Troubleshooting
Configuring an HMI analog output dimmer over BACnet/IP
Short answer
Working relay buttons prove the BACnet/IP link, so trace only the analog chain: screen tag value, the point in Mervis IDE, the analog output channel scaling, then the DC volts at the dimmer input. Map the screen's 0-100 percent across the output so 10 percent gives 1.0 V and full scale gives 10.0 V, and take the off function to a relay unless the dimmer datasheet documents switch-off below 1 V.

On this page
- Why do the relay buttons work but the dimmer does not?
- What should the dimmer control on the screen do?
- How do you confirm the value reaches the controller?
- Which analog output settings make 1-10 V dimming work?
- How do you prove the voltage reaches the dimmer?
- Why does the lamp dim but never turn off?
- What order do you fix the whole path in?
- Questions asked
A dimmer that ignores the screen while every relay button works is not a network fault: the buttons already prove the BACnet/IP write path into the M203. Dimming adds a second chain — a numeric tag on the screen, the analog point in Mervis IDE, the analog output channel and its scaling, then the voltage at the dimmer input — and you repair the first point where the number stops following the screen. Work the mapping as 0.1 V for one percent of screen range, so the full screen travel lands exactly on the dimmer's control span, and take the off function to one of the working relays unless the dimmer's datasheet documents switch-off below its control floor.
Why do the relay buttons work but the dimmer does not? #
Because a relay write and a dimming value share only the first part of the road: the buttons prove the BACnet/IP link, its address settings and the driver entry, while dimming adds a numeric tag, an analog object, scaling and a voltage that no button ever exercises.
BACnet, standardized as ANSI/ASHRAE 135, has the server publish standard object types, discrete and analog among them; the Mervis project on the M203 publishes the discrete objects your buttons already write, and it must publish an analog object for the dimmer. A relay button moves one bit into one discrete object and is done. A dimming value has to leave the screen as the right number in the right format, land on the analog object, survive the controller program's transfer to the physical output and come out as real volts. That is four more places to fail, so treat the working buttons as proof of the link and nothing more: trace the screen value, the Mervis value, the output scaling and the measured voltage, in that order.
What should the dimmer control on the screen do? #
Operate the dimmer control and watch its own numeric readout: the displayed value must step through 0-100 as you touch it, and if it does not, the fault is the screen object or its tag, not the network.
Give the dimmer a numeric object bound to a tag whose range is 0-100 percent, and confirm the object writes on change or release rather than only on press. The Weintek BACnet/IP connection guide adds the driver in System Parameter Settings and defines tags in Tag Manager; the relay writes prove those settings, so leave them untouched and re-check only the dimmer tag's own binding: it must point at an analog object on the controller, with a data format that matches what the controller publishes. A mismatch here sends a wrong number downstream while every status indication stays green. If the screen value itself misbehaves, the isolation order in Is It the Driver, the Tag or the Screen? Diagnosing HMI Values finds the failing layer faster than any network probe.
How do you confirm the value reaches the controller? #
Watch the analog point live in Mervis IDE while the screen steps through 0, 25, 50, 75 and 100: the monitored value must track those five numbers, and the first number it refuses tells you which side of the link owns the fault.
The Tag Manager entry and the point exposed by the M203 project must name the same BACnet object type and instance; a write aimed at one object while the program watches another leaves both sides looking healthy and the lamp dark. When the Mervis value moves but by the wrong amount — ten times too large, ten times too small, or stuck above 9 — the data format between screen and point is wrong, the same fault family as Why an HMI writes the wrong PLC value above 9; correct the format before touching wiring. When the value tracks, the rest is controller work: the network only delivers the number, and controller-side logic has to carry it to the physical output — the division of labor described in how PXC001.ED BACnet references support controller-side logic. Add that transfer to the Mervis program if it is missing.
Which analog output settings make 1-10 V dimming work? #
The M203 analog output must be configured, in the Mervis project, to put 1.0 V at the dimmer's minimum and 10.0 V at full output, because the dimmer's 1-10 V input defines that span.
Take the channel's signal range from the M203 hardware documentation, never from the model name — the datasheet states what the output can deliver and how the project configures it. Worked example, with a documented range of 0-10.0 V and the screen writing percent P from 0 to 100: the program multiplies by 0.1, so V = 0.1 × P. Check the arithmetic at three points: P = 10 gives 0.1 × 10 = 1.0 V, the dimmer's minimum; P = 50 gives 5.0 V; P = 100 gives 10.0 V. If the documented range differs, the factor is the range top divided by 100, and the same three checkpoints apply. One electrical check comes before wiring: the 1-10 V interface descends from IEC 60929, in which the control gear powers the control input and the controlling device pulls that voltage down, so confirm from the two datasheets that the M203 output may drive the dimmer's input directly and that both agree on the reference terminal.
How do you prove the voltage reaches the dimmer? #
Put a DC voltmeter between the output terminal and its reference and step the screen: a correct chain reads about 1.0 V at 10 percent, 5.0 V at 50 percent and 10.0 V at full scale, and where the reading stops following the screen is where the chain is broken.
Measure at the M203 terminal block first, then at the dimmer's input terminals, at the same three screen positions. A Mervis value that moves while the terminal voltage stays fixed points at channel configuration, the program's output assignment or the output hardware; a healthy terminal voltage that never appears at the dimmer input points at the cable and the reference conductor between the devices; correct voltage at the dimmer input with a dark or erratically bright lamp points at the dimmer module and its load, not at the HMI project. De-energize the dimmer module's supply before you move or re-terminate any control wire on its input terminals.
Why does the lamp dim but never turn off? #
Because the dimmer's floor is a minimum, not an off position: at the bottom of the mapped range the output already sits at 1.0 V, the lowest point of the dimmer's regulated span, and whether anything lower switches the lamp off is written only in the dimmer's datasheet.
Read the switch-off behavior from the dimmer module's documentation. If it documents a switch-off threshold inside the low end of its input, map percent zero to a value that drives the output below that threshold and prove the dark lamp at the bench. If it does not — or if the room simply must have a dependable off — drive one of the already-working relay outputs to switch the dimmer module's supply and keep the analog output inside the regulated span. For a consulting room in a hospital, take the second path: off becomes a discrete state you can verify, independent of control electronics at the bottom of the range, and the dimmer keeps its full usable travel.
What order do you fix the whole path in? #
Check the five points in order and repair only the first one that fails, because every later checkpoint depends on the ones before it; a wiring change made while the tag binding is still wrong wastes a bench hour and can mask the real fault.
- Screen: the dimmer object steps its numeric readout through the percent range; fix the object or its tag if it does not.
- Controller point: the Mervis value tracks the five walk values; fix the object type and instance in
Tag Managerif it does not. - Scaling: the program carries the point to the analog output with the factor from the documented range; fix the scaling or the output assignment if it does not.
- Terminals: the expected meter readings appear at the M203 terminals and again at the dimmer input; fix the channel, the wiring or the reference where they diverge.
- Endpoints: the lamp reaches its documented minimum at the floor of the span, and off comes from the documented threshold or from the relay; fix the endpoint mapping or move off to a relay.
A path that passes all five leaves the lamp following the screen from floor to full output, with off handled by whichever path the dimmer's documentation supports.
Questions asked
Is the HMI the BACnet server or the client in this setup?
Here the controller publishes the points and the HMI is the client that writes them, so the ordinary BACnet/IP driver in the connection guide is the right one. Weintek documents a separate BACnet/IP Server driver, with its own HMI Device ID setting, for the opposite arrangement where a building-management system reads values from the HMI; the dimmer project does not need that driver.
Can the same checkpoints be reused for a 0-10 V dimmer input?
Yes. A 0-10 V input uses the whole span, so percent passes straight through and the low-end floor disappears: zero percent gives zero volts and full scale gives the documented top of the range. Keep the same walk test and meter readings, and re-check the channel range against that dimmer's documentation before scaling.
The lamp flickers near the bottom of the range — what is the cause?
Percentages below ten drive a proportional output under the dimmer's regulated floor, into a region the module's documentation does not guarantee. Clamp the value in the controller so the analog output never leaves the regulated span, or remap the lowest percent of screen travel to the driver's documented minimum instead of letting the voltage fall below it.
Does the 1-10 V control pair need its own supply?
No. In the classic interface the dimmer's driver powers its own control input and the controlling device pulls that voltage down, which is why the controller output must be checked against the input before wiring. Adding another supply to the pair fights the driver's internal source and shifts the dimming level.