Connecting a LOGO! 0BA8 to an MT8050iE HMI over Ethernet

HMI and touchscreens Published 5 min read

Short answer

Yes, a LOGO! 0BA8 connects to a Weintek MT8050iE over Ethernet using the Siemens LOGO! (Ethernet) driver in EasyBuilder Pro, with both devices on the same subnet and a server-side Ethernet connection defined in the LOGO! project; prove the link with one read tag, then add writes only after that read follows a value you change in the controller.

On this page
  1. What the driver does and what it does not
  2. Set the network addresses
  3. Worked example: checking the two addresses share a subnet
  4. Configure the LOGO! project for the connection
  5. Configure the MT8050iE project in EasyBuilder Pro
  6. Prove reads before you allow writes
  7. If it still does not communicate
  8. Questions asked

Yes, a Siemens LOGO! 0BA8 connects to a Weintek MT8050iE over Ethernet, and it is a documented pairing: Weintek's connection guide covers the Siemens LOGO! (Ethernet) driver on pages 854 to 858 of PLC_Connection_Guide.pdf. The setup needs three things to line up: the right driver in the HMI project, distinct IP addresses in the same subnet, and a server-side Ethernet connection defined in the LOGO! project. The sequence below gets you to one verified read tag first, then adds writes.

What the driver does and what it does not #

The driver in the HMI project translates the addresses of your display objects into requests the LOGO! understands over TCP/IP. Ethernet is only the transport. Two mistakes are common here:

  • Selecting a Siemens driver from a different controller family because the name looks close. The guide entry is written for the LOGO!; use it.
  • Treating a lit Ethernet link LED as proof of communication. A working link can still carry requests the LOGO! rejects, and a working driver can read the wrong address without raising any alarm.

If your project instead shows a simulator that will not reach a LOGO!, the causes are different from a live-panel failure; see why an EasyBuilder Pro simulator fails to connect to a LOGO! OBA8 for that case.

Set the network addresses #

Both devices must sit on the same subnet unless a router provides a path between subnets. Assign each device its own address; never let two devices share one. Example values for a bench machine, not a required pair: HMI at 192.168.1.10 and LOGO! at 192.168.1.2, both with mask 255.255.255.0.

Also set the same values in the LOGO! programming project, so a later download does not silently change the address the HMI dials. Before you put the link in service, check that no other device already holds either address.

Worked example: checking the two addresses share a subnet #

Inputs: HMI address 192.168.1.10, LOGO! address 192.168.1.2, subnet mask 255.255.255.0 on both (example bench values you enter in the device menus and in EasyBuilder Pro).

The rule in words: two addresses are in the same subnet when masking each address with the subnet mask gives the same network portion.

The arithmetic: 192.168.1.10 AND 255.255.255.0 gives 192.168.1.0. 192.168.1.2 AND 255.255.255.0 also gives 192.168.1.0. The network portions match and the host portions, 10 and 2, differ.

Result: the two devices reach each other directly, with no gateway address needed in either device.

Decision: if the masked network portions had differed, no tag change would repair it — you would need a router between the subnets or a consistent readdressing of both devices. With the portions matching and the addresses distinct, proceed to the driver configuration.

Configure the LOGO! project for the connection #

The Weintek guide for this pairing works from the LOGO! side as a server. In the LOGO! programming software, open the network settings and configure Ethernet connections as the guide entry for 0BA8 shows: right-click Ethernet Connections, add a connection, and define it as the server connection the driver expects, then download the project to the module. The guide documents adding up to eight connections; on this panel you need one, but if a data collector or a second HMI will also poll this LOGO!, count it against that limit. Related reading on how the generations differ is in migrating LOGO! 0BA7 to 0BA8.

Configure the MT8050iE project in EasyBuilder Pro #

Work through the panel side in order:

  1. Confirm the project target model is the MT8050iE you have on the bench, not a similar panel.
  2. Add a new controller connection and select the driver documented for this pairing in the guide's HMI Setting section — the Siemens LOGO! (Ethernet) entry.
  3. Under the driver's settings, enter the LOGO!'s IP address (in the example above, 192.168.1.2) and the connection parameters exactly as the guide entry lists them for the 0BA8.
  4. Add one read-only numeric object on a start screen, mapped to a LOGO! value whose type and address you have confirmed in the LOGO! program — a VM word or a known bit, whatever the driver address table supports for your data.
  5. Compile and download the project to the panel by the transfer method you normally use, then confirm the running project on the actual panel, not only in the editor.

Keep the transfer method and the driver selection separate in your head; they are independent choices, as set out in separating HMI transfer method from PLC driver selection. The MT8050iE over serial to another controller family is a different guide entirely — for example the MT8050iE to an S7-200 over PPI setup.

Prove reads before you allow writes #

A displayed number is not proof of a live link: it may be an initial value or the last value received. Verify with a controlled change and an independent observation:

  • Force the test value in the LOGO! using its programming software while watching the panel. The displayed number must follow, with no communication indicator.
  • Cycle power to the LOGO! (on the bench only) and confirm the panel recovers the connection and resumes updating.
  • Compare two or three different values of different widths between the LOGO! program and the panel to catch a wrong data width or signedness before it bites an operator.

Only after reads pass, add a write object on a value that cannot start motion or change a process state. Press the HMI button once and watch the value change in the LOGO! program monitor. If you want a repeatable bench script for this kind of check, the tag-by-tag method in testing HMI simulation against a live PLC transfers directly to this pairing.

If it still does not communicate #

Work the layers in order. Check the link LEDs at both ports and the cable first. Then recheck the addresses with the masked comparison above — the most common bench failure is an HMI pointed at the wrong LOGO! address after someone changed one device. Then confirm the LOGO! project with the server connection is actually the one running on the module; a download from an older project file silently removes the connection definition. Last, re-read the failing tag against the driver address table. Communication faults, addressing faults and interpretation faults look identical on a frozen display, and only a forced value change tells them apart.

One safety note: any write object you leave on a running machine must act through the LOGO!'s own program logic, never write directly to an output coil that drives a contactor or valve; the LOGO! program remains the only path to the physical outputs.

Questions asked

How many Ethernet connections can the LOGO! 0BA8 accept in the Weintek setup?

The Weintek connection guide for Siemens LOGO! (Ethernet) documents adding connections under Ethernet Connections in the LOGO! server settings, with up to eight connections allowed. On an MT8050iE serving one LOGO! 0BA8 you need only one, but the panel-side limit of eight matters when several HMIs or a data collector share the same controller. Count every client that opens a connection before you commit the design.

Where do I set the IP address on the LOGO! 0BA8 itself?

The 0BA8 has a menu command on the module for network communication settings, so you can set the IP address and subnet mask at the device without a programming software transfer. Set the same values in the LOGO! project so a later download does not overwrite the address the HMI expects, and give the LOGO! its own address, never a duplicate of another device on the network.

The panel shows no communication error but the value never changes. What is wrong?

That usually means the displayed number is the last value received, or a tag mapped to the wrong address. Force a change in the value from the LOGO! side and watch the panel; if the number stays frozen with no alarm, check the tag against the driver address table, including memory area, data width and signedness. The driver connection itself is likely healthy.

Keep reading

  • How-to

    Connecting a Weintek MT8050iE to an S7-200 over PPI

    Yes. The MT8050iE talks to an S7-200 CPU 224XP over PPI with the Siemens S7/200 PPI driver in EasyBuilder Pro, assigned to a COM port documented for RS-485 with serial settings matched to the PLC. Project download runs over a USB A-to-mini-B cable or Ethernet and is independent of the PLC driver; confirm the real-time clock in the model datasheet.

    HMI and touchscreens

  • How-to

    Connecting a Fuji HMI to a ControlLogix PLC

    Yes, the pairing works. You need Rockwell's Logix package matched to the controller firmware on the PLC side and Fuji V-SFT for the panel; FactoryTalk View programs only Rockwell panels, and RSLinx is not part of the Fuji data path. The gate is the driver list for your exact panel model — V8, V9 and TechnoShot have the Allen-Bradley connection documented.

    HMI and touchscreens

  • How-to

    Connecting a Pro-face HMI to a Mitsubishi FX2 PLC

    License GP-Pro EX through Pro-face or an authorized distributor, select the Mitsubishi Electric Corporation FX serial driver for the FX2's built-in programming port, build the cable to the documented pinout, and prove the link with one read-only tag before enabling any writes. A connector that fits proves nothing.

    HMI and touchscreens