IMDTouchKnowledge BaseShop main store

Selection guide

Is a TP277 a Drop-in Replacement for a TP270 Touch Panel

HMI and touchscreens Published 6 min read

Short answer

No. The TP277 is the successor to the TP270, not a drop-in replacement: ProTool does not support it, so the TP270 project must be migrated to WinCC flexible, and the cut-out, connections and runtime behavior verified on the machine before you order.

On this page
  1. What actually changes between the two panels
  2. The migration path
  3. Worked example: checking configuring memory before you migrate
  4. Verify these four things before ordering the TP277
  5. The decision
  6. Questions asked

No, the TP277 is not a drop-in replacement for the TP270. It is the successor panel: the same 6-inch touch-panel class and 5.7-inch active display area, but a different part number, a different display technology and, decisively, a different engineering tool. ProTool does not support the TP277, so a TP270 project cannot be downloaded to it as-is. The panel only becomes a working replacement after you migrate the project to WinCC flexible, retarget it to the TP277, and prove it against the machine. This article gives you the documented differences, the migration path and the checks to run before you commit to the swap.

What actually changes between the two panels #

Item TP270 TP277
Order number 6AV6545-0CA10-0AX0 6AV6643-0AA01-1AX0
Panel class SIMATIC TP270 6-inch touch SIMATIC TP 277 6-inch touch
Display 5.7-inch color STN 5.7-inch TFT
Configuring memory 2 MB 4 MB
Engineering tool ProTool from V6.0 WinCC flexible 2005 Standard or higher

Two of these differences drive the whole decision. The engineering-tool change means there is no software path from a ProTool project to a running TP277 except migration into WinCC flexible. The display change from STN to TFT is an upgrade in contrast and viewing angle, but it also means the image will not look identical at the same mounting position.

The matching nominal sizes work in your favor mechanically, but they do not prove interchangeability. Confirm the cut-out dimensions and the connector positions against the datasheets for both order numbers before ordering; the panel cut-out reference page lists what to compare when a replacement has to fit an existing opening.

The migration path #

ProTool does not support the TP277, so the project must move through WinCC flexible:

  1. Back up the working TP270 and its ProTool project before touching anything. If the panel is still running and the source project is lost, recover the project from the panel first; the steps are in the HMI replacement project recovery guide.
  2. Open the ProTool project in WinCC flexible. The tool migrates it into a WinCC flexible project.
  3. Retarget the migrated project to the TP277, order number 6AV6643-0AA01-1AX0.
  4. Compile. Fix every warning that touches screens, tags, alarms or scripts before the first download; do not accept a compiled-but-warned project on a production panel.
  5. Download to the TP277 and test on the bench with the real controller before it goes into the machine.

If the migration target is a still newer platform, the same project can move onward from WinCC flexible into TIA Portal; the procedure is covered in the WinCC flexible to TIA Portal migration article.

Migrations reported on comparable projects ran without errors, but that experience is not a compatibility guarantee for your project. Scripts, third-party controller drivers and screen objects that ProTool allowed but WinCC flexible handles differently are where conversions typically need rework. Treat the converted project as a draft until step 5 passes.

Worked example: checking configuring memory before you migrate #

The TP270 carries 2 MB of configuring memory and the TP277 carries 4 MB. That gives you headroom, but quantify it rather than assume it.

Inputs:

  • TP270 configuring memory: 2 MB (from the panel's own specification, as listed in the comparison above).
  • TP277 configuring memory: 4 MB (same source).
  • Example: your compiled ProTool project occupies 1.6 MB on the TP270 (read this from the ProTool project properties or the panel's project information; 1.6 MB here is an illustrative value, not a measured one).

Rule: the migrated WinCC flexible project must fit in the target's configuring memory with margin for the runtime images and future edits. Compare the compiled size against the target memory:

  • Free memory on the TP270 today: 2 MB − 1.6 MB = 0.4 MB.
  • Free memory on the TP277 after migration: 4 MB − 1.6 MB = 2.4 MB, before any WinCC flexible overhead.

Result: on this example project the TP277 roughly doubles the margin, from 0.4 MB to 2.4 MB, so memory is not the constraint. The migration risk sits elsewhere: in the project conversion itself and in runtime behavior on the machine.

Decision: if your compiled TP270 project is well under 2 MB, memory will not block the TP277. If it approaches the 2 MB limit, the 4 MB target is actually part of the reason to migrate rather than refurbish. Either way, recheck the size after the WinCC flexible compile, because conversion can change compiled size in either direction.

Verify these four things before ordering the TP277 #

Memory headroom does not close the case. Before the order number 6AV6643-0AA01-1AX0 goes on a purchase list:

  • Cut-out and mounting: compare both datasheets' opening dimensions and mounting clip positions. The panels are the same nominal size class, but only the datasheet numbers settle it.
  • Connections and power: verify the supply voltage range and every connector you use (serial, PROFIBUS/MPI, Ethernet, USB where fitted) against the TP277 datasheet, not against the TP270's.
  • Controller driver: confirm the migrated WinCC flexible project still communicates with your PLC over the same port and protocol you use today, on the bench, with real tags writing and reading.
  • Runtime behavior: run the acceptance sequence an operator would: every screen, every alarm, a controller disconnect and recovery, and a panel power cycle. A structured way to run this proof is in the PC-based HMI qualification checklist; the same bench discipline applies to a panel swap.

The broader discipline of checking a replacement before money moves is laid out in the obsolete HMI replacement verification guide, and it applies word for word here.

The decision #

  • TP270 still running, project source available: the TP277 is a sound successor, not a drop-in. Budget the migration to WinCC flexible as part of the swap, verify cut-out, connections and drivers, and accept it only after the bench test on your controller passes.
  • TP270 still running, project source lost: recover the project from the panel before planning anything else; without a ProTool project there is nothing to migrate.
  • Machine at end of life anyway: weigh a move to a PC-based HMI running a current runtime instead of a legacy-panel successor; if that is the direction, the same qualification checklist governs the choice of industrial panel PCs.
  • Panel failed with no backup anywhere: the TP277 plus a rebuilt WinCC flexible project is a rebuild, not a replacement, and the rebuild effort is the real cost of the decision.

One safety note: a panel swap can change how operators reach stop, reset and acknowledge functions. Before the TP277 goes into production, walk the safety-related operator actions (E-stop indication, reset, bypass or override screens if any) with the machine's safety documentation and confirm nothing moved or disappeared in the migrated screens.

Questions asked

Which software configures the TP277 6AV6643-0AA01-1AX0?

WinCC flexible 2005 Standard or higher. The TP270 was configured with ProTool from version V6.0, and ProTool does not support the TP277, so the engineering station has to move to WinCC flexible even if nothing else on the machine changes.

Does WinCC flexible convert a ProTool project automatically?

WinCC flexible opens a ProTool project and migrates it into a WinCC flexible project. The conversion is a starting point, not a finished application: screens, tags, alarms and controller connections still need review, and the result must be tested against the real controller before the TP277 goes into production.

Is the TP277 display the same as the TP270 display?

Both are sold as 6-inch touch panels with a 5.7-inch active display area, but the TP270 uses a color STN display and the TP277 uses TFT. Contrast and viewing angle differ, so check readability at the machine's actual mounting position, especially off-axis.

Can I copy the TP270 project file straight onto a TP277?

No. A ProTool project file cannot run on the TP277 because the panel is not supported by ProTool. The file must first be migrated into a WinCC flexible project, configured for the TP277 order number 6AV6643-0AA01-1AX0, compiled and downloaded from WinCC flexible.

Keep reading

  • Explainer

    Can You Migrate a WinCC 7.2 Project to WinCC Flexible

    No migration path converts a WinCC 7.2 project into WinCC flexible 2008; Siemens documents the two as architecturally incompatible, and the documented directions run the other way - WinCC flexible into TIA Portal, and WinCC 7.2 up to WinCC V7.5. Treat the MP 377 12-inch Touch application as a new WinCC flexible project: inventory every function, rebuild it item by item, and verify each one on the bench.

    HMI and touchscreens

  • How-to

    HMI Replacement: Recover the Project Before Converting

    Back up the editable project and the complete hardware reference first, then convert a copy, clear every conversion warning, and commission in stages: project transfer, verified reads, and only then operator commands. The end-of-2026 discontinuation date for the old series sets when to order, not whether the new panel drops in.

    HMI and touchscreens

  • How-to

    Migrating a WinCC PC Runtime project to a Comfort panel

    There is no whole-project conversion from a WinCC PC runtime station to a TP1500 Comfort panel. Copying screens inside TIA Portal is supported, but each object, faceplate and system function must be dispositioned and reconfigured for the Comfort system. Advanced sources transfer with the least rework, Professional sources need object-by-object reconciliation, and a Unified source should move to a Unified Comfort panel instead of being converted.

    HMI and touchscreens