P1300 = 0 or 20 (no encoder control mode)
Display shows different language P0014 language parameter Set P0014 = 0 (English) or per site standard

12. Field-Proven Caveats

  1. Don't skip the no-load test. A 110 kW MM440 is not a small inverter. The difference between V/Hz and SLVC at first start can be the difference between a 1-second ramp and a 10-second ramp with full magnetizing current. Always test no-load before coupling the load.
  2. Check the firmware string, not the major version. MM430 firmware 2.02 and MM440 firmware 2.2 share the major "2.x" branch, but the parameter index mapping differs even within a major. Always archive r0018 for both drives and note them in the project README.
  3. Save the XML, not just the SDP project. STARTER projects (.sdp) are PC-installation-specific. The XML is portable across PCs, STARTER versions, and is the only thing you can hand off to a colleague without sending the full project tree.
  4. MM440 has more DO/RO and DI than MM430. The MM430 has 3 digital inputs, the MM440 has 6. If the original wiring used 4 or 5 DIN, the MM430 was probably a non-standard config — verify before assuming the MM440 is one-to-one pin-compatible.
  5. The BOP-2 is not fully compatible across MM4 generations. A BOP-2 from an MM420/430 may not display the full parameter tree on an MM440 firmware ≥ 2.0. Use the AOP or STARTER for first-time commissioning of the MM440.
  6. Archive the as-exported XML, the as-imported project, and the as-commissioned project. Three files, three timestamps. If a fault occurs in six months, you have the trail to prove the original settings.
  7. Current ratings: A 110 kW MM440 is the FS F chassis and weighs about 110 kg. Two people plus a hoist, or the lifting eye on top of the unit, is the minimum safe handling plan.

13. Standards and Compliance References

The MM440 family is CE-marked and complies with the following standards as of the relevant firmware:

  • EN 61800-5-1 — Adjustable speed electrical power drive systems — Part 5-1: Safety requirements — Electrical, thermal and energy
  • EN 61800-3 — EMC requirements and test methods for adjustable speed power drive systems
  • UL 508C — Power Conversion Equipment (for the UL-listed variants of the MM440)
  • IEC 61131-3 — For the PLC-side interface (relevant when the drive is controlled by a Siemens PLC like S7-1200/1500 via the PN or CBP module)

These standards define the safe operating envelope (overvoltage category, pollution degree, ambient temperature range 0–40 °C without derating up to 50 °C with derating). Verify the specific rating on the drive nameplate and in the operating instructions linked at the top of this article.

Can I directly clone a MicroMaster 430 to a MM440 without using STARTER?

No. The MM430 and MM440 use different firmware branches and parameter maps. A direct drive-to-drive parameter copy (e.g., via the BOP-2) is not supported. You must use STARTER to export the MM430 settings to XML, create a new MM440 project, and import the XML. The MM440 BOP-2 will warn "incompatible drive" and refuse any direct copy from an MM430 dataset.

Why is the Import option greyed out in STARTER?

The most common cause is that the active drive object in the project tree is still the MM430 from the previous project. Close the MM430 project, create a new MM440 offline project, then right-click the MM440 → Expert → Import. The Import command is only enabled when the active drive is the correct target type for the XML file.

Do I need to re-run motor identification after the parameter transfer?

Yes. Even if the source MM430 was commissioned with a motor ID, the MM440's SLVC controller has different default gains and the stator resistance / leakage inductance values are drive-specific. Run P1910 = 1 (static motor ID) before first run. Run P1960 = 1 (rotating ID) only if the load can be decoupled.

What happens to MM430-only parameters that don't exist on the MM440?

STARTER marks them as "not imported" in the import status window. They have no equivalent on the MM440 and are simply dropped. The most common omissions are MM430-specific free-function-block parameters and some legacy BICO interconnects. The MM440 substitutes its own defaults for the missing parameters; reconcile the result against the original commissioning report.

Can I clone a 110 kW MM430 to a 110 kW MM440 of the same frame size without changing motor nameplate data?

Yes — the motor nameplate data (P0304–P0311) transfers cleanly. The drive nameplate data (P0201, P0205) must be verified against the new inverter's actual rating, which should match for the same FS F 110 kW chassis. The power and current parameters are within the MM4 family common map and import without manual rework in the same frame size.

Is the STARTER XML format compatible between STARTER 4.x and STARTER 5.x?

STARTER 5.x reads STARTER 4.x XML files, but a STARTER 4.x project may warn on missing fields when opened in STARTER 5.x. The XML schema has been stable for MM4 family projects since STARTER 4.2 SP2. Always save the project in the version of STARTER that you are commissioning with, but the XML is portable in both directions for MM4 family devices.

Back to blog