Explainer

Can You Migrate a WinCC 7.2 Project to WinCC Flexible

HMI and touchscreens Published 8 min read

Short answer

No migration path converts a WinCC 7.2 project into WinCC flexible 2008; Siemens documents the two as architecturally incompatible, and the documented directions run the other way - WinCC flexible into TIA Portal, and WinCC 7.2 up to WinCC V7.5. Treat the MP 377 12-inch Touch application as a new WinCC flexible project: inventory every function, rebuild it item by item, and verify each one on the bench.

On this page
  1. Can you migrate a WinCC 7.2 project into WinCC flexible 2008?
  2. Why can't WinCC 7 and WinCC flexible open each other's projects?
  3. What migration paths does Siemens actually document?
  4. How do you scope the MP 377 rebuild?
  5. How do you rebuild the application in WinCC flexible 2008?
  6. What has to match when you recreate tags, alarms and commands?
  7. How long does a function-by-function rebuild take?
  8. Should you reprogram the MP 377 or replace it?
  9. Questions asked

No - there is no documented migration that turns a WinCC 7.2 project into a WinCC flexible 2008 project. Siemens documents the two product families as architecturally incompatible, and its documented conversion paths run upward: WinCC flexible projects into WinCC in TIA Portal, and WinCC 7.2 projects up to WinCC V7.5 inside the SCADA line. So the MP 377 12-inch Touch application is planned, not converted: a new WinCC flexible 2008 project on the exact panel target, a function inventory taken from the 7.2 source, and a controlled function-by-function rebuild verified at the bench. Below are the documented paths and why 7.2 has no door into flexible 2008, the allocation table that scopes the rebuild, a worked schedule example with the arithmetic shown, and the keep-or-replace decision for the terminal itself.

Can you migrate a WinCC 7.2 project into WinCC flexible 2008? #

No - Siemens documentation states that a WinCC V7.0 SP3 project cannot be migrated to WinCC flexible 2008 SP2, naming the two products architecturally incompatible, and no WinCC flexible 2008 release documents a WinCC 7.x import of any kind.

The V7.0 SP3 rejection is the closest documented data point to your case, and nothing in the flexible 2008 documentation accepts any WinCC 7.x source, so 7.2 has no path either. The only WinCC-to-flexible conversion that ever existed was a one-way legacy import predating the V7 line, and the chronology rules your case out on its own: WinCC flexible 2008 shipped years before WinCC 7.2 existed, and no service pack of it documents a WinCC 7.x importer. What the request asks for is a tool that reads a foreign project database and re-expresses its tags, alarms and screens in a different runtime model. Flexible 2008 never did that for V7. Decision: treat 7.2 into flexible 2008 as unavailable and schedule the work as a rebuild.

Why can't WinCC 7 and WinCC flexible open each other's projects? #

Because they are two different engineering systems that only share a name: WinCC V7 is a PC SCADA package whose project is a database with its own tag manager, alarm engine and archives, while WinCC flexible 2008 is a panel tool that generates a device-specific project for one HMI terminal.

The tag models, alarm handling, screen formats and runtime targets differ on both sides. Your 7.2 project executes in the SCADA runtime on a PC; the MP 377 executes a flexible project compiled for that panel. Nothing in one file maps mechanically into the other, which is what the architectural-incompatibility statement means in practice, and it is why renaming files produces no usable panel project. The working differences between the three environments are laid out in the comparison of WinCC V7.4, WinCC flexible 2008 and TIA Portal. Decision: plan the transfer as engineering work - inventory, mapping, recreation - not as a file operation.

What migration paths does Siemens actually document? #

Two, and both run away from your problem: WinCC flexible 2008 projects migrate upward into WinCC in TIA Portal, and WinCC 7.2 projects migrate upward to WinCC V7.5 - no documented path runs WinCC 7.2 down into flexible 2008.

On the panel side, the documented route is flexible to TIA Portal: the flexible project must be fully compiled with no errors first, the TIA installation needs the "Project migration for WinCC flexible 2008" option enabled under Migration together with the migration service, and the guide then has you remove unsupported hardware components after the import. Those steps are walked through in migrating a WinCC flexible project to TIA Portal. On the SCADA side, the documented upgrade for a WinCC 7.2 or 7.3 project is WinCC V7.5; do that after the panel work, not during it. The running system does not have to stop while you decide either - a WinCC 7.x project can be carried to another PC without a rebuild, as covered in running a WinCC 7.0 project on another PC without a new build. Decision: V7.5 is the source project's future, TIA Portal is the flexible side's future, and the MP 377 gets a rebuilt flexible project today.

How do you scope the MP 377 rebuild? #

By taking a complete inventory of the 7.2 source and giving every function an owner - the panel, the controller, or the retained SCADA - before any screen is drawn.

A SCADA project carries functions a local HMI cannot hold: historian archives, reports, batch records. Walk the source and list startup screens, navigation, process values, operator commands, alarms, trends, recipes, user permissions, controller connections, scripts, and every dependency on files or external applications. Then allocate each item with its acceptance evidence named up front. A controlled rebuild is an established migration method rather than a fallback - the write-up of how an IndraLogic migration uses a controlled ctrlX rebuild runs the same discipline on a controller change.

Source function Destination decision Acceptance evidence
Process displays Recreate values, units, status and navigation within the panel's usable screen area Live values and states match the controller
Operator commands Recreate the command and its user permission in the flexible project The intended controller action occurs once, from an authorized user
Alarms Map trigger, text, acknowledgment and reset into flexible alarm logging Each tested alarm steps through the required state sequence in runtime
Archives, trends and reports Keep history in the retained WinCC SCADA; show live values on the panel Required records stay accessible at the designated PC
Scripts and external links Redesign against flexible runtime support or move the logic into the controller Every required function has an implemented, tested destination

Decision: no required function is left without an owner, and every owner has a test that proves it.

How do you rebuild the application in WinCC flexible 2008? #

On a new project built for the exact device, not on a converted file: create the project with the MP 377 12-inch Touch selected as the target, connect it to the controller, prove that connection on one diagnostic screen, and only then expand it function group by function group.

  1. Create a new WinCC flexible 2008 project and select the exact MP 377 12-inch Touch variant installed on the machine - a visually similar device is not a substitute.
  2. Configure the controller connection from the machine documentation and the controller itself; the source project's connection names are reference material, not settings.
  3. Build one diagnostic screen holding a known read-only process value and a controller status indication, compile it clean, and transfer it to the panel.
  4. Recreate the function groups from the scoping table in the order the machine runs them: displays, then commands, then alarms, then recipes and users.
  5. Compile and transfer at every group so errors surface while their cause is still in view.

Judge nothing from the engineering screen alone: a function counts only once the rebuilt, transferred runtime shows it working, which is the trap behind WinCC flexible edits that do not show in runtime. One safety rule covers the whole rebuild: every interlock and safety function stays in the controller, and a recreated screen is an operator interface, never a safety device. Decision: expand only on top of a compiling, transferred project.

What has to match when you recreate tags, alarms and commands? #

Behavior, not names: a tag matches only when its controller address, data type, signedness, scaling, engineering units and write direction all match, and a command matches only when it produces exactly the intended controller action from an authorized user.

A wrong scaling or signedness setting produces a plausible but incorrect number, so keep a mapping list that takes every destination tag back to a named source tag and its intended interpretation. Alarm work follows the same discipline: acknowledgment records that an operator saw a message and does not by itself clear the process condition, so map trigger, text, acknowledgment and reset separately and watch each tested alarm step through its state sequence in runtime. Configure command events deliberately, including press and release behavior where the machine expects it. Rebuild screens for the panel's usable touch area instead of shrinking desktop screens into clipped, overlapping objects. Test representative values across the operating range, not one comfortable set point. Decision: acceptance is function-by-function evidence at the controller, never visual similarity.

How long does a function-by-function rebuild take? #

Plan it as bench verification time, and for a mid-size application that lands in days rather than hours - here is the arithmetic on a clearly labeled example.

Illustrative planning example, with assumed rates that are not benchmarks: suppose the inventory finds 18 screens averaging 30 objects each, 120 tags and 40 alarms. Screens: 18 x 30 = 540 objects, and verifying 15 objects per hour at the bench gives 540 / 15 = 36 h. Tags: mapping address, type, scaling and access direction at 4 min each gives 120 x 4 = 480 min = 8 h. Alarms: exercising trigger, acknowledgment and reset at 6 min each gives 40 x 6 = 240 min = 4 h. Bench verification totals 36 + 8 + 4 = 48 h, which is 48 / 8 = 6 working days - before screen layout, the connection setup from the rebuild steps, or a site acceptance test with operations. Your counted inventory and your own pace replace every rate in the example; the method - count, multiply, divide by hours per day - does not move. Decision: commit the schedule from the counted objects, and if the result exceeds the shutdown window you have, cut the object count by allocating more functions to the controller or the retained SCADA in the scoping table.

Should you reprogram the MP 377 or replace it? #

Reprogram it if the panel is healthy and you can hold a licensed WinCC flexible 2008 engineering seat, because a rebuilt flexible project is the only supported way to put the 7.2 application's functions on that terminal; replace the terminal when the hardware itself is failing or the machine is being modernized anyway.

The rebuild is not a dead end if the second case arrives later. The project you build is a real WinCC flexible project, and the same project can be carried into PC runtime - running a WinCC flexible 2008 project in PC runtime shows how. PC runtime puts the visualization on a touchscreen computer mounted at the machine instead of on the aging 12-inch terminal, which is the territory of industrial panel PCs. Decision: a healthy terminal means rebuild onto it; a failing terminal or a planned modernization means rebuild once and run the result on PC hardware.

Questions asked

Can I open the WinCC 7.2 project in WinCC flexible 2008 just to copy the screens?

No. Neither tool reads the other's project format, so there is nothing to open or copy from. Keep the source on the WinCC V7 SCADA PC and build your reference pack there: printed or exported screen lists, the tag table with addresses and data types, the alarm texts, and the user permission matrix. The rebuild in WinCC flexible 2008 follows that pack object by object.

Would WinCC flexible 2008 SP3 accept a WinCC 7.2 project where SP2 refuses it?

No. The documented rejection covers a WinCC V7.0 SP3 project into WinCC flexible 2008 SP2, and no service pack documentation for WinCC flexible adds a WinCC 7.x import. Service packs repair and extend the tool inside its own product family; they do not reverse a documented architectural incompatibility, so a newer flexible service pack does not unlock a 7.2 conversion.

Can the WinCC 7.2 SCADA keep running while I rebuild the panel project?

Yes, and it should. The SCADA PC continues to run its 7.2 project untouched while the rebuild happens in WinCC flexible 2008 on the engineering station against the same controller. Freeze the source at 7.2 for the duration so your reference pack stays valid, then upgrade the SCADA to WinCC V7.5 after the panel passes acceptance - changing both systems in the middle of a rebuild doubles your variables.

Is there any converter that turns a WinCC 7.2 project into a WinCC flexible project?

None is documented by Siemens, and anything undocumented puts an unverified translation between you and a running machine. A converter claim still has to be qualified the way this rebuild is qualified - every tag, alarm and command checked against the controller - which is the same work as rebuilding, minus the traceability. Plan the rebuild in WinCC flexible 2008 and spend the schedule on verification you can hand to operations.

Keep reading

  • How-to

    How to migrate a WinCC flexible project to TIA Portal

    One TIA Portal installation replaces both STEP 7 Classic and WinCC flexible, but the two project types move differently: the STEP 7 V5.x project is imported, and the WinCC flexible 2008 project is migrated through an intermediate release because the newest TIA Portal versions no longer offer that migration. Verify the exact S7-300 CPU and panel against the device lists and license STEP 7 and WinCC Comfort separately.

    HMI and touchscreens

  • Comparison

    WinCC V7.4, WinCC Flexible 2008 and TIA Portal Compared

    WinCC V7.x is PC-based SCADA software, WinCC Flexible 2008 engineers operator panels and single PC stations and is discontinued as a standalone tool, and WinCC inside TIA Portal is the successor engineering platform alongside STEP 7. Decide by the target device and the exact project files on your engineering workstation, not by the shared WinCC name. STEP 7 is the PLC tool, not a WinCC product.

    HMI and touchscreens

  • Troubleshooting

    Why WebIQ 2.13 Publishing Hangs After a 2.12 Project Update

    The never-moving publishing screen is a workspace lock on the ctrlX, not a slow transfer. Run the migration with Designer 2.13 against a 2.13 runtime, confirm the connection target with --ws-host and --ws-port, and read %APPDATA%/webiq-designer/designer.log for the active-workspace ApiError. The release is a restart of the complete ctrlX device; uninstalling Designer leaves the ctrlX workspace directory untouched.