HMI and touchscreens Published 5 min read

Short answer

A WinCC 7.2 project-creation failure is an engineering-tool problem on the engineering PC, not a runtime communication fault. Fix it by verifying the Windows prerequisites WinCC 7.2 requires: MS Message Queuing installed and running, English regional and language settings, an administrator launch of WinCC Explorer, and a writable project folder.

On this page
  1. Separate project creation from panel connection
  2. Work the checks in this order
  3. Decision table
  4. Example: reading one failure sequence
  5. The decision
  6. Questions asked

Why does WinCC 7.2 fail when you create a new project? Because one of the Windows prerequisites the WinCC V7.2 installation notes require is missing on the engineering PC, in this order: check that the Windows component MS Message Queuing (MSMQ) is installed and its services are running, set the regional and language settings to the English combination the installation notes require, launch WinCC Explorer as administrator, and create the project in a local folder the account can write to. Only when all of those pass does a reinstall of WinCC itself become the next step.

Separate project creation from panel connection #

Project creation initializes project files and supporting configuration inside WinCC Explorer on the engineering PC. A failure there has nothing to do with runtime communication or the panel. If a second error reports a connection failure to the panel, treat it as its own branch: identify the panel model, the engineering software and the transfer interface, then check physical connectivity, configured addressing and the panel's documented transfer state. The application already on the panel is no reason to erase it, and deleting it cannot fix a project-creation fault.

Capture the complete failure record first: the dialog title, the full message text, any error identifier, and the operation immediately before it. Note whether creation fails at once or leaves a partially created directory, and keep that directory intact for the logs it contains. Use a different project name for every test that follows so an incomplete attempt does not become a second variable.

Work the checks in this order #

  • MS Message Queuing. The WinCC V7.2 installation notes (Siemens entry ID 37437018) state that the MS Message Queuing services must be installed and that Windows security policies must be adapted. Verify MSMQ through Windows component management, not by assuming another messaging program covers it. If a required feature is missing, install it through Windows and complete the restart. Then confirm the Message Queuing service actually starts; an installed feature with a failing service is still an unresolved prerequisite.
  • Regional and language settings. Record display language, regional format and system locale separately; changing one does not change the others. The documented troubleshooting step is the English combination. Apply the combination the installation requirements specify, restart Windows when prompted, and retest.
  • Administrator launch. Membership in the administrators group does not make every process elevated. Launch WinCC Explorer explicitly as administrator. If creation succeeds only when elevated, the fault is in the account's rights on the project location, not in WinCC.
  • Project folder and privileges. Create the project in a local folder writable by the engineering account. Check free disk space and whether endpoint protection logged a block at the failure time; resolve a block through the site's approved exception process rather than leaving protection disabled. Assign only the necessary rights; never grant broad permissions to all users or take ownership of system directories.
  • Installation health, before any reinstall. Open Event Viewer and read application and system events at the recorded failure time. Review installation logs: a missing prerequisite and a failed WinCC component need different corrections, and only Siemens or an authorized distributor supplies applicable updates. Installing an unspecified update is not a diagnostic method.

Decision table #

Test and result What it proves Next action
Creation succeeds only when WinCC Explorer runs as administrator Access rights on the project location Correct the account's permissions on the project path and supporting resources
Local writable folder works, original location fails Storage or path problem Fix the original path's permissions or storage access
MSMQ feature missing or service fails to start Unmet WinCC 7.2 prerequisite Install the feature, start the service, retest before other changes
Non-English regional combination Settings conflict with the installation requirements Set the documented English combination and restart
Elevated launch plus writable local folder still fails the same way Component or installation health Return to the recorded error and the logs; only then consider reinstall

Example: reading one failure sequence #

Say the dialog appears two seconds after you confirm the new project name, and Event Viewer shows an application error at that timestamp naming a Windows component. Two facts carry the diagnosis. First, the failure occurred after WinCC Explorer began writing project files, so the shell works and the fault sits in a prerequisite the notes require, such as the MS Message Queuing services. Second, a named component in the event beats every other candidate: check that component's service state before touching regional settings or permissions. If the service starts and creation now completes, the decision is closed. If the service starts and the same error remains at the same two-second point, the decision moves to the last table row: elevated launch and a writable local folder, then installation logs, and only then a reinstall.

The decision #

Fix prerequisites before software: MSMQ installed and running, English regional combination, administrator launch, writable local project folder. Retest project creation after each single change. When every check passes and the same error persists with the same recorded message, the WinCC 7.2 installation itself is the remaining suspect, and reinstalling from the authorized medium is justified. The panel and its existing application stay untouched throughout; once a project is created successfully, troubleshoot the connection error separately along the transfer path.

Before replacing the engineering workstation or an aging terminal, it is worth checking HMI engineering software compatibility first; the same ordered check applies there.

Questions asked

Do I need to delete the program already on the panel to fix this?

No. The project-creation error happens in WinCC Explorer on the engineering PC before any project exists, so nothing has changed on the panel and nothing there needs to be erased. A connection error to the panel is a separate diagnostic branch about the transfer path. First create a valid project on the PC, then troubleshoot the transfer with the panel and its existing application left intact.

Why must regional and language settings be English for WinCC 7.2?

WinCC 7.2's installation requirements expect an English combination of Windows regional format and language settings; other combinations can break project file initialization with errors that do not name the locale as the cause. Set the display language, regional format and system locale to the combination the installation notes specify, restart Windows if it asks, and only then retest creating a project.

Should I turn off the Windows firewall to fix project creation?

No. Project creation is a local operation on the engineering PC and involves no network traffic, so the firewall is not the cause unless the recorded error explicitly names a blocked connection. Disabling the firewall indiscriminately removes a protection without addressing a local file or component fault. If the error and logs do identify a blocked connection, apply one narrowly scoped rule instead.

Keep reading

  • Explainer

    Can You Migrate a WinCC 7.2 Project to WinCC Flexible

    No migration path converts a WinCC 7.2 project into WinCC flexible 2008; Siemens documents the two as architecturally incompatible, and the documented directions run the other way - WinCC flexible into TIA Portal, and WinCC 7.2 up to WinCC V7.5. Treat the MP 377 12-inch Touch application as a new WinCC flexible project: inventory every function, rebuild it item by item, and verify each one on the bench.

    HMI and touchscreens

  • How-to

    Running a WinCC 7.0 project on another PC without a new build

    No. WinCC has no compile-to-EXE option: the destination PC needs WinCC Runtime of version 7.0 or higher, installed and licensed, and you transfer the project files to it. A newer WinCC opens and converts the project; an older release will not open it.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC 7.5 Runtime Fails Under a New Windows User

    Runtime failing under a newly created Windows account while Explorer opens is a Windows security-context problem, not a WinCC project problem. Put the account in the SIMATIC HMI group, sign out fully, verify effective access to the project, and after an Admin password change update the logon identities of services and scheduled tasks.