IMDTouchKnowledge BaseShop main store

Troubleshooting

Why a LOGO 0BA8 network output does not update an HMI tag

HMI and touchscreens Published 5 min read

Short answer

On a LOGO! 0BA8, a Network Output block is not published at the physical Q address; it is published at the V bit address the NQ block itself was assigned, inside the NQ range. Point the HMI tag there, not at Q1.0 and not in the network-input region, and set the acquisition cycle to 500 ms or 1 s.

On this page
  1. What is actually happening
  2. Where NQ bits live
  3. Setting the tag correctly
  4. Worked example
  5. Connection budget and related LOGO! reads
  6. Decision
  7. Questions asked

The tag must point at the V address the Network Output block itself was assigned, not at a Q address. On a LOGO! 0BA8 an NQ block publishes its bit into the V (variable memory) area, at the address shown in the block's own properties — for example V100.1. A tag defined as Bool Q1.0 polls a physical output terminal the NQ block never drives, so it stays 0 forever. Set the acquisition cycle to 1 s (500 ms minimum for a fast alarm) instead of 100 ms, and the bit updates within one cycle.

What is actually happening #

You placed an NQ block with address 1.0 in the LOGO! program and created a Bool tag Q1.0 at a 100 ms cycle in WinCC Flexible. Three faults stack up here, and all three must be fixed before the tag works:

  1. Wrong address area. The NQ block does not publish into the Q space. Q1.0 is the first physical relay output; polling it returns the terminal state, which your program never switches.
  2. Wrong V sub-range. After the first fix attempt the tag was moved to V2.5, but the lower V bytes belong to the Network Input (NI) blocks. No NI block is driven there, so the polled bit is still a permanent 0.
  3. Cycle too short. A 100 ms acquisition cycle against the S7-compatible Ethernet exchange is aggressive; the driver can round it up or time out, and a timeout is held as the last known value — again 0.

The result is exactly what you saw: the circle stays red even though the NQ coil is TRUE in the program and in online test.

Where NQ bits live #

The V area on the 0BA8 is partitioned by block type. Network Inputs occupy the low bytes; Network Outputs sit in a range starting at V100.0. The NQ block's properties dialog shows the exact assigned address — read it there and copy it character for character into the HMI tag. The Siemens system manual for the LOGO! documents how network digital outputs are exposed over the device's network settings from the 0BA8 generation onward; it is the reference for the V map your firmware version uses.

Tag address What the HMI actually reads Result
Q1.0 First physical output terminal Stuck 0
V2.5 Network Input region (NI byte 2, bit 5) Stuck 0
V100.1 The NQ block's published bit Follows the program

So the address the NQ block shows in LOGO!Soft Comfort is the address the HMI polls. There is no redirection from Q into V, and no setting that makes it happen.

Setting the tag correctly #

  1. In LOGO!Soft Comfort, open the NQ block and note the full bit address shown in its properties (for example V100.1).
  2. Save the project and transfer it to the LOGO!, and check the Ethernet connection settings so the HMI's client slot is permitted.
  3. Give the LOGO! a static IP on the same subnet as the panel (for example 192.168.0.10 with mask 255.255.255.0) and confirm you can ping it.
  4. In WinCC Flexible, define the tag as data type Bool, address V100.1, at the target acquisition rate.
  5. Download to the panel, force the rung TRUE in online test, and confirm the circle turns green within one cycle.

The write direction you already have working follows the same logic in reverse: an NI block publishes a V bit the HMI writes into, as covered in why an HMI button should write a LOGO VM bit instead of a network input. The rule is symmetrical — read the address the block shows, never the Q or I terminal that happens to have the same number.

Worked example #

Say the alarm condition drives NQ1, and the block properties show address V100.1.

  • Wrong tag: Bool Q1.0, 100 ms. The HMI polls a relay terminal the program never sets → always 0.
  • First attempted fix: Bool V2.5 at the target rate. V2 is an NI byte → still always 0.
  • Correct tag: Bool V100.1, 1 s. When the rung goes TRUE, the LOGO! publishes 1 at V100.1; at the next poll, at most 1 s later, the tag reads 1 and the circle turns green.

If you want a faster lamp, drop the cycle to 500 ms, but only on a lightly loaded network — above that, keep the target rate.

A LOGO! 0BA8 can talk to other 0BA8 devices, SIMATIC S7 PLCs, a SIMATIC HMI or a PC, so before adding panels or loggers check how many client slots the Ethernet connections list already consumes. For a concrete panel hookup over this same driver, see connecting a LOGO! 0BA8 to an MT8050iE HMI over Ethernet, and for the other read-special case from the same device family, the LOGO 0BA8 clock transfer via VW991 shows how a fixed V word is the contract between LOGO! and HMI — the NQ bit is the same idea, one bit instead of a word.

Decision #

  • Screen-only bit on a 0BA8: place an NQ block, copy its V address into the HMI tag exactly, cycle at the target rate. Done — no spare physical outputs needed.
  • Tag already on a V address but still 0: check the sub-range. Bits in the NI region are written by the HMI, not read from NQ blocks; move the tag to the NQ range the block reports.
  • Bit updates erratically or drops out: the 100 ms cycle is the suspect; set the target rate before touching anything else.
  • HMI must write into the program: that is the NI block's job at its own V address, not a reversed NQ.

Questions asked

Can an HMI write to an NQ block to send a bit into the LOGO! 0BA8?

No. An NQ block only publishes a LOGO! bit outward for reading. To write from the HMI into the program you place a Network Input (NI) block and point the HMI tag at the V address the NI block was assigned. The two block types work in opposite directions and occupy different V ranges.

Why does the tag read 0 even though the NQ block shows TRUE in the LOGO! program?

Because the tag is polling an address the NQ block does not publish. Reading a Q address returns a physical output terminal, and reading a bit in the network-input region returns an NI byte nobody is driving. Move the tag to the exact V bit the NQ block was assigned, such as V100.1, and the polled value follows the block.

What acquisition cycle should the tag use against a LOGO! 0BA8 over Ethernet?

Set 1 s as the working default for status bits and alarms, and use 500 ms only on a lightly loaded network when you need a faster indicator. A 100 ms cycle over the S7-compatible Ethernet exchange can be rounded up or timed out by the driver, and a timeout is typically held as the last known value, which reads as a stuck 0.

Do I still need spare physical outputs just to show bits on the screen?

No. That is exactly what the NQ block is for. An NQ block assigned to a V bit makes an internal LOGO! state visible to the HMI without consuming a relay output, so screen-only lamps and alarms no longer need spare Q points.

How many HMI or external connections can one LOGO! 0BA8 serve?

A LOGO! 0BA8 establishes network communication with other LOGO! 0BA8 devices, SIMATIC S7 PLCs, a SIMATIC HMI or a PC, within the device's documented connection limit. Before adding a second panel or a data logger, count the clients already using the Ethernet server and confirm slots remain in the connection settings.

Keep reading

  • Troubleshooting

    Why an HMI Button Should Write a LOGO VM Bit Not I1

    Pressing the Weintek button never raises Q1 because it writes LOGO! input I1, and a physical input is set only by the signal at its terminal. Point the button at a bit in the LOGO! variable memory, read that bit through a network input, and let the program drive Q1 from it. The driver's fixed address map, the link checks in order and one worked retarget to a free VM address follow.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Start and Stop buttons do not control an S7-300 output

    The Start and Stop buttons do nothing because E0.0 and E0.1 are S7-300 input image addresses: the CPU refreshes them from the input modules every scan, so an HMI write cannot survive. Step 7 simulation changes the simulated input state itself, which is why the LED follows it. Move the two commands to memory bits such as M0.0 and M0.1, latch them in the PLC, and let the program drive A4.0.