RFID card login on a Comfort Panel with PM-LOGON Basic

HMI and touchscreens Published 7 min read

Short answer

PM-LOGON Basic, supplied inside the free SIMATIC HMI Option+ package, adds RFID card login to a SIMATIC Comfort Panel through a SIMATIC RF1000 reader on the USB interface, and user administration stays local on the panel. Binding a card UID to a Windows user belongs to full PM-LOGON with SIMATIC LOGON, which is a different product and a different account architecture.

On this page
  1. What PM-LOGON Basic actually is
  2. Local accounts or a central Windows identity
  3. Worked example: the decision for three identical Comfort Panels on one operator list
  4. What the RF1000 requirement covers, and what it does not
  5. What else Option+ installs on the panel
  6. Commissioning order that avoids dead ends
  7. Questions asked

RFID login on a SIMATIC Comfort Panel is not a hidden panel setting; it exists only through PM-LOGON software, and there are two different products behind that name. PM-LOGON Basic, supplied inside the free SIMATIC HMI Option+ package, adds card login through a SIMATIC RF1000 reader connected to the panel's USB interface, and the panel's user administration stays exactly where it was: local on the panel. The card-UID-to-Windows-user assignment most engineers expect when they hear "RFID login" is the full PM-LOGON product working together with SIMATIC LOGON. Decide the account architecture first; the software choice follows from it in one step.

What PM-LOGON Basic actually is #

PM-LOGON Basic is a login convenience layer for the panel: an operator presents a card to a reader and the panel logs in the assigned local user, instead of somebody typing a user name and password on the touch screen. Siemens documents that, with PM-LOGON Basic integrated through SIMATIC HMI Option+, RFID user identification can be configured and commissioned on the operator panel in a few steps.

Three restrictions come with the Basic route, and each one matters when you specify the system:

  • The reader must come from the SIMATIC RF1000 RFID system. USB is the connection interface, not a compatibility certificate; a reader that enumerates on the USB bus or delivers a card number to some application is not automatically able to work with the login software.
  • The user administration stays local on the panel. The card is bound to a panel account, and the panel account database remains the authority for who may operate what.
  • PM-LOGON Basic is delivered as part of SIMATIC HMI Option+, so installing a reader alone is not the complete configuration; the Option+ package has to be on the panel as well.

Card compatibility is a separate decision from reader compatibility. The RF1000 family covers several card standards, but the right reader family does not make every RFID credential usable; check the specific card your plant issues against the reader's documentation before you commit to it.

Local accounts or a central Windows identity #

The full PM-LOGON product does something Basic does not: it enables the assignment of the unique identifier (UID) of an RFID card to a Windows user, in conjunction with SIMATIC LOGON. SIMATIC LOGON is a tool for system-wide user administration; when you use it, users are managed centrally outside the application or HMI device. The full solution is documented as consistent across SIMATIC HMI systems from Comfort Panel through WinCC RT Advanced and Professional.

Question PM-LOGON Basic Full PM-LOGON with SIMATIC LOGON
Where the users live Local on each panel Centrally managed outside the HMI device
What the card is bound to A panel user account The card UID, to a Windows user
Documented HMI scope SIMATIC Comfort Panel Comfort Panel through WinCC RT Advanced/Professional
How it is supplied Inside the free SIMATIC HMI Option+ package Separate full-version solution
Reader for a panel install SIMATIC RF1000 system reader on USB Per the full solution's system description

One question the thread around this topic raises deserves a direct answer: pointing at a RADIUS server, including SINEC INS as a proposed server, does not create a documented client path from PM-LOGON Basic. A workable design needs documented support at both ends and a defined credential exchange. For central identity on these panels, the documented route is full PM-LOGON with SIMATIC LOGON, not a RADIUS arrangement bolted onto the Basic package.

If you currently create and retire panel accounts by hand, the workflow for WinCC runtime user accounts and password changes on the runtime side is the same discipline the panel accounts need; see managing WinCC runtime user accounts and password changes for how that looks on a WinCC runtime system.

The decision. One panel whose accounts belong to the machine: PM-LOGON Basic, and nothing else is needed. Any requirement that one operator identity work across several panels, or that the card tie to the plant's Windows accounts: full PM-LOGON with SIMATIC LOGON.

Worked example: the decision for three identical Comfort Panels on one operator list #

The architecture question usually arrives when the second line is added, so take that case. The inputs:

  • Three identical Comfort Panels (example assumption; the thread's own case is one panel, and for one panel the answer is simply Basic).
  • One shared operator roster, twelve operators for example, one card per operator.
  • One account change per event: a new hire, a role change or a departed operator is one user edit, made wherever that user's account lives. This follows from the documented fact that PM-LOGON Basic keeps user administration local on each panel, so each panel owns its own user database.

The rule in words: with PM-LOGON Basic, one account change costs one edit per panel, because the account exists separately on every panel; with full PM-LOGON and SIMATIC LOGON, the users live centrally, so the same change costs one edit in total.

The arithmetic. Per account change under Basic: 1 change × 3 panels = 3 edits. Over a year with, for example, 24 account changes: 3 × 24 = 48 edits. Under the central arrangement: 1 × 24 = 24 edits. Card issuance is identical either way: 12 operators × 1 card = 12 credentials.

The result: 48 edits a year versus 24 in this example, and the difference is not only workload. With local databases, retiring a departed operator means finding every panel that still holds that account; miss one and the card still logs in on that machine. The threshold: at N = 1 panel, Basic; at N ≥ 2 panels sharing one operator list, or whenever a card must bind to a Windows account, full PM-LOGON with SIMATIC LOGON.

What the RF1000 requirement covers, and what it does not #

The reader restriction is a hard boundary, and it is worth knowing what it does not say. It does not say that any reader the panel recognizes is usable; it says the login software works with the SIMATIC RF1000 system, which includes USB readers such as the RF1060R in that family. When card detection fails, work from the physical connection upward: cable and USB port first, then reader recognition on the panel, then the card itself. Editing panel users cannot correct a reader that never delivered a credential, so establish a repeatable card-detection event before you investigate accounts or permissions at all.

Before commissioning, confirm the reader's supported card standards against the credentials your plant issues, and confirm the Option+ package documentation against the exact panel and its software image. Preserve the project and account configuration before any package install or update that could replace local settings.

What else Option+ installs on the panel #

SIMATIC HMI Option+ extends the Comfort Panel and serves as a gateway between the panel operating system and the WinCC Runtime executing the HMI application. One of its other functions writes system information such as the IP address, device information and memory utilization into internal HMI variables via OPC UA, so the HMI application can read and display it.

Keep that function clearly separated in your head during commissioning: a device-info value on the screen that matches the panel's own settings proves the OPC UA data path works, and proves nothing about RFID authentication. They are different paths through the same package.

Commissioning order that avoids dead ends #

  1. Create the panel user accounts and their operating permissions in the panel's local user administration first. Verify one permitted and one restricted operation per test account before any card is involved.
  2. Install SIMATIC HMI Option+ with PM-LOGON Basic per the package documentation for your panel and software image.
  3. Connect the SIMATIC RF1000 reader to the panel's USB interface and confirm the reader is recognized without a connection error.
  4. Present a compatible test card and confirm a repeatable detection event on the reader or in the login diagnostics.
  5. Associate the test credential with the local test user through the PM-LOGON Basic workflow supplied with the package, then confirm that presenting the card selects the intended panel user.
  6. Test the boundary: a permitted operation succeeds, a restricted operation stays blocked, and a card with no assigned user gains no privileges. User management can behave differently on the real panel than in engineering simulation, which is exactly the gap the article on HMI user management working in simulation but not on the panel walks through.
  7. If the PLC should know who is logged in, the active HMI user can be forwarded to the controller; the way login macros send the active HMI user to the PLC is covered in sending the active HMI user to the PLC with login macros.

Card login is a convenience and accountability layer: the panel's own user access protection still governs what each logged-in user may operate, and no card workflow replaces the machine's safety functions.

Questions asked

Which card types does the SIMATIC RF1000 reader family read?

The RF1000 family is documented to support card standards including ISO 15693, ISO 14443, MIFARE, LEGIC, HID iClass and FeliCa. Reader compatibility and card compatibility are separate decisions: confirm the exact card or token your plant wants to issue against the specific reader's documentation before ordering credentials, because the right reader family does not make every RFID card usable with the login function.

Can PM-LOGON Basic assign a card UID to a Windows user?

No. UID-to-Windows-user assignment is a function of the full PM-LOGON product working together with SIMATIC LOGON, which manages users centrally outside the HMI device. With PM-LOGON Basic the user administration remains local on the panel, so the card is bound to a panel account, not to a Windows or domain identity.

Will any USB RFID reader that shows a card number work?

No. The documented login route on a Comfort Panel with PM-LOGON Basic is restricted to readers of the SIMATIC RF1000 RFID system connected over USB. A reader that enumerates on USB or delivers a card number to some application is not automatically compatible; the login software is built for that reader family, not for arbitrary HID keyboard-wedge card readers.

Can SINEC INS act as a RADIUS server for panel card login?

Naming a RADIUS server, including SINEC INS, does not establish a documented client connection from PM-LOGON Basic. A usable design needs documented support at both ends and a defined credential exchange, and no such path is documented for PM-LOGON Basic. If the requirement is central identity, the documented route is full PM-LOGON with SIMATIC LOGON.

What else does SIMATIC HMI Option+ install besides RFID login?

Option+ extends the Comfort Panel and acts as a gateway between the panel operating system and WinCC Runtime. That data path is separate from the RFID login function.

Keep reading

  • Explainer

    PowerTags vs the variables per device limit in TIA Portal HMI

    The variables per device limit in a panel's technical data counts every entry in the HMI tag tables, internal tags and PLC-linked tags together. A PowerTag is only a tag with an external link and is a PC runtime licensing counter, so size the project from the compile log's total tag count. The compiler can finish an over-limit build without a warning, so compare the counts yourself.

    HMI and touchscreens

  • How-to

    Migrating a WinCC PC Runtime project to a Comfort panel

    There is no whole-project conversion from a WinCC PC runtime station to a TP1500 Comfort panel. Copying screens inside TIA Portal is supported, but each object, faceplate and system function must be dispositioned and reconfigured for the Comfort system. Advanced sources transfer with the least rework, Professional sources need object-by-object reconciliation, and a Unified source should move to a Unified Comfort panel instead of being converted.

    HMI and touchscreens

  • How-to

    Unified Comfort Panel image updates when two versions are needed

    TIA Portal can hold only one installed panel image per major version and device type, so installing the V21 Update 2 image overwrites Update 1 on the engineering PC. Upgrade every affected panel to Update 1 first, then install Update 2, or extract image packages to separate folders and install them per panel through ProSave or USB.

    HMI and touchscreens