Comfort Panel viewer print option disabled: the viewer, not the driver

HMI and touchscreens Published 5 min read

Short answer

The disabled Print command is a limitation of the Comfort Panel office viewer, which has no print function; no driver or ProSave action can enable it. Print HMI-generated reports through the configured report action, capture the visible screen with PrintScreen, or print a copied spreadsheet off the panel.

On this page
  1. Where the chain actually breaks
  2. What the installed driver is for
  3. The three output paths, and when each one applies
  4. Worked example: a copied Excel sheet on a TP700 Comfort with PostScript V1.3 installed
  5. Making the hardcopy path work
  6. Questions asked

The Print command is greyed out because the office viewer on a Comfort Panel has no print function, not because the printer driver is missing or wrong. PostScript V1.3 installed through ProSave and selected under Control Panel > Printers serves the HMI application's own print output: configured report actions and the PrintScreen hardcopy. No driver reinstall, Control Panel setting or firmware change enables printing inside the viewer. Decide by what you need on paper. An HMI-generated report goes through its report print action, the visible screen goes through PrintScreen, and a complete copied spreadsheet can only be printed off the panel.

Where the chain actually breaks #

A print job passes through three stages: the application must offer Print and produce printable output, the driver must translate that output into the printer's page-description language, and the printer must put it on paper. A greyed Print command stops the chain at the first stage. The driver and the printer are never reached, which is why the same greyed command survives every driver change.

The office viewers on Comfort Panels are viewers: they render copied documents but have no print function wired to anything. Reinstalling PostScript V1.3 through ProSave, re-selecting the driver in Control Panel > Printers, or adjusting printer settings in the Start Center changes the panel's printing subsystem, not the viewer's command set. That distinction decides the whole diagnosis: an unavailable command is an application limitation, while a failed print job after an accepted request is a driver, connection or printer problem.

What the installed driver is for #

PostScript V1.3, installed through ProSave and selected in Control Panel > Printers, belongs to the panel's print subsystem. It translates print output that reaches that subsystem: report actions configured in the HMI project and screen hardcopies triggered by PrintScreen. It is a correct and necessary part of both of those paths, and it is irrelevant to the viewer.

So keep the driver installed. Removing it or switching the Printer Language entry would break the report and hardcopy paths while still leaving the viewer greyed out. The fix for the viewer case is never in the driver settings; the fix is choosing an output path the panel actually supports.

The three output paths, and when each one applies #

  • An HMI-generated report: build the report in the TIA Portal project and print it through its configured report print action. This is the supported path for shift reports, alarm logs and tag archives, and the only path that paginates data beyond one screen.
  • The visible screen: assign the PrintScreen system function to a button or event. It prints the screen currently displayed from the printer connected to the HMI device. Use it when every value the record needs is on screen.
  • A complete copied spreadsheet: the panel cannot print it. Open the file on a workstation with a spreadsheet application and print there; a copied document is not an HMI object, so no panel setting turns it into one.

For archiving rather than paper, the panel's supported print output can also be written as PDF files on its storage; the setting lives in the printer properties and is described in the answers below.

Worked example: a copied Excel sheet on a TP700 Comfort with PostScript V1.3 installed #

The inputs, all from the reported case: a TP700 Comfort; PostScript V1.3 installed through ProSave and selected in Control Panel > Printers; an Excel file copied to the panel and opened in the office viewer; the Print command greyed out.

The rule in words: a greyed Print command fails the printing chain at its first stage, before the driver enters the picture, so the driver and its settings cannot influence the outcome.

The arithmetic on the routes: the panel offers three candidate outputs for the content of that file — the viewer's Print command, the PrintScreen hardcopy and the HMI report action. The viewer command is unavailable, so 3 − 1 = 2 routes remain: the hardcopy and the report action. Zero attempts through the viewer can succeed, whatever the driver says.

The result: Print stays disabled in the viewer, and the driver is confirmed healthy for its own paths.

The decision, with its threshold: if every value the record needs is visible in one view on the panel, the PrintScreen hardcopy satisfies it; if any value sits off-screen or on another worksheet tab, the hardcopy is not equivalent and the record must come from a report action or from a workstation. For this case — a full Excel worksheet — the decision is: print it off the panel, because the viewer path is closed by design.

Making the hardcopy path work #

In the TIA Portal project, place a button on the screens that matter and assign PrintScreen to it, then transfer the project and test on a bench printer before relying on it at the machine. The output is a picture of the displayed screen: it shows exactly what is visible and nothing else.

The page setup is configurable. If the hardcopy comes out wrong for your paper, the layout options are covered in configuring the WinCC runtime hardcopy landscape print layout. If the capture should be triggered from logic rather than a button, the same job can be done with a WinCC VBScript hardcopy button that triggers a screen capture via script.

The destination printer must process what the panel sends: keep PostScript V1.3 selected only when the connected printer handles PostScript, and check the configured connection in Printer Properties, opened through the Printer icon in the Start Center settings. If a valid print request produces no paper, the checks in why a Comfort Panel will not print to a Brother label printer on USB cover the printer side; the viewer command itself remains out of reach on purpose.

Questions asked

How do I produce a PDF file on a Comfort Panel instead of a paper printout?

Start the Printer application from the Control Panel, open Printer Properties, and select PDF V1.3 under Printer Language. The panel then writes its print output as PDF files on its own storage instead of sending paper to a printer. Copy the files off the panel on a USB stick or memory card and print or archive them on a workstation. This works for the panel's supported print paths; it still does not add a Print command to the office viewer.

The driver is installed and selected, but the printer produces nothing. What now?

That is a different fault from the greyed viewer command, and it lives downstream of an accepted print request. First check that the destination printer actually processes PostScript, because PostScript V1.3 output sent to a printer without PostScript support yields nothing or garbled pages. Then check the configured connection and printer status in Printer Properties, opened through the Printer icon in the Start Center settings. Test from a supported path such as a report action or PrintScreen, never from the office viewer.

I only need the Excel sheet occasionally. Is there any way to print it on the panel?

No. The office viewer has no print function, so the panel cannot print that file. Copy the file from the panel's storage on a USB stick or memory card to a workstation, and print it there with full pagination. If operators need those values at the machine on paper regularly, build them into an HMI report or onto a screen the PrintScreen hardcopy can capture. That gives a repeatable print path instead of depending on a viewer command that does not exist.

Keep reading

  • Troubleshooting

    Why ProTool Lite Cannot Open a TP270 Project It Does Not Support

    A TP270 project that will not open in ProTool is blocked by the editor edition: ProTool Lite does not support the TP270 target. Installing the full ProTool edition, reported working at version 6.0, opens the project before any PLC or transfer diagnosis is needed.

    HMI and touchscreens

  • Troubleshooting

    Fixing a fatal error installing Unified Comfort Panel V17 images

    The fatal-error dialog from the Unified Comfort Panel V17 image installer usually means the copy step failed after extraction, not a corrupt download. Verify the package's SHA-256 checksum, run the installer as administrator with TIA Portal closed, and if it still aborts, use its extract-only option and copy the image files into the TIA Portal V17 image folder by hand.

    HMI and touchscreens

  • Explainer

    RFID card login on a Comfort Panel with PM-LOGON Basic

    PM-LOGON Basic, supplied inside the free SIMATIC HMI Option+ package, adds RFID card login to a SIMATIC Comfort Panel through a SIMATIC RF1000 reader on the USB interface, and user administration stays local on the panel. Binding a card UID to a Windows user belongs to full PM-LOGON with SIMATIC LOGON, which is a different product and a different account architecture.

    HMI and touchscreens