Remote panel mirroring versus an independent WinCC runtime
Short answer
Two architectures can put your operator panel on an office PC. Sm@rtServer-style remote panel access mirrors the live panel session with no second project; an independent WinCC runtime shows its own screens and needs engineered connections, tag mapping and its own licensing. A popup on a desktop does not turn either into a SCADA system.
On this page
You can put your S7-300 operator panel on an office PC two ways, and they are not the same architecture. Sm@rtServer-style remote access mirrors the panel's live session: the PC shows exactly what the operator sees, on the panel's screens, driven by the panel's own connection to the CPU. An independent WinCC runtime runs its own project on the PC: its own screens, its own tag list and its own communication connection to the PLC, all engineered separately. Pick the mirror when the requirement is to watch or share the operator's view; pick the independent runtime when the PC must navigate, collect data or grow into a multi-machine system.
What each architecture actually shows #
| Requirement | Remote panel access | Independent WinCC runtime |
|---|---|---|
| See the operator's current screen | Yes, it is the same session | No, the PC shows the PC project's selected screen |
| Reuse the panel's screens | Yes, nothing to engineer | No, screens are rebuilt, converted or re-created |
| Office user navigates independently | No, navigation affects the operator's session | Yes, its own screen hierarchy |
| Office user operates controls | Possible, and it acts at the machine | Possible, through the PC runtime's own tags |
| Central alarms, logging, archiving | No, viewing does not collect data | Yes, with the runtime edition and configuration that provide them |
| Add more machines to one desktop | One remote endpoint per panel | One engineered connection and screen set per machine |
The row that decides most projects is the navigation row. If office staff must look at a screen other than the one the operator is using, the mirror is the wrong tool.
Remote panel mirroring with Sm@rtServer #
Sm@rtServer is the panel's remote-access service. Once it is enabled on the panel, a supported client on the PC connects and the panel session is mirrored; what happens on one side appears on the other. It is a replica requirement solved with a service and a client, not a second HMI project.
Check three things before you commit to it:
- The panel's exact order number and installed software generation, because remote-access support, the permitted client types and the required license are documented per device, not per screen size or touch technology.
- Whether viewing-only is enough. If office access must not operate the machine, configure the client and its permissions so it cannot, and test that during a controlled window with the operator's knowledge.
- The network path. The office PC reaches the panel over the plant network with authenticated access; treat the panel's remote service like any other remote HMI endpoint and keep it off flat, unfiltered networks. If the connection later behaves oddly while the PLC link stays healthy, the usual causes are covered in article:why-hmi-remote-access-fails-while-plc-access-still-works.
The mirror costs engineering time only at the panel and network, and it shows all the panel's tags because it is the panel. What it cannot do is navigate on its own or feed a historian.
What an independent WinCC runtime really requires #
A WinCC runtime on the PC is a separate visualization project, and "WinCC" names a family, not one interchangeable executable. The engineering tool, the target device and the runtime edition must match what you deploy:
- WinCC Advanced runs a PC runtime of the panel class: your own screens and tags, connected to the controller. It does not provide the SCADA-level functions.
- WinCC Professional provides the SCADA functions: client-server architectures, central alarm logging and long-term archiving across stations. Whether a given installation actually carries those functions is a license question, not a software-installed question; article:does-a-wincc-professional-entry-mean-scada-runtime-is-installed walks through telling the two apart.
On the engineering side, the work is:
- Configure a supported communication connection from the PC project to the S7-300, with the CPU's addresses and connection type taken from the existing project, not inferred from screen labels.
- Map the tags the PC must show. The panel's tag list is not the PLC's variable set: internal panel tags, script results and calculated display values have no PLC address and must be re-created or re-derived on the PC.
- Rebuild the screens you need for the PC target and resolve objects that do not transfer from a panel project.
- Test on a bench before the office goes live; article:testing-hmi-simulation-against-a-live-plc gives the test sequence against a real controller.
The limit that decides how many clients the S7-300 accepts #
Every active communication partner occupies one of the CPU's connection resources, and on an S7-300 that total is defined by the CPU, expandable by adding communications processors. PC-type connections get what is left after the resources reserved for S7 standard communication and the other configured services.
Worked example, using the documented figures from Siemens' S7-300 connection example: with the settings used there, the CPU supports a minimum of 4 and a maximum of 6 OP-type connections depending on how its resources are allocated. Say your panel holds one and you want the PC runtime to be a second active partner, leaving room for a programming device. Against a 6-connection allocation you have 4 spare after panel and PC runtime, which is comfortable; against a 4-connection allocation you have 2 spare, which is enough for one engineering station but nothing more. If a later machine pushes the count past the CPU's total, you add a communications processor rather than a new CPU. Count every partner you plan: panel, PC runtime, engineering station, any historian or gateway, then compare against the CPU's documented total and the expansion path.
The same counting applies to adding whole machines later, as covered for a different controller family in the IMDHMI article on two ways to add a second panel to a CODESYS HMI PLC: each new partner consumes resources on its own controller first.
Why a popup is not a SCADA system #
A popup is a display container. Closing it does not define whether the connection underneath keeps updating, whether alarms keep being logged or whether history keeps being collected; those are properties of the connections, tags and logging configuration, and they must be engineered and tested separately. Opening each machine's mirror screen in sequence inside popups on one desktop gives you a screen switcher, not centralized data acquisition: nothing accumulates, nothing alarms centrally, and each popup still needs its own endpoint or connection.
The honest decision rule: a popup over remote panel views is acceptable when the requirement is "look at whichever machine I need right now". The moment the requirement adds "and record alarms and trends from all of them centrally", you need the SCADA-class runtime with engineered connections to every controller, licensed and configured for logging and archiving.
The decision #
- Operator replica, viewing or shared operation, one panel: enable the panel's documented remote-access service, budget its license and a counted connection resource, and configure viewing-only permissions if office staff must not operate.
- Independent navigation from the office: build a WinCC Advanced PC project with its own connection and tag mapping, and count it as a second active partner on the CPU.
- Central data collection or multi-machine growth: WinCC Professional with engineered connections per controller, archived alarms and trends, and per-machine connection-resource budgeting from day one.
One safety note: any path that lets an office PC operate the machine is operator access to that machine. Apply the same access control, permission testing and network segmentation you would require of a physical operator station, and prove the viewing-only configuration on the bench before anyone relies on it.
Questions asked
Can WinCC Advanced be used as a SCADA system?
No. WinCC Advanced runs a PC visualization of the panel type: its own screens, tags and connections to a controller. Functions that define a SCADA application, such as central alarm logging, long-term archiving and client-server scaling across many stations, belong to WinCC Professional. If the office desktop must collect data from several machines, plan on Professional and its licenses from the start.
Does Sm@rtServer use a PLC connection resource on the S7-300?
The mirror itself is panel-to-client traffic, but every device that actively communicates with the CPU occupies one of its connection resources, and the panel already holds one. Before enabling the remote service or adding a PC runtime, count the panel, the remote client and any engineering station against the CPU's documented resource total, and add a communications processor if the count exceeds it.
Will my panel project run unchanged as a WinCC runtime popup on the PC?
Not unchanged. A panel project may contain device-specific screens, scripts and internal tags that a PC target does not accept as transferred. The PC project needs its own communication connection to the PLC, a mapped tag list for the values the PC must show, and screens rebuilt or converted for the PC target. Budget that engineering work; the popup itself is only a display container.
How do I add more machines to the same office desktop later?
Each added machine needs either its own remote panel endpoint, so one desktop session opens one panel view at a time, or its own engineered connection and screens in the central runtime. Either way, each added controller consumes CPU connection resources and network capacity on the machine side. Extend the resource and license budget per machine, not once for the desktop.