How-to
Connect an S7-400H to WinCC Professional with a Device Proxy
Short answer
Yes: keep the S7-400H project in SIMATIC Manager under STEP 7 V5.6, build the WinCC Professional V15.1 runtime station in TIA Portal, and join the two projects with a Device Proxy. Enable the redundancy option on the SIMATIC S7-300/400 connection so the runtime follows the active H-CPU, then prove the switchover on a bench before the plant relies on it.
On this page
- Can a STEP 7 V5.6 H system talk to WinCC Professional V15.1?
- Why does the S7-414H need a Device Proxy?
- What must the SIMATIC Manager project contain first?
- How do I create and initialize the Device Proxy in TIA Portal?
- How does WinCC Professional follow the H-CPU switchover?
- How do I prove the switchover works before the plant relies on it?
- Which versions and licenses must line up?
- Which stations does this route cover?
- Questions asked
Yes, you can. Keep the S7-400H project where it belongs — SIMATIC Manager under STEP 7 V5.6 — and build the operator station in TIA Portal with WinCC Professional V15.1. The two projects meet through a Device Proxy: a stand-in device that carries the H station's controller data into the HMI project, documented in the manufacturer's combined-configuration support entry 73502293. Enable the redundancy option on the SIMATIC S7-300/400 connection and the runtime follows the changeover between the two H-CPUs on its own. This article gives the order of operations, the example addresses, and the bench test that proves the switchover before the plant depends on it.
Can a STEP 7 V5.6 H system talk to WinCC Professional V15.1? #
Yes: keep the S7-400H project in SIMATIC Manager under STEP 7 V5.6, build the WinCC Professional V15.1 runtime station in TIA Portal V15.x, join the two projects with a Device Proxy, and enable the redundancy option on the SIMATIC S7-300/400 connection so the runtime follows the active H-CPU.
Both halves of that route are documented, not improvised: the support entry "Combined configuration with WinCC (TIA Portal) and STEP 7 V5.x" (entry 73502293) defines the device proxy function that joins the two project worlds, and the H system manual's section 4.2, "Communication between H-CPU and plant PCs" (entry 90885106), defines what a plant PC may connect to on an H system. Nothing in the route touches the redundancy engineering of the PLC project, so the fault-tolerant behavior you have commissioned stays commissioned. Decision: for any new operator station on this PLC, keep STEP 7 V5.6 for the controller and take the proxy route for the HMI.
Why does the S7-414H need a Device Proxy? #
The S7-414H pair is programmed only in STEP 7 V5.x, so the fault-tolerant engineering stays in the SIMATIC Manager project, and the Device Proxy lets the TIA Portal HMI project reference that controller without merging the two project files.
Inter-project engineering is the documented function that exchanges controller data between separate projects by way of a device proxy. The proxy carries the H station's name, type and interface addresses into the HMI project, so its connection settings resolve against the real station instead of hand-typed values, and the manufacturer's description of the function notes the integration works without manual tag handling. That division of labor between the two engineering tools is the same one described in How WinCC and STEP 7 work together in a PLC project.
What must the SIMATIC Manager project contain first? #
The SIMATIC Manager project must already hold the complete H station — both H-CPUs configured, their synchronization link in place and one Ethernet interface on each CPU joined to the plant network — because the proxy copies its controller data, name, type and addresses, out of that configuration.
Check that the station compiles without errors before you start the exchange. The HMI connects to the CPUs' Ethernet interfaces, never to the synchronization link, which is reserved for CPU-to-CPU traffic. Write down both interface addresses before you leave this project, because the WinCC connection will need them both. If the H system already runs in the plant, these items exist; verify them instead of assuming them.
How do I create and initialize the Device Proxy in TIA Portal? #
In TIA Portal, add the WinCC Professional runtime as a PC station, add a Device Proxy as the H station's stand-in, and initialize it from the controller data file exchanged between the projects; the "Initialize device proxy" dialog lists the controllers the file contains for assignment to the proxy.
- Create the TIA Portal project for the operator station and add a PC station configured with the WinCC Professional V15.1 runtime.
- In the SIMATIC Manager project, create the controller data file for the exchange, exactly as support entry 73502293 shows for your V5.6 release.
- Add a Device Proxy to the TIA Portal project as the stand-in for the redundant H station.
- Initialize the proxy from that file: the "Initialize device proxy" dialog lists the controllers the file contains, and you assign the H station to the proxy.
- On the runtime station, add an HMI connection of type SIMATIC S7-300/400 and enable its redundancy (fail-over) option; the addresses go in as the next section shows.
- Compile both projects, then download each one the way you normally do.
Keep each project the master of its own objects: PLC program, hardware and H parameters stay in SIMATIC Manager; screens, tags, alarms and the connection stay in TIA Portal.
How does WinCC Professional follow the H-CPU switchover? #
Give the runtime station an HMI connection of type SIMATIC S7-300/400, point it at the Ethernet interfaces of both H-CPUs, and enable the connection's redundancy (fail-over) option, which makes WinCC Professional follow the switchover from the leading CPU to the standby without a new configuration.
To the runtime, the H system appears as one logical controller whose active endpoint moves from CPU 0 to CPU 1 when the leading CPU fails; the fail-over option is what lets the connection follow instead of dying with CPU 0. Set the option in the connection properties and enter both CPU addresses there.
Worked example, with example addresses: CPU 0's Ethernet interface at 192.168.10.11, CPU 1's at 192.168.10.12, subnet mask 255.255.255.0, runtime PC at 192.168.10.60. Check the network with a bitwise AND: 192.168.10.11 AND 255.255.255.0 = 192.168.10.0, and 192.168.10.12 AND 255.255.255.0 = 192.168.10.0, so both CPUs and the PC sit in one subnet and the fail-over path crosses one switch and no router. Ping both CPU addresses from the runtime PC before you configure anything; a missing reply from either address is a connection that fails on that CPU no matter what the option does.
If you also run a non-redundant S7-400, its connection layout is the one described in Connecting an HMI to an S7-400 across Ethernet and PROFIBUS; the H system adds only the redundancy option. When the SCADA must later watch a second redundant S7-400H system, adding a second redundant S7-400H system to WinCC SCADA covers the SCADA side of that expansion.
How do I prove the switchover works before the plant relies on it? #
Prove the fail-over on an isolated bench first: switch the leading H-CPU out of run, watch the connection move to the standby, and measure loss and recovery separately with timestamped observations on test tags you verified in both CPUs.
Build the test around verified tags: a counter the PLC increments every cycle, a heartbeat bit, and a test write issued from the HMI. With an example acquisition cycle of 1 s, force the switchover, and record the timestamp of the last good value and the timestamp of the first new one. The two intervals are different measurements: the connection-error interval is the loss, and the catch-up shows up in the counter.
Example arithmetic from a bench run: the displayed counter reads 4,180 before the switch and 4,185 after recovery, so 4,185 - 4,180 = 5 cycles at 1 s, about 5 s of catch-up. An example pass limit for this setup: the connection error clears within 5 s and the next test write is accepted. That limit belongs to this bench example, not to the manufacturer's data sheet.
Run the first changeovers on the bench. On the plant, force a CPU switchover only with the process in a state where a few seconds without HMI values and writes is safe.
Which versions and licenses must line up? #
Line up four versions before you configure anything: STEP 7 V5.6 in SIMATIC Manager, TIA Portal V15.1 for engineering, the matching WinCC Professional V15.1 runtime on the PC station, and a runtime license whose edition covers that station.
Match the configured runtime device version to the runtime actually installed on the PC station, and confirm the license edition covers the station type you configured rather than assuming the engineering package carries it. Take the V5.6-to-TIA pairing for the proxy exchange from support entry 73502293 for your exact releases, not from a forum guess. If a Touch Panel joins the same project, its panel image must match the project version, which Matching an HMI panel image to its TIA Portal project version walks through.
Which stations does this route cover? #
One WinCC Professional V15.1 project covers the mixed case — a Touch Panel and a PC runtime station side by side on the same S7-414H — because each HMI device in the TIA Portal project builds its own S7-300/400 connection to the same Device Proxy.
Panel only, PC only, or both: the route is identical. Decision by case: for a panel-only station, initialize the proxy and connect the panel; for a PC-only SCADA station, connect the WinCC Professional runtime the same way; for the mixed case, build both devices in one TIA Portal project against one proxy so screens, tags and alarms are written once. Do not migrate the H project into TIA Portal, and do not replace the proxy with hand-typed addresses — the proxy is what keeps the two validated projects pointing at each other.
Questions asked
Does the project file for the proxy ever contain more than one controller?
Yes. The initialization can hand you a file with several controllers in it, and the Initialize device proxy dialog is where you choose: select the S7-400H station from the list and assign it to the proxy. If you assign the wrong station, every connection in the HMI project points at the wrong controller data, so check the station name before you confirm.
Does each Touch Panel need its own Device Proxy?
No. One proxy represents the redundant H station for the whole TIA Portal project, and every HMI device in that project builds its own connection to the represented station. Check each device's connection settings separately, because the fail-over behavior a panel delivers depends on the device type and firmware you selected for it.
Can the PLC project stay in STEP 7 V5.6 for good?
Yes, and that split is the point of the arrangement: PLC changes stay in SIMATIC Manager, screen work stays in TIA Portal. One rule follows: when you change the H station's hardware in the V5.x project, swap an interface or change an address, re-run the proxy exchange so the HMI project sees the new controller data instead of stale addresses.
What does the operator see while the CPUs change over?
The runtime keeps showing the last values it received until the connection reports the failure, then shows the connection error state, and returns to live values once the standby CPU answers. Put a diagnostic message or a connection-status bit on the screens so operators see the changeover, and remember that tags neither update nor accept writes during the gap.