How-to
Selecting a WinCC Unified PC Target in TIA Portal
Short answer
An IPC can host WinCC Unified as a PC-based HMI. If the SIMATIC HMI application list shows only WinCC RT Advanced, your TIA Portal installation is missing the Unified PC engineering option: add a PC station, add the SIMATIC WinCC Unified PC application, then match the runtime version and license on the target computer. The hardware is not the deciding check.
On this page
- What an RT Advanced-only list actually tells you
- The three PC targets and what each one needs
- Adding the SIMATIC WinCC Unified PC target
- Host checks on the target computer
- Entering the runtime PC's address
- Checking subnet reachability for a runtime PC at 192.168.0.10
- Accepting the target on a bench
- The decision for each case
- Questions asked
An IPC can run WinCC Unified as a PC-based HMI. When the SIMATIC HMI application list for a selected IPC offers only WinCC RT Advanced — as in the TIA Portal V16 test project described below — the list is reporting your engineering installation, not the hardware. The Unified PC engineering option is missing or is not being offered through the selection path you used. The decision is therefore software, and it is quick: add a PC station, add the SIMATIC WinCC Unified PC application to it, match the runtime version and license on the target computer, and configure the network address. Cycling through IPC entries in the device catalog will never make a missing application appear.
What an RT Advanced-only list actually tells you #
In the reported case, a simple test project in TIA Portal V16: after selecting the IPC in the device catalog, the SIMATIC HMI application list offered only WinCC RT Advanced. Read that observation for what it is. It happened at the engineering PC, before any download, so it is not a runtime startup failure, not a PLC communication fault and not a measured hardware limit. The catalog entry describes the computer; the application list is the set of HMI applications your installed TIA Portal options can configure on that station. An engineering installation that lacks the Unified PC option shows the same short list under every IPC entry, which is why re-picking catalog entries cannot fix it.
Separate the two possible faults. A missing target is an engineering-station problem: the installed components do not include the Unified PC option, and the fix lives at that workstation. An unsuitable host is a deployment problem: the target computer's operating system and resources must meet the runtime release's documented requirements, and that check runs against the release documentation, not against the application list. Where the Unified runtime can run once installed, including remote client access, is its own subject — the overview of where WinCC Unified runtime can run and the remote HMI options covers it.
Decision: if the list shows only WinCC RT Advanced, treat it as a missing-components question at the engineering PC, never as a verdict on the IPC.
The three PC targets and what each one needs #
TIA Portal offers three PC visualization families in the application list: WinCC Unified (PC), WinCC Advanced and WinCC Professional, with Professional requiring its own installation. The entry you saw — WinCC RT Advanced — is the Advanced family's runtime name; the options list calls the family WinCC Advanced. Advanced is not panel-only: one documented setup runs a TIA Portal V14 HMI on WinCC Runtime Advanced on a PC, so an RT Advanced entry on an IPC is a working PC-HMI target in its own right, just not the Unified one.
| Application entry | Family | Engineering PC needs | Runtime PC needs |
|---|---|---|---|
| WinCC Unified (PC) | Unified | Unified engineering option installed | Unified PC Runtime installed and licensed |
| WinCC RT Advanced | Advanced (listed as WinCC Advanced among the options) | Advanced engineering option | WinCC Runtime Advanced installed and licensed |
| WinCC Professional | Professional | Professional option, a different installation | Professional runtime installed and licensed |
The family boundaries across WinCC generations blur easily; the side-by-side of WinCC Explorer, Advanced, Professional, Flexible and Unified sorts the names out. Decision: one family per target, matched end to end — the application you add must be the family whose runtime the target PC actually runs.
Adding the SIMATIC WinCC Unified PC target #
- Add the station. In TIA Portal, add a new device — a PC station or a compatible IE device — from the device catalog. The IPC entry itself is not what changes; the station type decides which HMI applications can be added to it.
- Add the application. Add the SIMATIC HMI application SIMATIC WinCC Unified PC to that station. Expected result: the project contains a Unified PC target, not an Advanced application standing in for one.
- If only WinCC RT Advanced is offered, install the missing option. Close TIA Portal, install the Unified engineering option from the installation media or download you obtained from the vendor or an authorized distributor, then reopen TIA Portal and check the list again. If the setup itself fails before installing anything — an installer reporting an empty, zero-byte source is a known medium fault — clear that first with the fix for a STEP 7 installation CD that shows 0 bytes, because a damaged medium fails the same way on a healthy PC.
- Record and match versions. Note the engineering version (V16 in the case above; the documented current pairing is Unified V21 with TIA Portal V21) and set the device's configured runtime version to the version actually installed on the target computer.
- Compile small. Build one screen with one tag and compile for the Unified PC target before growing the project. Expected result: a clean compile, proving the engineering side is complete.
Host checks on the target computer #
The application list can never vouch for the computer it names. Three separate checks decide whether the IPC can host the runtime:
- Matching runtime. Unified PC Runtime installed on that computer, at the version the device is configured for.
- License. A runtime authorization for that computer. The engineering option you installed in the steps above is a separate product and a separate install; it licenses nothing on the target.
- Host. Operating system and resources meeting the runtime release's documented requirements. The IPC's own data sheet never answers this; the release documentation does, so the release decides — not the application list.
If the machine-side station still has to be fitted rather than repurposed, the runtime belongs on one of the industrial panel PCs built for touchscreen duty at the machine.
Entering the runtime PC's address #
With the target compiling, communication comes next, and the vendor's communication-settings document for WinCC Unified PC runtime gives the shape of it: enter the full device name of the runtime PC, click Add IP address, and add the device's IP address — the document's example is 192.168.0.10. That document describes the behavior as of TIA Portal V20, so expect the exact dialog to move between releases. The one calculation that decides whether that address works without a router is subnet membership, worked out below.
Checking subnet reachability for a runtime PC at 192.168.0.10 #
Inputs. Runtime PC address 192.168.0.10, the example address in the vendor's communication-settings document. Engineering PC address 192.168.0.51 with subnet mask 255.255.255.0 — illustrative station values, since no site addressing was given; 255.255.255.0 is the standard /24 mask for a machine-network segment.
Rule. Two IPv4 hosts talk directly, with no router in between, when ANDing each address with the subnet mask produces the same network portion. If the portions differ, packets must cross a gateway, and the gateway has to be configured on the sending adapter.
Arithmetic. Engineering PC: 192.168.0.51 AND 255.255.255.0, octet by octet — 192 AND 255 = 192, 168 AND 255 = 168, 0 AND 255 = 0, 51 AND 0 = 0 — giving the network portion 192.168.0.0. Runtime PC: 192.168.0.10 AND 255.255.255.0 gives 192.168.0.0 by the same steps. Compare: 192.168.0.0 equals 192.168.0.0, so both stations sit on the same subnet.
Result. Under a 255.255.255.0 mask the first three octets decide; both stations share 192.168.0, so the engineering PC reaches the runtime directly.
Decision. Network portions equal → enter the full device name, click Add IP address, add 192.168.0.10, and download over the direct link with no gateway entry. Had the engineering PC been addressed 192.168.10.51, its portion 192.168.10.0 would differ from 192.168.0.0 — and any differing network portion means the same thing: align the addressing or configure routing first, before suspecting the runtime or the IPC. Threshold in one line: network portions equal → direct link; network portions differ → route.
Accepting the target on a bench #
Prove the target where a wrong write cannot move anything: an isolated bench controller or a test project, with every tag verified against the controller program before the runtime uses it. Compile, download, start the runtime, and read the station back — it should report the Unified PC application, with no Advanced target standing in for it. Then exercise the basics on the bench: a write to a test tag, a controlled controller disconnect and reconnect, and a runtime restart, watching that values recover and alarms return. Keep the first download off the line controller: a runtime writing to live tags before its tags are verified is how a software test becomes a process upset.
The decision for each case #
- Only WinCC RT Advanced appears under the IPC. The Unified engineering option is missing at the engineering PC. Install it through the vendor or an authorized distributor, confirm the installation media is sound, then add the SIMATIC WinCC Unified PC application to a PC station. The IPC is not the blocker.
- SIMATIC WinCC Unified PC appears. Add it to the PC station, set the device's runtime version to the version installed on the target, and confirm the target has Unified PC Runtime installed, licensed, and meeting the release's host requirements.
- The target compiles but download or online access fails. Check the full device name, the IP address entry, and the subnet decision above before touching hardware.
- Still unsure about the computer itself. The runtime release's documented requirements decide, never the application list.
Questions asked
Does WinCC Unified PC Runtime replace WinCC Runtime Advanced on a PC?
Yes, for PC-based visualization the migration documentation positions WinCC Unified PC Runtime as the successor to WinCC Runtime Advanced. New PC projects should target the Unified PC application, while existing Advanced projects stay in their family. Keep the engineering application and the installed runtime in the same family, because a Unified target will not run under an Advanced runtime or the other way around.
Can one TIA Portal project hold a Unified PC target together with panels?
Yes. A WinCC project may contain HMI devices configured for different runtime versions, so a Unified PC station and panel entries can share one project. Set each device's configured runtime version to the version actually installed on that device before downloading, and confirm the version-compatibility rules for your exact engineering and runtime pairing when the releases differ.
Can I check the Unified PC target before the runtime PC is available?
Yes. The Unified PC runtime can be installed on an engineering or spare PC and used to simulate the device; the V21 pairing is documented for simulating WinCC Unified devices from TIA Portal V21. Simulation proves the target compiles and screens run. It does not prove PLC traffic, so still bench-test writes, disconnects and restarts against real, verified tags.
Why does WinCC Professional not appear under the IPC either?
WinCC Professional is a separate installation from WinCC Advanced and WinCC Unified in TIA Portal. If the Professional entry never appears, that option is missing from the engineering installation too; install it through the same vendor or authorized-distributor channel as the Unified option. Its absence, like the missing Unified entry, says nothing about the IPC hardware.