How-to
HMI Replacement: Recover the Project Before Converting
Short answer
Back up the editable project and the complete hardware reference first, then convert a copy, clear every conversion warning, and commission in stages: project transfer, verified reads, and only then operator commands. The end-of-2026 discontinuation date for the old series sets when to order, not whether the new panel drops in.
On this page
- What does a 2026 end-of-life date actually decide?
- Should I redraw the screens or reuse the old project?
- How do I recover the editable project from the old panel?
- What do I record before I disconnect the old panel?
- How do I convert the project to the replacement model?
- What breaks when the new panel has more pixels?
- Will the replacement fit the existing cut-out?
- How do I commission the new panel in stages?
- Questions asked
Swap the panel only after the editable project is recovered, backed up, converted on a working copy, and commissioned in stages — in that order. The GP4000-series discontinuation planned for the end of 2026 is a procurement deadline, not a compatibility guarantee: it fixes when to order, not whether the replacement drops in. The steps below cover recovery, conversion, warning review, physical fit, and a transfer-then-reads-then-commands startup.
What does a 2026 end-of-life date actually decide? #
It decides your order date, nothing else: the announced end-of-2026 sales stop for the GP4000 series means the replacement should be ordered and commissioned before then, while installed panels keep running regardless of the date.
The announcement promoting the GP6000 series as the successor — with project reuse, a GP4601T-to-GP6600T replacement path, higher resolution and 16 million colors — is a reason to plan, not proof of fit. Discontinuation is a commercial event: spares and repair options shrink after it, and screens do not go dark. Whatever the brand, the date belongs in a lifecycle check first, the same first step as checking PanelView 5000 lifecycle status before an HMI replacement.
The decision: a replacement proven and commissioned before the end of 2026, or a shelved spare of the installed model and a later migration on your own schedule.
Should I redraw the screens or reuse the old project? #
Reuse the recovered project; redrawing is the expensive path and the lossy one, because alarms, recipes, security levels, scripts and device mappings live below the visible screens and rarely survive a manual rebuild.
Three shortcuts waste time on this job. Do not redraw first: manual recreation drops alarm behavior, recipes, security levels, scripts and device mappings that are less visible than the screens. Do not change PLC addresses to cure a transfer failure: project download and runtime communication are separate functions, so diagnose the failed connection before editing either side. Do not order by front appearance: a similar bezel proves nothing about the hole, the connectors or the supply.
Beyond those, change only what the replacement genuinely requires, so that any fault found at commissioning has one variable. The decision stands even when the new series is advertised as an easy upgrade: the recovered project is the conversion input, and a feature is redrawn only when the conversion demonstrably cannot carry it.
How do I recover the editable project from the old panel? #
Find the editable source on the engineering PC or in backups first, and treat anything uploaded out of the panel as suspect: a runtime copy with the right file name is not proof it matches the running application.
Know which kind of file you hold — a separately stored editable source, a device restore backup, or an export of selected data — because only the editable source converts cleanly, and why an uploaded HMI copy is not an editable project covers that distinction in detail. Compare the candidate file's screens and settings against the installed panel before trusting it. If the source is gone, use the recovery path the vendor documents for the exact tool and target, and check whether the panel itself holds recoverable project data. Where a vendor documents moving the project memory card into an identical model, that is the fast like-for-like swap path, not a migration path.
Recipes, logs and retained operator settings are runtime data: export them separately from the project backup, and complete both before anything is disconnected. If no editable application can be recovered, resolve that first — screen photographs capture appearance, not hidden logic or device mappings.
What do I record before I disconnect the old panel? #
Record the complete installed reference and configuration while the panel still runs, because every later decision — ordering, conversion, wiring, commissioning — is checked against what you write down at this step.
- The panel's full ordering reference, option modules included, and the engineering software version the project opens in.
- Communication settings for every connected device: driver, interface, addressing, baud or IP details, and any gateway in the path.
- An inventory of alarms, recipes, retained operator settings, security users and scripts.
- Connected peripherals — printers, readers, drives — and the ports they use.
- Runtime data needing separate export, with the export date noted.
- Photographs of the wiring and the running screens, cables labeled at both ends.
- The as-built mounting: cut-out, front dimensions, clamp positions, rear service clearance.
- The untouched project backup, stored where the conversion cannot reach it.
How do I convert the project to the replacement model? #
Convert a working copy inside an engineering environment that officially supports the new target, save the result as a separate project, and do not close the conversion until every warning is either resolved or explicitly accepted.
- Confirm the engineering environment supports the exact target model and firmware — the tool-by-tool walk-through is checking HMI engineering software before a panel replacement.
- Open the working copy and change the target through the supported operation. In EasyBuilder Pro the target sits in "System Parameter Settings" on the "Model" tab, where a project is moved to a listed model such as "MT8071iE / MT8101iE (800 x 400)".
- Save the converted project under a new name; the original stays untouched for rollback.
- Work the warning list item by item, separating automatic substitutions from functions that need manual rework, and use the vendor's generation-conversion guide when one is published for your model pair.
- Check drivers, device addresses, data types, scripts, alarm conditions and recipe mappings against the configuration recorded before disconnection.
- Build and validate — then read a clean build for what it is: the project suits the engineering environment, and nothing is yet proven about the installed cable, the controller's response, or what an operator command does to the machine.
What breaks when the new panel has more pixels? #
The pixel grid breaks first: moving a project to a screen with a different resolution stretches, letterboxes or re-anchors it, and a height factor as small as 1.20 moves every touch target operators had memorized.
Worked example, with the replacement resolution chosen to illustrate: "MT8071iE / MT8101iE (800 x 400)" is a real listed target, so take an 800 x 400 project and an 800 x 480 replacement.
- Aspect ratio: 800 ÷ 400 = 2.00, against 800 ÷ 480 ≈ 1.67 — same glass width, different shape.
- Stretched to fill: height factor 480 ÷ 400 = 1.20, so a 12-pixel text row becomes 12 × 1.20 = 14.4 px and a 1-px separator becomes 1 × 1.20 = 1.2 px; fractional scaling rounds some edges to one pixel and their neighbors to two.
- Anchored top-left: 480 − 400 = 80 px of dead band, and a full-height bar covers 400 ÷ 480 ≈ 83% of the glass.
Neither landing is acceptable unreviewed. Walk every converted screen and re-touch every target. Sizing that review is arithmetic, not guesswork: 40 screens at five minutes each is 40 × 5 = 200 minutes, one bench shift, before the panel is wired to anything. The 16 million colors on the new series change none of this; the pixel grid does.
Will the replacement fit the existing cut-out? #
Not unless the drawings say so: match cut-out, front dimensions, mounting hardware and rear service clearance against the opening before ordering, because a similar bezel has never guaranteed the same hole.
Compare complete ordering references, not series names: supply requirements and terminal arrangement, grounding, communication ports, peripheral connectors, and the enclosure rating the location demands — a washdown area and an outdoor post each need their own documented rating, and one rating never implies another. Where the existing opening is the constraint, line both dimension sets up against a panel cut-out reference before the order goes in. If the cut-outs differ, machining the door or making an adapter plate becomes a planned work item with its own drawing, not a surprise on changeover day.
How do I commission the new panel in stages? #
In three bounded stages — transfer the project, verify live reads, then test operator commands one at a time — so any failure lands inside one stage instead of somewhere across the whole swap.
Wire and install to the replacement model's instructions, matching documented terminal functions rather than connector appearance, then run the stages in order:
- Transfer the validated project and confirm the intended startup screen loads.
- Establish communication and verify reads: open runtime diagnostics before touching any address, compare displayed values against independently observed controller values, and include values that are changing so stale data cannot pass for live. Configure read-error behavior here; engineering tools expose a per-symbol setting for it, and Beckhoff's documented "Symbol Read Error Handling" includes a "Reset" option that resets the control attribute, so a dead driver shows a defined state instead of a frozen good number.
- Test operator commands last, lowest-risk first, one at a time. Treat every command test as a machine actuation: gate it behind the machine's lockout and safety procedure, with nobody exposed to what the command moves.
Finish by updating the as-built record — new ordering reference, firmware version, converted project archive, communication settings — and keep the old panel as the rollback until the machine has completed a full production cycle on the new one.
Questions asked
Can I just move the memory card from the old panel to the new one?
Only where the vendor documents card-based device replacement for that exact model pair, and it is a like-for-like swap path, not a migration path. A series change still goes through the engineering software: convert a copy, clear the warnings, and commission in stages. Even a documented card swap gets its startup screen and communications verified before the machine returns to service.
Do I need to change the PLC program when the HMI is replaced?
Normally no. The controller does not know which panel is talking to it, so keep the PLC side frozen and any commissioning fault has one variable. Change the PLC program only when the replacement cannot speak the existing protocol at all, a serial-only panel replaced by an Ethernet-only model for example, and then treat that protocol change as its own tested work package, not a side effect.
Should I update the replacement panel's firmware before transferring the project?
Transfer onto the firmware version the converted project was validated against, not the newest posted release. Mismatched runtime and firmware versions are a common cause of transfer failures and of objects that behave differently on the glass. If an update is needed later, do it deliberately and re-run the three commissioning stages afterward. Write the version into the as-built record.
What if I cannot get a migration done before the old series stops shipping?
Buy one spare of the installed model before sales stop and shelve it. That converts the deadline into a planned project instead of an emergency, because the expensive outcome the date warns about is a failed panel with no spare and no migration. Then migrate on your own schedule with the recovered project already in hand.