IMDTouchKnowledge BaseShop main store

How-to

Transfer a WinCC license from USB key to hard disk

HMI and touchscreens Published 6 min read

Short answer

Open Automation License Manager, confirm the USB key and the local disk both appear as drives, right-click each WinCC license on the key and run the License Key > Transfer command to the local disk. A transfer is a managed move, not a file copy: the license must leave the key and appear on the disk with valid status, after which the station no longer needs the key.

On this page
  1. What you are actually moving
  2. Before you start
  3. The transfer, step by step
  4. Worked example: two licenses from one key on a WinCC V7 SP1 station
  5. When the transfer fails or WinCC still asks for a license
  6. Where the license should live
  7. Questions asked

Use the Automation License Manager shipped with your WinCC release: connect the USB license key, open the utility, right-click each WinCC license listed under the key, and run the License Key > Transfer command with the local hard disk as the destination. A transfer is a managed move — the license leaves the key and is written to the disk in one operation — so copying the visible files with Windows Explorer accomplishes nothing. On a WinCC V7 SP1 delivery holding two entitlements, Runtime and Runtime and Configuration, transfer both and check the count on each drive before you unplug the key.

What you are actually moving #

A WinCC license key is an entitlement, not an installable file. Runtime authorizes operating the project, and Runtime and Configuration covers operating and engineering in a single entitlement — the split explained for WinCC RT vs RC licenses and moving a runtime key. Record the installed release before you touch the key: WinCC V6.0 and WinCC V7 SP1 are separate compatibility cases, and each license carries version eligibility that either matches the installed release or does not. In the manager, right-click the top-level License Manager entry and select Flat view to list every license across all drives with its version alongside, which settles eligibility before anything moves. TIA Portal installations hold to the same principle: the license key is installed with the Automation License Manager from the accompanying storage medium, and WinCC options bring their own keys.

Before you start #

  1. Close WinCC and its engineering tool on the station.
  2. Schedule the move outside production, because taking a license off a computer that uses it changes what that computer can run while the key is elsewhere.
  3. Plug the key into the station that will hold the license and open Automation License Manager from the Siemens program group; a current single-license guide opens version 5.3 or newer on the source PC, while a V6.0 or V7 SP1 installation uses the manager version shipped with that release.
  4. Check the drive list for both the key and the local disk. Windows detecting the device proves storage, not license recognition.
  5. Leave the key connected until the transfer finishes.

The transfer, step by step #

  1. Select the USB drive in the manager's drive list; its WinCC licenses appear with identification and status.
  2. Right-click the license you need and choose the transfer command; the menu path is License Key > Transfer.
  3. Set the local hard disk as the destination and run the transfer.
  4. Repeat once per license when the key holds more than one, as the V7 SP1 delivery does for Runtime and Runtime and Configuration.
  5. Reopen or refresh both drive inventories: the moved licenses show on the local disk with usable status, and the key's list reflects a move rather than a duplicate.
  6. If the utility reports an error, record the exact message and inspect both inventories before retrying, because the message alone does not say where the license is now.

Worked example: two licenses from one key on a WinCC V7 SP1 station #

Inputs:

  • Installed software: WinCC V7 SP1, read from the station's version information.
  • License medium: one USB key from the delivery holding two entitlements, WinCC Runtime and WinCC Runtime and Configuration.
  • Function needed: operate and edit on this station, and leave no entitlement on removable media when the key goes into storage.
  • Utility: the Automation License Manager version belonging to that release.

Rule in words: each license key moves as one managed operation from the USB drive to the local disk, and license count is conserved — what leaves the key appears on the disk, one entry per transfer.

The arithmetic:

  • Licenses on the USB key before: 2
  • Licenses on the local disk before: 0
  • Transfers run: 1 + 1 = 2, one per license key
  • Licenses on the USB key after: 0
  • Licenses on the local disk after: 2
  • Conservation check: 2 + 0 = 0 + 2, so the two drives together still hold exactly 2 entitlements.

Result: with 2 licenses on the local disk and 0 on the key, the station starts runtime and opens the editor with the key removed, and the Runtime and Configuration entry alone carries the operating and editing rights.

Decision: do not unplug the key until the disk count equals the number of transfers you ran. Any other pair of numbers — an entry still on the key, or the same entry on both drives — means the move is incomplete or was a copy, and step 6 above applies.

When the transfer fails or WinCC still asks for a license #

Symptom What it separates What to do
USB key missing in Windows Connection or device detection Fix detection first; nothing downstream will work
Key visible in Windows, absent from the manager Utility compatibility or device access Compare the manager version with the release
Drive listed, no license under it Supplied medium or license status Record it for support; do not format or repair the key
Local disk not offered as destination Destination accessibility Read the transfer diagnostic and check disk access
Transfer ends with an error Operation failed partway Inspect both inventories and locate the license before retrying
Licenses display as inactive Windows update side effect Delete the inactive entries in the manager first

One documented case sits behind the last row: after Windows update KB5058411, licenses can display as inactive, and the inactive entries must be deleted in the manager before active licenses can be re-transferred from their source drive.

If the transfer succeeded and WinCC still requests a license, compare the entitlement with the function you started — operating needs a Runtime-capable key, the editor needs one that includes configuration — and re-check version eligibility in Flat view. A request that appeared right after moving a project to a newer release is a compatibility fault rather than a transfer fault; see why WinCC 8.0 runtime deactivates after a V7.5 migration. Never edit license data outside the manager: an unresolved case goes to Siemens support with the WinCC release, the manager version, the license description, both locations and the exact message.

Where the license should live #

On a station that runs daily, the license belongs on the local disk and the emptied key goes into storage — the arrangement the transfer above produces. Leave a license on the key only when it must travel between stations, and then keep the key connected for as long as the software runs. A runtime in a virtual machine is the same decision in another form: pass the key through to the guest and leave it attached, the arrangement covered under running a USB license dongle in VMware for WinCC.

Questions asked

Can I copy the license files from the USB key with Windows Explorer instead?

No. What Explorer shows are the stored files of a managed license; copying them duplicates bytes without moving the authorization, so the station still finds nothing on its local disk. The transfer command in Automation License Manager removes the license from the key and writes it to the destination as one operation, which is the supported way to relocate it.

Can I move the license back to the USB key later?

Yes. The transfer command moves a license between any two storage locations the manager shows, so selecting the local disk as the source and the key as the destination reverses the move. Run it outside production hours, because the station loses that entitlement the moment the move completes.

The two computers cannot be connected. Can the license still be moved?

Yes. The License Key > Offline Transfer command in Automation License Manager moves a license manually by exchanging a start code, a request code and an activation code between the machines. Follow the offline procedure documented for your manager version and keep the codes with the license records until the destination lists the license.

Do I need both the Runtime and the Runtime and Configuration license on one station?

Not necessarily. A station that only operates the project needs the Runtime entitlement; a station where the project is edited needs an entitlement that includes configuration, and Runtime and Configuration already covers operating as well. One combined station is fully licensed by its Runtime and Configuration key alone, so transfer what that station's job requires and keep the second entitlement where another station will use it.

Keep reading

  • Explainer

    WinCC RT vs RC Licenses and Moving a Runtime Key

    RT authorizes running the configured WinCC project; RC (Runtime plus Configuration) is what lets a PC also edit it in WinCC Explorer, and the number in a class such as RT 128 is the external-tag capacity. A license key reaches another PC only through the documented transfer, which removes it from the source machine.

    HMI and touchscreens

  • Troubleshooting

    How WinCC Flexible License Authorization Transfer to a Panel Works

    Transferring authorization to an HMI device moves a license for a panel option package such as SmartService onto the panel, and it is independent of the WinCC flexible installation. The 14-day license transfers only once and is spent. When the unlimited license does not appear at the destination, check whether it is still at the source before transferring again.

    HMI and touchscreens

  • How-to

    Running a WinCC 7.0 project on another PC without a new build

    No. WinCC has no compile-to-EXE option: the destination PC needs WinCC Runtime of version 7.0 or higher, installed and licensed, and you transfer the project files to it. A newer WinCC opens and converts the project; an older release will not open it.

    HMI and touchscreens