There is no whole-project conversion from a WinCC PC runtime station to a TP1500 Comfort panel. Copying screens inside TIA Portal is supported, but each object, faceplate and system function must be dispositioned and reconfigured for the Comfort system. Advanced sources transfer with the least rework, Professional sources need object-by-object reconciliation, and a Unified source should move to a Unified Comfort panel instead of being converted.
On this page
- Identify the source edition before anything else
- Match the device version before you copy anything
- Copy screens through the supported path
- Give every object one of four dispositions
- Rebuild faceplates instead of pasting them
- Reconfigure system functions and events
- Prove it on one pilot screen, then scale
- The decision, by source edition
- Questions asked
A WinCC project engineered for a PC runtime station does not convert as a whole to a TP1500 Comfort panel, and no tool performs that conversion. What does exist is a supported screen copy path inside TIA Portal plus a per-object reconciliation that you do yourself. The edition the source project was built in decides how much survives the copy, so the first job is to identify it. A pasted screen that comes out "disconfigured" is the expected result of skipping that step: the copy works, but objects carry source properties the Comfort system does not support.
Identify the source edition before anything else #
- Open the source project in its engineering environment. If it opens in TIA Portal with a PC station configured as RT Advanced or RT Professional in the device view, note which one it is. If it needs the Unified engineering environment, it is a Unified project. If it opens in the classic WinCC Explorer rather than TIA Portal, it is a classic WinCC V7 application.
- Record the edition and the engineering version. Both determine the copy behavior and the device versions available to you.
- Commit to the route that matches the result, because the four editions are not variations of one migration:
- RT Advanced source: closest to the Comfort system. Screen copying between the devices is a documented operation and most objects transfer; plan light reconfiguration.
- RT Professional source: a more elaborate architecture than the Comfort HMI system. Plan an object-by-object reconciliation; some controls exist only in Professional.
- Unified source: there is no supported conversion to Comfort. Change the hardware decision to a Unified Comfort panel and keep the project; do not rebuild it.
- Classic V7 source: the TIA Portal copy path does not apply. Rebuild the application from its requirements.
If the editions blur together on your desk, the differences between the classic explorer, Advanced, Professional and Unified are sorted out in WinCC Explorer vs Advanced, Professional, Flexible and Unified.
Match the device version before you copy anything #
- Check the device version of the Comfort panel in the project against the image version on the physical panel. The image installed on the panel must be compatible with the runtime version configured in the project, or the load will be refused.
- If you raise the device version in the project to match a newer panel image, TIA Portal runs an adaptation of the device on the existing configuration. Answer its prompts and confirm the object list afterwards; a failed adaptation on a Comfort panel is its own fault with a known set of causes, covered in resolving adaptation of target device failed on a TP700 Comfort.
- Only after the target device is consistent do the screen copies mean anything. A paste onto an unadapted device proves nothing about the final project.
Copy screens through the supported path #
- Copy one or more screens from the "Screens" folder of the source device and paste them into the "Screens" folder of the Comfort device. This is the documented copy operation between the devices; dragging objects individually onto an open screen is not the same thing and drops more configuration.
- Create the tag tables and the PLC connection on the panel first. A pasted object keeps its configuration only where the referenced tags exist on the target; otherwise the connection fields come across empty.
- Inspect the pasted screen immediately, object by object, against the source: connections, limits, texts, event configuration. Judge the configuration, not the picture. A screen that looks almost identical can still be missing the settings that made it work.
- Anything that did not survive the paste goes on the disposition list in the next section; do not fix it ad hoc on the first screen.
Give every object one of four dispositions #
Walk each source screen and classify every object as reusable (supported on Comfort, transfers intact), reconfigurable (exists on Comfort but needs different properties or behavior), replaceable (no direct equivalent, but a Comfort object does the same job), or redesign (Professional-only control or structure with no counterpart). A planning count turns that list into hours. Example arithmetic, with inputs from a hypothetical plant project:
- Screens: 38, averaging 24 objects each, so 38 × 24 = 912 objects total.
- The pilot screen found 8 of its 24 objects needing work (6 reconfigure, 1 replace, 1 redesign), so 8 / 24 = 33 % of objects need attention.
- Estimated rework: 912 × 8 / 24 = 304 objects.
- At 15 minutes per reworked object: 304 × 15 min = 4 560 min = 76 h, plus verification at 0.5 h per screen: 38 × 0.5 h = 19 h.
- Total: 76 h + 19 h = 95 h of engineering before commissioning.
Those percentages are example planning inputs, not measured compatibility rates; substitute the counts your own pilot produces.
Rebuild faceplates instead of pasting them #
- List every faceplate in the source. Professional faceplates belong to "types" whose structure differs from Comfort faceplates, including the settings shown in the Screen Manager. Pasting the graphic transfers the picture, not the type definition or runtime behavior behind it.
- For each faceplate, capture what it must do: its tag connections, its dynamic properties, and how screens instantiate and pass values to it.
- Model a Comfort faceplate that meets those requirements, then update every screen that instantiated the old one to use the new version. Budget this as redesign, not reconfiguration, for a Professional source.
- Make a faceplate-heavy screen your first pilot. If it adapts cleanly, the rest of the faceplate set is routine; if it does not, you have found the real cost of the migration before touching the other 37 screens.
Reconfigure system functions and events #
- List the system functions the application actually uses: screen navigation, scripts, tag-based triggers, user administration, alarms, recipes, logging.
- Some functions configured on a Professional source exist only there, or behave differently on Comfort. For each configured event, confirm that the target offers the function and test the result, not just the presence of the dialog.
- Where no direct equivalent exists, redesign the action from Comfort-supported functions. The object can look identical while its event now invokes the wrong behavior, so recheck every event after the switch.
Prove it on one pilot screen, then scale #
- Pick the screen that exercises the widest spread of what the application uses: an animated object, a faceplate instance, a scripted event, an alarm view.
- Copy it, disposition its objects, rebuild what failed, and load it to the panel with verified test tags on an isolated bench. Test the writes, the navigation and the events.
- Use what the pilot produced to fix the per-object effort, then run the remaining screens from the disposition list in batches, verifying each batch on the panel before starting the next.
The decision, by source edition #
- Advanced to Comfort: commit to the copy-and-reconfigure route. Screen copying is supported, most objects transfer, and the pilot tells you the residual hours within a day.
- Professional to Comfort: commit to a partial rebuild. Reuse the screens that pass the disposition list, redesign faceplates and Professional-only controls, and price the job with the object count method above — in the worked example, 95 h for 912 objects.
- Unified to Comfort: do not convert. Put a Unified Comfort panel at the machine and keep the project intact.
- Classic V7 to Comfort: rebuild from requirements; for the version background see WinCC V7.4, WinCC Flexible 2008 and TIA Portal compared.
Whichever route applies, copy-and-paste is a labor-saving step inside a conversion, never the conversion itself.
Questions asked
Does pasting a screen bring its tag connections across?
The paste carries the object configuration, but every referenced tag must already exist in the target panel's tag tables. Missing tags leave the connection fields empty after pasting. Copy or recreate the tag tables and the PLC connection on the panel first, then paste the screens and rebind whatever dropped.
Can the PC runtime and the new Comfort panel read the same controller?
Yes. Each runtime polls the PLC over its own connection, so both stations can display and write the same tags. Count both connections against the controller's documented connection resources, and add an interlock or handover rule so an operator at one station cannot silently overwrite a setpoint written at the other.
Which engineering license do I need to build the Comfort project?
Programming a Comfort panel requires at least the WinCC Comfort engineering license. If you already hold the WinCC Advanced or Professional engineering license, that covers it, because they are the higher tiers of the same TIA Portal family. WinCC Unified is licensed separately and does not include Comfort engineering.
Is there a tool that converts a Unified project to Comfort?
No supported conversion exists between the Unified engineering world and the Comfort system. Moving a Unified application onto a Comfort panel is a from-requirements rewrite. If your source project is Unified, keep the project and put a Unified Comfort panel at the machine instead of converting it.