Activating the XBTOT Target Family in Vijeo Designer 6.2
Short answer
Enter upgrade code VJDHTGTOPV62M in the full Vijeo Designer 6.2 edition under Help > About > License > Upgrade, restart the software, and XBT OT appears in the new-project target list. Vijeo Designer Lite 1.2 or 1.3 cannot list or unlock the family.
On this page
The XBTOT family, including the XBT012110, is locked out of a default Vijeo Designer 6.2 installation. Schneider Electric documents the unlock in FAQ FA357907: open Help > About, select Upgrade in the License tab, enter the code VJDHTGTOPV62M, and restart the software. The XBT OT node then appears in the target list of a new project. Two conditions decide whether this works for you: you must run the full Vijeo Designer 6.2 edition, because Lite 1.2 and 1.3 neither list XBTOT nor accept an upgrade to it, and the software must be registered before the Upgrade button shows.
What the code unlocks, and in which edition #
VJDHTGTOPV62M is a target-list upgrade code, not a separate license file. Entered once per installation, it adds the XBT OT node — the XBT012110 and its siblings — to the target list you see when creating a new project. It is specific to the 6.2 build; entering it in another build fails.
The terminal itself explains why this path matters. The XBT012110 is a discontinued 5.7 in monochrome STN panel at 320 x 240 px, powered at 24 VDC, with a single serial COM port (RS-232C / RS-422 / RS-485) and no Ethernet or USB device port. Everything you do with it goes through that port and through this one software generation. Get the 6.2 base installer from Schneider Electric or its distributors — the vendor support site carries it under reference FAQ000282775 — rather than from file-sharing sources, because the upgrade code is checked against the licensed build.
Activating the XBTOT family in Vijeo Designer 6.2 #
- Install the full Vijeo Designer 6.2 edition, running the installer as administrator.
- Launch Vijeo Designer.
- Open Help > About.
- In the License tab, select Upgrade. If the button is missing, register the software first, close it completely, and relaunch — the button then appears.
- Enter VJDHTGTOPV62M.
- Confirm the dialog reporting that the XBTOT family has been added.
- Close Vijeo Designer completely, including any runtime process, and relaunch it.
- Open File > New Project and select XBT OT from the target list.
If you are already registered and the button still does not show, launch the program as administrator and repeat from step 3.
When the code or the button fails #
| Symptom | Reason | Fix |
|---|---|---|
| Upgrade button missing in the License tab | Software not registered yet | Register, close completely, relaunch, and the button appears |
| Code VJDHTGTOPV62M rejected | Not the 6.2 build | Check the version under Help > About and use the code for that build |
| XBT OT still absent after entering the code | A Vijeo Designer or runtime process survived the restart | Close every Vijeo Designer process and relaunch |
| Lite 1.2 or 1.3 lists no XBTOT and offers no Upgrade path | Lite edition | Install the full 6.2 edition, then apply the code |
Downloading over the serial port #
The PC reaches the terminal through the Schneider XBT ZG 935 cable or an equivalent built to the panel instruction sheet and user guide on the vendor download site. If the original cable is gone and you must make one, work only from those documents — the page on uploading an HMI program without the right cable pinout covers how to build a lead from the connector pinout you have.
In the transfer settings, start at 9600 bps, 8 data bits, no parity, 1 stop bit, no flow control. After the first handshake the bootloader negotiates up to 115200 bps, and the difference is large enough to plan around. With 8-N-1 framing each byte costs 10 bits on the wire:
- 9600 bps / 10 bits per byte = 960 B/s
- At 960 B/s, an illustrative 2.0 MB compiled project (2,000,000 B) takes 2,000,000 / 960 = 2083 s, about 35 minutes
- After negotiation, 115200 bps / 10 = 11520 B/s, and the same 2,000,000 B take 2,000,000 / 11520 = 174 s, about 3 minutes
The 2.0 MB size is an example; your project size sets the actual minutes. The ratio is fixed at 12 to 1, so let the slow first phase finish and never power-cycle the panel mid-transfer.
The upload limitation #
An XBT012110 surrenders its application only if the original download was made with the upload option enabled in the transfer dialog. Without that option the flash holds a runtime image only, and nothing — vendor tools included — reconstructs the source from it. So before you modify a running machine, locate the .vdz project archive in the machine documentation and save a dated copy of every version you download. For panels where the option was enabled, the page on uploading a program from an old touchscreen HMI walks the recovery.
The decision for each case #
- Full Vijeo Designer 6.2 installed: enter the code, restart, and program the terminal today. The only remaining dependency is the serial cable.
- Lite 1.2 or 1.3 installed: stop there. There is no code path; install the full 6.2 edition first.
- Code rejected: you are not on the 6.2 build. Verify the version under Help > About and use the upgrade code documented for the build you run.
- Source lost and upload never enabled: budget a rewrite from the machine I/O list, or move to a current terminal — the page on planning an HMI terminal replacement from an older operator panel covers that selection.
Questions asked
Will VJDHTGTOPV62M work in Vijeo Designer 6.1 or 6.3?
No. The code is the documented target upgrade for the 6.2 build only, and other builds reject it when you enter it. Before entering anything, check the version you are running under Help > About. Then use the upgrade code that Schneider Electric documents for the build you actually have installed on that engineering station.
The Upgrade button does not appear in the License tab. What now?
Register the software first, close Vijeo Designer completely, and relaunch it. The button then appears, which is the fix Schneider Electric support gives for this exact symptom. Launching the program as administrator also avoids a license write failing silently.
How long does a project download take over the serial cable?
At the 9600 bps starting rate with 8-N-1 framing you get 960 bytes per second, so a 2 MB project takes about 35 minutes. Once the bootloader negotiates 115200 bps, the same project takes about 3 minutes. Keep the cable seated and the 24 VDC supply stable for the whole transfer.
Can I get the program back out of an XBT012110 terminal?
Only if the upload option was enabled when the original download was made. If it was not, the terminal holds a runtime image only and no procedure reconstructs the source. Find the .vdz archive in the machine documentation and keep a dated copy every time you change the project.