Does a WinCC Professional entry mean SCADA runtime is installed

HMI and touchscreens Published 6 min read

Short answer

No. The WinCC Professional line in the TIA Portal version information names the engineering product only. WinCC Runtime Professional is a separate installation with its own license, sized in capacity tiers rather than per-tag fees, so check the installed product list and Automation License Manager entries before you build the project.

On this page
  1. What the version information is telling you
  2. The three checks that settle it
  3. One station or server plus clients
  4. What a fee per tag really means
  5. Example: does the runtime license cover a 2,400-tag application?
  6. Which PC carries the runtime
  7. The decision for each case
  8. Questions asked

No. The WinCC Professional entry in the TIA Portal version information names the engineering product on that PC: the software you configure the project with. It does not tell you that WinCC Runtime Professional, the SCADA runtime that executes the finished application, is installed, and it says nothing about licensing. Runtime is a separate installation with its own license, bought in capacity tiers rather than as a fee per tag. Run three checks before you build the project: the engineering product, the installed runtime, and the runtime license.

What the version information is telling you #

The version information lists the products and components installed with that TIA Portal release. WinCC Professional is the SCADA edition inside TIA Portal: it adds the editors for a PC-based supervisory application, and that application executes on WinCC Runtime Professional. The entry therefore proves the engineering side exists. It carries no information about the runtime side, because the runtime is a product in its own right, installed separately and licensed separately. For where a WinCC system divides its work between configuration and operation, see what WinCC does in an HMI and SCADA system.

Keep the editions straight while you plan. If the job in front of you is a machine-level application rather than a supervisory station, the Advanced path behaves differently — running a TIA Portal V14 HMI on WinCC Runtime Advanced shows what that looks like in practice.

The three checks that settle it #

What you look at What it proves What it does not prove
TIA Portal version information Which engineering products that TIA Portal release installed That any runtime is installed or licensed
Windows installed-programs list WinCC Runtime Professional is present on the PC That the installation is licensed or compatible with the project
Automation License Manager Which licenses exist on the PC and their capacity That the capacity covers the project's counted variables

First, read the complete engineering product name and version in the version information, so the identification rests on a product and version rather than on the single word WinCC. Second, search the Windows installed-programs list for WinCC Runtime Professional and note its version; the engineering release, the runtime release, the operating system and any required extensions have to work together, so compare the combination against the compatibility notes for your release. Third, open Automation License Manager and list the licenses that PC holds. Runtime licenses can arrive on a USB key as well as on the hard disk, and moving a WinCC license from a USB key to the hard disk shows how the manager handles them.

The decision falls straight out of the table. Version information showing WinCC Professional while the installed-programs list has no WinCC Runtime Professional entry means that PC is an engineering seat only, and nothing on it runs the SCADA application until the runtime product is installed and a runtime license of the right capacity sits on it.

One station or server plus clients #

Decide the architecture before any software is ordered, because the roles drive the installation, the licensing and the maintenance plan. A single-user system operates the application on one runtime station. A multi-user system puts the application on a runtime server and serves client stations, so every computer needs the software and the license its role calls for. Moving from one operating station to a server-plus-client layout is a project of its own, and converting a single-user OS to a multi-user server shows what changes on the software side.

You are also choosing between two engineering paths: WinCC Professional inside TIA Portal, and classic WinCC, the Explorer-based 7.x line, outside it. An existing project base usually decides, because projects are maintained where they were created. The differences between the generations are laid out in WinCC V7.4, WinCC Flexible 2008 and TIA Portal compared.

One installation caution: WinCC Unified is a separate runtime family, and running a Unified runtime alongside WinCC Runtime Professional on one PC is restricted, with rules that differ by TIA Portal release, so check the parallel-installation notes for your version before combining them. If a project targets Unified, the PC is set up as a Unified target, which selecting a WinCC Unified PC target in TIA Portal walks through.

What a fee per tag really means #

The per-tag story is a misreading of how this licensing works. WinCC runtime licensing is sold in capacity tiers: the license document defines a counting unit and a tier size, and the tier is the thing you buy, not the individual tag. Engineering and runtime entitlements stay separate as well. An engineering license authorizes development on the workstation, not operation on any PC, and a runtime license authorizes operation at a stated capacity. When a piece is missing, the legitimate path is to buy the product and tier that fit from the vendor or an authorized distributor; an incomplete license is a purchasing decision, never a configuration workaround.

Example: does the runtime license cover a 2,400-tag application? #

Worked example with illustrative counts; your project's tag table and license entry give the real figures.

Inputs:

  • 1,860 external tags: variables that exchange values with the controllers. Source: the project tag table, filtered to external tags.
  • 540 internal tags: variables that exist only inside the application, for screen logic and intermediate values. Source: the same tag table, filtered to internal tags.
  • 2,000 variables: the capacity granted by the example runtime tier. Source: the capacity entry shown for the runtime license; your own license document states yours.
  • 600 tags: growth planned for the next revision. Source: your expansion plan.

Rule in words: read which variables the license document counts, total the variables in that category, add planned growth, and the combined figure must fit inside the tier.

Arithmetic:

  • All tags: 1,860 + 540 = 2,400.
  • Against the 2,000-variable tier: counting external tags only fits, leaving 2,000 − 1,860 = 140 variables of headroom, while counting all tags comes in 2,400 − 2,000 = 400 over.
  • With planned growth: 2,400 + 600 = 3,000 variables to cover.

Result: the counting rule decides the verdict. Counting external tags only, the example fits today; counting every tag, it does not.

Decision: size the tier to the planned count, not to today's figure — 3,000 variables here, so the example needs a tier of at least 3,000 in the documented counting unit. If the counted total exceeds the tier by even one variable, the application is not covered, and the tier goes up before startup.

Which PC carries the runtime #

Runtime Professional executes on a PC, so the last planning question is which hardware sits at the line. The engineering workstation only configures; the operating station runs the application where operators work with it. When that supervisory station needs a touch interface mounted at the machine, industrial panel PCs are the hardware category that carries the runtime or one of its clients. Check the host operating system against the supported list for your release, and settle the runtime version on that station before the hardware is specified.

The decision for each case #

  • The version information shows WinCC Professional and the installed-programs list has no runtime entry: that PC is engineering-only. Install WinCC Runtime Professional there if it must operate the application; otherwise configure on it and run the project on a dedicated station.
  • The runtime is installed but Automation License Manager shows no runtime license: operation is not entitled yet, so buy the product and tier that fit.
  • A runtime license exists but the counted variable total exceeds its tier: raise the tier before startup.
  • The job is a machine-level HMI rather than a supervisory station: use the Advanced path on a PC or a panel-based HMI instead of Professional.
  • The projects to maintain already live in classic WinCC: keep them in their own engineering environment rather than rebuilding them for the sake of it.

Questions asked

How do I tell classic WinCC apart from WinCC Professional in TIA Portal?

Classic WinCC, the 7.x line, stores its projects in its own engineering environment built around WinCC Explorer, and those projects never open inside TIA Portal. A WinCC Professional application is configured inside the TIA Portal project itself and executes on WinCC Runtime Professional. The two paths use different project structures, so the engineering environment a project needs follows from where the project was first created.

Do WinCC Basic, Advanced and Professional target the same devices?

No. WinCC Basic targets entry-level panels, Comfort adds mobile and keypad panels, Advanced adds PC runtime for machine-level HMI applications, and Professional is the SCADA-class PC runtime that supports single-user and multi-user systems. Matching the edition to the target device first keeps engineering and licensing simple, because each edition configures a different set of runtime targets and carries a different feature set.

What happens when the project grows past the licensed tag tier?

The tier is a ceiling on the variables the license document counts, not a usage meter. Once the counted total passes it, the application exceeds what that license covers, and the fix is the next tier up, obtained through the vendor or an authorized distributor. Read the counting rules in the license description first, because a project's total tag count and the counted total are not automatically the same figure.

Does one license cover a development PC and a separate runtime station?

No. The engineering license stays with the workstation that configures the project, and every PC that operates the application needs its own runtime license sized to the variables counted on that station. In a server-and-client layout, the server and the clients are licensed according to their roles. Count each operating computer before you order, and keep the license records with the machines they belong to.

Keep reading

  • Comparison

    WinCC vs WinCC Flexible for small PC SCADA applications

    WinCC Flexible can build a small SCADA application that runs on a PC, but only the Advanced edition does it — Standard stops at operator panels. Treat two decisions separately: the Advanced engineering license buys the PC runtime capability, and each PC that runs the finished application still needs its own runtime license. Beyond single-station scope, the WinCC family is the SCADA tool.

    HMI and touchscreens

  • How-to

    Deploy a WinCC 6.2 Project on a Separate Runtime PC

    Install WinCC 6.2 on both machines: Runtime installs with the same setup, so there are no separate runtime files to carry. License the desktop PC that activates the project, copy the whole project folder to it, register the folder in AutoStart, and build the job as a Single-User Project.

    HMI and touchscreens

  • How-to

    Running a WinCC 7.0 project on another PC without a new build

    No. WinCC has no compile-to-EXE option: the destination PC needs WinCC Runtime of version 7.0 or higher, installed and licensed, and you transfer the project files to it. A newer WinCC opens and converts the project; an older release will not open it.

    HMI and touchscreens

Why WinCC Logging for Runtime Advanced asks for a license